Page-verified permit transcription

QTS Investment Properties Manassas LLC

Prince William County, Virginia

QA status VerifiedRelease dated July 29, 2026

EVIDENCE NOTE

What the public record says

A manually verified transcription of equipment groups and permit limits stated in Virginia DEQ permit 74161-5, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.

Primary sourceVirginia DEQ permit document

Virginia Department of Environmental Quality

Open original source ↗

Summary fields cite p. 3, p. 4.

What this record does not establish

The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.

How to read the status

Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.

VERIFIED PERMIT TERMS

Equipment and limits,
kept separate from actual use.

This is a conservative transcription of reviewed permit sections, not an exhaustive legal digest. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.

Permitted equipment

5 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.

ReferenceEquipment / modelCount / ratingFuel / controlsStated operating fieldSource
Gen01-Gen20emergency engine gen-setMTU · 16V4000G83L20 units2250 kW eachdiesel fuel oil unless noted in permitengine design / good operating practiceSee operating-scope tablep. 5
Gen21-Gen52emergency engine gen-setMTU · 20V4000G64S32 units2500 kW eachdiesel fuel oil unless noted in permitengine design / good operating practiceSee operating-scope tablep. 5
Gen53emergency engine gen-setMTU · 12V4000G24S1 units1600 kW eachdiesel fuel oil unless noted in permitengine design / good operating practiceSee operating-scope tablep. 5
Gen54, Gen138 and Gen159emergency engine gen-setCaterpillar · C323 units1250 kW eachdiesel fuel oil unless noted in permitengine design / good operating practiceSee operating-scope tablep. 5
Gen55-Gen137 and Gen139-Gen158emergency engine gen-setMTU / Caterpillar · 16V4000G84S and/or 3516C103 units2250 or 2500 kW eachdiesel fuel oil unless noted in permitengine design / good operating practiceSee operating-scope tablep. 5

Operating scope

Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.

ReferenceLimitBasisSource
Gen01-Gen20500 hours/year per unitall purposesCondition 8.p. 9
Gen01-Gen20100 hours/year per unitscheduled MCRT plus unscheduled maintenance/testing/trainingCondition 8.p. 9
Gen01-Gen20500 hours/year combinedscheduled MCRTCondition 8.p. 9
Gen21-Gen15930 hours/year per unitscheduled MCRTCondition 9.p. 9
Gen21-Gen159500 hours/year per unitall purposesCondition 9.p. 9

Permitted emission limits

45 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.

Inspect 45 transcribed limit rows
ReferencePollutantLimitBasis / scopeSource
Gen01-Gen20NOx as NO2emergency43.0 lb/hrhourlyper unitemergency operationp. 11
Gen01-Gen20COemergency6.6 lb/hrhourlyper unitemergency operationp. 11
Gen01-Gen20VOCemergency1.32 lb/hrhourlyper unitemergency operationp. 11
Gen01-Gen20PMemergency0.59 lb/hrhourlyper unitemergency operationp. 11
Gen01-Gen20PM10emergency0.73 lb/hrhourlyper unitemergency operationp. 11
Gen01-Gen20PM2.5emergency0.73 lb/hrhourlyper unitemergency operationp. 11
Gen21-Gen52NOx as NO2emergency48.6 lb/hrhourlyper unitemergency operationp. 11
Gen21-Gen52COemergency11.84 lb/hrhourlyper unitemergency operationp. 11
Gen21-Gen52VOCemergency2.27 lb/hrhourlyper unitemergency operationp. 11
Gen21-Gen52PMemergency0.94 lb/hrhourlyper unitemergency operationp. 11
Gen21-Gen52PM10emergency1.12 lb/hrhourlyper unitemergency operationp. 11
Gen21-Gen52PM2.5emergency1.12 lb/hrhourlyper unitemergency operationp. 11
Gen53NOx as NO2emergency29.2 lb/hrhourlyper unitemergency operationp. 11
Gen53COemergency5.0 lb/hrhourlyper unitemergency operationp. 11
Gen53VOCemergency1.37 lb/hrhourlyper unitemergency operationp. 11
Gen53PMemergency0.39 lb/hrhourlyper unitemergency operationp. 11
Gen53PM10emergency0.46 lb/hrhourlyper unitemergency operationp. 11
Gen53PM2.5emergency0.46 lb/hrhourlyper unitemergency operationp. 11
Gen54,Gen138,Gen159NOx as NO2emergency24.09 lb/hrhourlyper unitemergency operationp. 11
Gen54,Gen138,Gen159COemergency2.1 lb/hrhourlyper unitemergency operationp. 11
Gen54,Gen138,Gen159VOCemergency0.4 lb/hrhourlyper unitemergency operationp. 11
Gen54,Gen138,Gen159PMemergency0.24 lb/hrhourlyper unitemergency operationp. 11
Gen54,Gen138,Gen159PM10emergency0.27 lb/hrhourlyper unitemergency operationp. 11
Gen54,Gen138,Gen159PM2.5emergency0.27 lb/hrhourlyper unitemergency operationp. 11
Gen55-Gen137,Gen139-Gen158 / Caterpillar 3516CNOx as NO2emergency48.06 lb/hrhourlyper unitemergency operationp. 11
Gen55-Gen137,Gen139-Gen158 / Caterpillar 3516CCOemergency6.09 lb/hrhourlyper unitemergency operationp. 11
Gen55-Gen137,Gen139-Gen158 / Caterpillar 3516CVOCemergency1.21 lb/hrhourlyper unitemergency operationp. 11
Gen55-Gen137,Gen139-Gen158 / Caterpillar 3516CPMemergency0.4 lb/hrhourlyper unitemergency operationp. 11
Gen55-Gen137,Gen139-Gen158 / Caterpillar 3516CPM10emergency0.59 lb/hrhourlyper unitemergency operationp. 11
Gen55-Gen137,Gen139-Gen158 / Caterpillar 3516CPM2.5emergency0.59 lb/hrhourlyper unitemergency operationp. 11
Gen55-Gen137,Gen139-Gen158 / MTU 16V4000G84SNOx as NO2emergency44.35 lb/hrhourlyper unitemergency operationp. 11
Gen55-Gen137,Gen139-Gen158 / MTU 16V4000G84SCOemergency9.37 lb/hrhourlyper unitemergency operationp. 11
Gen55-Gen137,Gen139-Gen158 / MTU 16V4000G84SVOCemergency2.2 lb/hrhourlyper unitemergency operationp. 11
Gen55-Gen137,Gen139-Gen158 / MTU 16V4000G84SPMemergency0.78 lb/hrhourlyper unitemergency operationp. 11
Gen55-Gen137,Gen139-Gen158 / MTU 16V4000G84SPM10emergency0.92 lb/hrhourlyper unitemergency operationp. 11
Gen55-Gen137,Gen139-Gen158 / MTU 16V4000G84SPM2.5emergency0.92 lb/hrhourlyper unitemergency operationp. 11
Gen01-Gen159NOx as NO2facility-wide98.09 tpyannualall units combinedall purposesp. 12
Gen01-Gen159COfacility-wide51.14 tpyannualall units combinedall purposesp. 12
Gen01-Gen159VOCfacility-wide17.95 tpyannualall units combinedall purposesp. 12
Gen01-Gen159PMfacility-wide5.37 tpyannualall units combinedall purposesp. 12
Gen01-Gen159PM10facility-wide5.73 tpyannualall units combinedall purposesp. 12
Gen01-Gen159PM2.5facility-wide5.73 tpyannualall units combinedall purposesp. 12
Gen01-Gen159visible emissionsstated opacity limit5 percent opacityvisibleper exhaust/sourcenormal operationp. 12
Gen01-Gen159visible emissionsstated opacity limit10 percent opacityvisibleper exhaust/sourceone six-minute period in any one hour; also startup/shutdown baselinep. 12
Gen01-Gen159visible emissionsstated opacity limit20 percent opacityvisibleper exhaust/sourceone six-minute period in any one hour during startup/shutdownp. 12

DOCUMENT HISTORY

What this document says it changes

combined minor NSR permit

Explicitly supersedes the document dated 2024-10-01.

p. 3, p. 4

QA NOTES

Ambiguity stays visible

  • Transcribed from exact official PDF; source page is 1-based PDF position.
← Return to evidence index