Page-verified permit transcription

Amazon Data Services IAD-870

Spotsylvania County, Virginia

QA status VerifiedRelease dated July 29, 2026

EVIDENCE NOTE

What the public record says

A manually verified transcription of equipment groups and permit limits stated in Virginia DEQ permit 74329-2, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.

Primary sourceVirginia DEQ permit document

Virginia Department of Environmental Quality

Open original source ↗

Summary fields cite p. 3, p. 4.

What this record does not establish

The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.

How to read the status

Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.

VERIFIED PERMIT TERMS

Equipment and limits,
kept separate from actual use.

This is a conservative transcription of reviewed permit sections, not an exhaustive legal digest. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.

Permitted equipment

3 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.

ReferenceEquipment / modelCount / ratingFuel / controlsStated operating fieldSource
EG-01 through EG-192non-emergency engine gen-setMTU · 20V4000G74S / generator 20V4000 DS2800192 units2750 kW eachdiesel fuel oil unless noted in permitSCR and cDPFSee operating-scope tablep. 5
AWB-01 and AWB-02emergency engine gen-setMTU · 12V1600G91S / generator 12V1600 DS9002 units900 kW eachdiesel fuel oil unless noted in permitnoneSee operating-scope tablep. 5
HS-01 and HS-02emergency engine gen-setMTU · 16V2000G86S / generator 16V2000 DS7502 units750 kW eachdiesel fuel oil unless noted in permitnone; de-ratedSee operating-scope tablep. 5

Operating scope

Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.

ReferenceLimitBasisSource
AWB-01, AWB-02, HS-01, HS-02500 hours/year per unitall emergency purposesCondition 11.p. 10
AWB-01, AWB-02, HS-01, HS-0235 hours/year per unitscheduled MCRTCondition 11.p. 10
EG-01 through EG-192No numeric value statedno numeric annual hour cap located for non-emergency unitsOperation bounded by fuel-throughput equation and other conditions; no numeric hour cap transcribed.p. 11

Permitted emission limits

32 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.

Inspect 32 transcribed limit rows
ReferencePollutantLimitBasis / scopeSource
AWB-01,AWB-02 / MTU 12V1600 DS900NOx as NO2emergency16.82 lb/hrhourlyper unitemergency operationp. 12
AWB-01,AWB-02 / MTU 12V1600 DS900PMemergency0.14 lb/hrhourlyper unitemergency operationp. 12
AWB-01,AWB-02 / MTU 12V1600 DS900PM10emergency0.17 lb/hrhourlyper unitemergency operationp. 12
AWB-01,AWB-02 / MTU 12V1600 DS900PM2.5emergency0.17 lb/hrhourlyper unitemergency operationp. 12
AWB-01,AWB-02 / MTU 12V1600 DS900COemergency3.67 lb/hrhourlyper unitemergency operationp. 12
AWB-01,AWB-02 / MTU 12V1600 DS900VOCemergency0.66 lb/hrhourlyper unitemergency operationp. 12
AWB-01,AWB-02 / MTU 12V1600 DS900SO2emergency0.01 lb/hrhourlyper unitemergency operationp. 12
HS-01,HS-02 / MTU 16V2000 DS750NOx as NO2emergency13.28 lb/hrhourlyper unitemergency operationp. 12
HS-01,HS-02 / MTU 16V2000 DS750PMemergency0.16 lb/hrhourlyper unitemergency operationp. 12
HS-01,HS-02 / MTU 16V2000 DS750PM10emergency0.21 lb/hrhourlyper unitemergency operationp. 12
HS-01,HS-02 / MTU 16V2000 DS750PM2.5emergency0.21 lb/hrhourlyper unitemergency operationp. 12
HS-01,HS-02 / MTU 16V2000 DS750COemergency2.38 lb/hrhourlyper unitemergency operationp. 12
HS-01,HS-02 / MTU 16V2000 DS750VOCemergency0.71 lb/hrhourlyper unitemergency operationp. 12
HS-01,HS-02 / MTU 16V2000 DS750SO2emergency0.01 lb/hrhourlyper unitemergency operationp. 12
EG-01 through EG-192 / MTU 20V4000 DS2800NOx as NO2SCR controlled4.48 lb/hrhourlyper unitnon-emergency operationp. 12
EG-01 through EG-192 / MTU 20V4000 DS2800NOx as NO2uncontrolled53.36 lb/hrhourlyper unitnon-emergency operationp. 12
EG-01 through EG-192 / MTU 20V4000 DS2800PMcDPF controlled0.19 lb/hrhourlyper unitnon-emergency operationp. 12
EG-01 through EG-192 / MTU 20V4000 DS2800PM10cDPF controlled0.38 lb/hrhourlyper unitnon-emergency operationp. 12
EG-01 through EG-192 / MTU 20V4000 DS2800PM2.5cDPF controlled0.38 lb/hrhourlyper unitnon-emergency operationp. 12
EG-01 through EG-192 / MTU 20V4000 DS2800COcDPF controlled2.67 lb/hrhourlyper unitnon-emergency operationp. 12
EG-01 through EG-192 / MTU 20V4000 DS2800VOCcDPF controlled1.18 lb/hrhourlyper unitnon-emergency operationp. 12
EG-01 through EG-192 / MTU 20V4000 DS2800SO2stated limit0.04 lb/hrhourlyper unitnon-emergency operationp. 12
all unitsNOx as NO2all operations94.05 tpyannualall units combinedall purposesp. 13
all unitsPMall operations6.33 tpyannualall units combinedall purposesp. 13
all unitsPM10all operations10.45 tpyannualall units combinedall purposesp. 13
all unitsPM2.5all operations10.45 tpyannualall units combinedall purposesp. 13
all unitsCOall operations76.99 tpyannualall units combinedall purposesp. 13
all unitsVOCall operations88.32 tpyannualall units combinedall purposesp. 13
all unitsSO2all operations0.81 tpyannualall units combinedall purposesp. 13
all unitsvisible emissionsstated opacity limit5 percent opacityvisibleper exhaust/sourcenormal operationp. 13
all unitsvisible emissionsstated opacity limit10 percent opacityvisibleper exhaust/sourceemergency one six-minute exception; also startup/shutdown baselinep. 13
all unitsvisible emissionsstated opacity limit20 percent opacityvisibleper exhaust/sourceone six-minute period in any one hour during startup/shutdownp. 13

DOCUMENT HISTORY

What this document says it changes

new minor NSR permit

No superseded-document date is asserted beyond the cited source wording.

p. 3, p. 4

QA NOTES

Ambiguity stays visible

  • Transcribed from exact official PDF; source page is 1-based PDF position.
← Return to evidence index