Page-cited permit extraction

Amazon Data Services Inc IAD-205/307/317/612/612x

Manassas City, Virginia

QA status Machine-extractedRelease dated July 29, 2026

EVIDENCE NOTE

What the public record says

A machine-extracted candidate of equipment groups and permit limits stated in Virginia DEQ permit 74317-1, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.

Primary sourceVirginia DEQ permit document

Virginia Department of Environmental Quality

Open original source ↗

Summary fields cite p. 1, p. 3.

What this record does not establish

The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.

How to read the status

Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.

MACHINE-EXTRACTED CANDIDATE

Equipment and limits,
kept separate from actual use.

These page-cited rows are machine-extracted and still require a second manual review. Verify every reused value against the linked official PDF. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.

Permitted equipment

8 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.

ReferenceEquipment / modelCount / ratingFuel / controlsStated operating fieldSource
1 through 22emergency engine generator setMTU · 16V4000G94S22 units2500 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
23 through 48non-emergency engine generator setMTU · 20V4000G74S26 units2750 kW eachdiesel fuel oilselective catalytic reduction (SCR); diesel particulate filterSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
49 through 74emergency engine generator setCummins · QSK78-G36 non-26 units2750 kW eachdiesel fuel oilselective catalytic reduction (SCR); diesel particulate filterSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
75emergency engine generator setMTU · 12V1600G80S1 units600 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
76emergency engine generator setMTU · 16V2000G86S1 units1000 or 750 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
77emergency engine generator setCummins · QST30-G51 units750 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
78 and 79emergency engine generator setCaterpillar · 3512C2 units1600 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
T1 and T2emergency engine generator setCaterpillar · 3516C2 units2000 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.

Operating scope

Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.

ReferenceLimitBasisSource
1 through 22, 75 through 79, T1, and T2500 hours/yearunit (which involves fuel combustion) shall be minimized to the maximum extent practical. (9VAC5-80-1180) [8/28/2025] 11. Operating Hours – a. Each emergency diesel engine gen-set (Ref. Nos. 1 through 22, 75 through 79, T1, and T2) shall not operate more than 500 hours per year for all purposes (as provided in Condition 7) combined. b. Each emergency diesel engine gen-set (Ref. Nos. 1 through 22, 75 through 79, T1, and T2) shall not operate more than 35 hours per year for Scheduled MCRT (as prMachine-extracted normative operating-hours statement; second review pending.p. 10
1 through 22, 75 through 79, T1, and T235 hours/yearrough 22, 75 through 79, T1, and T2) shall not operate more than 500 hours per year for all purposes (as provided in Condition 7) combined. b. Each emergency diesel engine gen-set (Ref. Nos. 1 through 22, 75 through 79, T1, and T2) shall not operate more than 35 hours per year for Scheduled MCRT (as provided in Condition 7.c). The annual limits for hours of operation shall be calculated monthly as the sum of each consecutive 12-month period. Compliance for the consecutive 12-month period shalMachine-extracted normative operating-hours statement; second review pending.p. 10

Permitted emission limits

68 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.

Inspect 68 transcribed limit rows
ReferencePollutantLimitBasis / scopeSource
MTU 16V4000 Ref. Nos. 1 through 22NOx as NO247.77 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 12V1600 Ref. No. 75NOx as NO211.53 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 16V2000 Ref. No. 76NOx as NO213.29 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 16V4000 Ref. Nos. 1 through 22PM0.68 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 12V1600 Ref. No. 75PM0.19 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 16V2000 Ref. No. 76PM0.16 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 16V4000 Ref. Nos. 1 through 22PM100.68 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 12V1600 Ref. No. 75PM100.19 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 16V2000 Ref. No. 76PM100.16 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 16V4000 Ref. Nos. 1 through 22PM2.50.68 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 12V1600 Ref. No. 75PM2.50.19 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 16V2000 Ref. No. 76PM2.50.16 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 16V4000 Ref. Nos. 1 through 22NOx as NO29.81 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 12V1600 Ref. No. 75NOx as NO21.04 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 16V2000 Ref. No. 76NOx as NO22.38 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 16V4000 Ref. Nos. 1 through 22VOC1.70 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 12V1600 Ref. No. 75VOC0.42 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 16V2000 Ref. No. 76VOC0.71 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 16V4000 Ref. Nos. 1 through 22SO20.04 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 12V1600 Ref. No. 75SO20.01 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 16V2000 Ref. No. 76SO20.01 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins QST30 Ref. No. 77NOx as NO211.88 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
CAT 3512C Ref. Nos. 78 and 79NOx as NO230.75 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
CAT 3516C Ref. Nos. T1 and T2NOx as NO238.85 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins QST30 Ref. No. 77PM0.47 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
CAT 3512C Ref. Nos. 78 and 79PM0.44 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
CAT 3516C Ref. Nos. T1 and T2PM0.57 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins QST30 Ref. No. 77PM100.47 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
CAT 3512C Ref. Nos. 78 and 79PM100.44 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
CAT 3516C Ref. Nos. T1 and T2PM100.57 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins QST30 Ref. No. 77PM2.50.47 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
CAT 3512C Ref. Nos. 78 and 79PM2.50.44 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
CAT 3516C Ref. Nos. T1 and T2PM2.50.57 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins QST30 Ref. No. 77NOx as NO22.37 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
CAT 3512C Ref. Nos. 78 and 79NOx as NO25.78 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
CAT 3516C Ref. Nos. T1 and T2NOx as NO23.95 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins QST30 Ref. No. 77VOC0.35 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
CAT 3512C Ref. Nos. 78 and 79VOC0.87 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
CAT 3516C Ref. Nos. T1 and T2VOC1.14 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins QST30 Ref. No. 77SO20.01 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
CAT 3512C Ref. Nos. 78 and 79SO20.02 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
CAT 3516C Ref. Nos. T1 and T2SO20.03 lb/hrhourlyp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 20V4000 (Ref. Nos. 23 through 48) Uncontrolled by SCRNOx as NO2uncontrolled53.30 lb/hrhourlyp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
Controlled by SCRNOx as NO2controlled4.48 lb/hrhourlyp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins QSK78 (Ref. Nos. 49 through 74)NOx as NO251.51 lb/hrhourlyp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
Controlled by SCRNOx as NO2controlled4.46 lb/hrhourlyp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 20V4000 (Ref. Nos. 23 through 48) Uncontrolled by SCRPMuncontrolled0.20 lb/hrhourlyp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins QSK78 (Ref. Nos. 49 through 74)PM0.14 lb/hrhourlyp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 20V4000 (Ref. Nos. 23 through 48) Uncontrolled by SCRPM10uncontrolled0.20 lb/hrhourlyp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins QSK78 (Ref. Nos. 49 through 74)PM100.14 lb/hrhourlyp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 20V4000 (Ref. Nos. 23 through 48) Uncontrolled by SCRPM2.5uncontrolled0.20 lb/hrhourlyp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins QSK78 (Ref. Nos. 49 through 74)PM2.50.14 lb/hrhourlyp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 20V4000 (Ref. Nos. 23 through 48) Uncontrolled by SCRNOx as NO2uncontrolled3.11 lb/hrhourlyp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins QSK78 (Ref. Nos. 49 through 74)NOx as NO20.36 lb/hrhourlyp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 20V4000 (Ref. Nos. 23 through 48) Uncontrolled by SCRVOCuncontrolled0.80 lb/hrhourlyp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins QSK78 (Ref. Nos. 49 through 74)VOC0.36 lb/hrhourlyp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 20V4000 (Ref. Nos. 23 through 48) Uncontrolled by SCRSO2uncontrolled0.04 lb/hrhourlyp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins QSK78 (Ref. Nos. 49 through 74)SO20.04 lb/hrhourlyp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
All Units Ref. Nos. 1 through 79, T1, and T2NOx as NO294.77 tpyannualcombinedp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
All Units Ref. Nos. 1 through 79, T1, and T2PM4.44 tpyannualcombinedp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
All Units Ref. Nos. 1 through 79, T1, and T2PM104.44 tpyannualcombinedp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
All Units Ref. Nos. 1 through 79, T1, and T2PM2.54.44 tpyannualcombinedp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
All Units Ref. Nos. 1 through 79, T1, and T2NOx as NO265.33 tpyannualcombinedp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
All Units Ref. Nos. 1 through 79, T1, and T2VOC16.82 tpyannualcombinedp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
All Units Ref. Nos. 1 through 79, T1, and T2SO20.90 tpyannualcombinedp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
visible emissions5 percent opacityvisiblep. 15Machine-extracted from a page line in an older official PDF; literal context: 18. Visible Emission Limit – a. Visible emissions from each non-emergency engine gen-set (Ref. Nos. 23 through 74) shall not exceed 5% opacity as determined by EPA Method 9 (reference 40 CFR 60, Appendix A). This requirement applies at all times except during startup, shutdown
visible emissions10 percent opacityvisiblep. 15Machine-extracted from a page line in an older official PDF; literal context: b. Visible emissions from each emergency engine gen-set (Ref. Nos. 1 through 22, 75 through 79, T1, and T2) shall not exceed 5% opacity except during one six-minute period in any one hour in which visible emissions shall not exceed 10% opacity as determined by the EPA Method 9 (reference 40 CFR 60, Appendix A). This
visible emissions20 percent opacityvisiblep. 15Machine-extracted from a page line in an older official PDF; literal context: During startup and shutdown, visible emissions from each engine gen-set shall not exceed 10% opacity except during one (1) six-minute period in any one-hour in which visible emissions shall not exceed 20% opacity as determined by EPA Method 9 (reference 40 CFR 60, Appendix A).

DOCUMENT HISTORY

What this document says it changes

permit to construct and operate

No superseded-document date is asserted beyond the cited source wording.

p. 1, p. 3

QA NOTES

Ambiguity stays visible

  • Machine-extracted candidate. Verify every reused value against the cited official PDF page.
  • Verify table column grouping and any alternative models.
  • Confirm whether the limit is per unit, combined, or limited to testing/maintenance.
  • Confirm multi-row and merged-column header association.
  • Older-PDF text fallback; verify row and unit alignment.
← Return to evidence index