Page-cited permit extraction

Amazon Data Services Inc IAD-350

Stafford Co., Virginia

QA status Machine-extractedRelease dated July 29, 2026

EVIDENCE NOTE

What the public record says

A machine-extracted candidate of equipment groups and permit limits stated in Virginia DEQ permit 74309-1, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.

Primary sourceVirginia DEQ permit document

Virginia Department of Environmental Quality

Open original source ↗

Summary fields cite p. 1, p. 3.

What this record does not establish

The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.

How to read the status

Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.

MACHINE-EXTRACTED CANDIDATE

Equipment and limits,
kept separate from actual use.

These page-cited rows are machine-extracted and still require a second manual review. Verify every reused value against the linked official PDF. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.

Permitted equipment

3 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.

ReferenceEquipment / modelCount / ratingFuel / controlsStated operating fieldSource
EG-01 through EG- 48emergency engine generator setCummins · QSK78-G3648 units2750 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
HS-01 and HS-02emergency engine generator setCummins · QST30-G52 units750 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
Pollutantengine generator set1 unitsNo reliable per-unit rating transcribedSee operating-scope tablep. 10Machine-extracted from an official document equipment table; column grouping requires second review.

Operating scope

Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.

ReferenceLimitBasisSource
EG-01 through EG-48, HS-01, and HS-0235 hours/year(which involves fuel combustion) shall be minimized to the maximum extent practical. (9VAC5-80-1180) [3/27/2025] 7. Operating Hours – Each individual emergency diesel engine gen-set (Ref. Nos. EG-01 through EG-48, HS-01, and HS-02) shall not operate more than 35 hours per year for scheduled maintenance checks and readiness testing (Scheduled MCRT, as provided in Condition 3.c). Each individual emergency diesel engine gen-set (Ref. Nos. EG-01 through EG-48, HS-01, and HS-02) shall not operateMachine-extracted normative operating-hours statement; second review pending.p. 8
EG-01 through EG-48, HS-01, and HS-02500 hours/yearte more than 35 hours per year for scheduled maintenance checks and readiness testing (Scheduled MCRT, as provided in Condition 3.c). Each individual emergency diesel engine gen-set (Ref. Nos. EG-01 through EG-48, HS-01, and HS-02) shall not operate more than 500 hours per year for all purposes (as provided in Condition 3) combined. The annual limits for hours of operation shall be calculated monthly as the sum of each consecutive 12-month period. Compliance for the consecutive 12-month periodMachine-extracted normative operating-hours statement; second review pending.p. 8

Permitted emission limits

18 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.

Inspect 18 transcribed limit rows
ReferencePollutantLimitBasis / scopeSource
Cummins QSK78-G36 (Ref. Nos. EG-01 through EG-48)NOx as NO251.15 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins QST30-G5 (Ref. Nos. HS-01 and HS-02)NOx as NO211.88 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins QSK78-G36 (Ref. Nos. EG-01 through EG-48)NOx as NO23.65 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins QST30-G5 (Ref. Nos. HS-01 and HS-02)NOx as NO22.37 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins QSK78-G36 (Ref. Nos. EG-01 through EG-48)VOC1.14 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins QST30-G5 (Ref. Nos. HS-01 and HS-02)VOC0.35 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins QSK78-G36 (Ref. Nos. EG-01 through EG-48)PM100.43 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins QST30-G5 (Ref. Nos. HS-01 and HS-02)PM100.53 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins QSK78-G36 (Ref. Nos. EG-01 through EG-48)PM2.50.43 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins QST30-G5 (Ref. Nos. HS-01 and HS-02)PM2.50.53 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
All Engine Gen-Sets (Ref. Nos. EG-01 through EG-48, HS-01, and HS-02)NOx as NO294.68 tpyannualcombinedp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
All Engine Gen-Sets (Ref. Nos. EG-01 through EG-48, HS-01, and HS-02)NOx as NO236.61 tpyannualcombinedp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
All Engine Gen-Sets (Ref. Nos. EG-01 through EG-48, HS-01, and HS-02)VOC11.00 tpyannualcombinedp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
All Engine Gen-Sets (Ref. Nos. EG-01 through EG-48, HS-01, and HS-02)PM102.59 tpyannualcombinedp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
All Engine Gen-Sets (Ref. Nos. EG-01 through EG-48, HS-01, and HS-02)PM2.52.59 tpyannualcombinedp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
visible emissions5 percent opacityvisiblep. 11Machine-extracted from a page line in an older official PDF; literal context: (9VAC5-80-1180) [3/27/2025] 13. Visible Emission Limit – Visible emissions from each emergency diesel engine gen-set (Ref. Nos. EG-01 through EG-48, HS-01, and HS-02) exhaust shall not exceed 5% opacity except during one (1) six-minute period in any one-hour in which visible emissions shall
visible emissions10 percent opacityvisiblep. 11Machine-extracted from a page line in an older official PDF; literal context: (Ref. Nos. EG-01 through EG-48, HS-01, and HS-02) exhaust shall not exceed 5% opacity except during one (1) six-minute period in any one-hour in which visible emissions shall not exceed 10% opacity as determined by EPA Method 9 (reference 40 CFR 60, Appendix A). This condition applies at all times except during startup, shutdown and malfunction.
visible emissions20 percent opacityvisiblep. 11Machine-extracted from a page line in an older official PDF; literal context: During startup and shutdown, visible emissions from each emergency diesel engine gen-set shall not exceed 10% opacity except during one (1) six-minute period in any one-hour in which visible emissions shall not exceed 20% opacity as determined by EPA Method 9 (reference 40 CFR 60, Appendix A).

DOCUMENT HISTORY

What this document says it changes

permit to construct and operate

No superseded-document date is asserted beyond the cited source wording.

p. 1, p. 3

QA NOTES

Ambiguity stays visible

  • Machine-extracted candidate. Verify every reused value against the cited official PDF page.
  • Verify table column grouping and any alternative models.
  • Confirm whether the limit is per unit, combined, or limited to testing/maintenance.
  • Confirm multi-row and merged-column header association.
  • Older-PDF text fallback; verify row and unit alignment.