Page-verified permit transcription

Amazon Data Services, Inc. IAD-51 IAD-56 IAD-88 IAD-89

Loudoun County, Virginia

QA status VerifiedRelease dated July 29, 2026

EVIDENCE NOTE

What the public record says

A manually verified transcription of equipment groups and permit limits stated in Virginia DEQ permit 74063-5, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.

Primary sourceVirginia DEQ permit document

Virginia Department of Environmental Quality

Open original source ↗

Summary fields cite p. 1, p. 3.

What this record does not establish

The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.

How to read the status

Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.

VERIFIED PERMIT TERMS

Equipment and limits,
kept separate from actual use.

This is a conservative transcription of reviewed permit sections, not an exhaustive legal digest. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.

Permitted equipment

10 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.

ReferenceEquipment / modelCount / ratingFuel / controlsStated operating fieldSource
D1-D22emergency engine-generator setCaterpillar · 3516E22 units2750 kW eachdieselSCR+cDPF500 hourshours/year for all purposes; no single unitp. 5, p. 10
L3-L4; L19-L21; L29; L38emergency engine-generator setCaterpillar · 3516C-HD7 units2500 kW eachdiesel500 hourshours/year for all purposes; no single unitp. 5, p. 10
H2emergency engine-generator setCaterpillar · C181 units600 kW eachdiesel500 hourshours/year for all purposes; no single unitp. 5, p. 10
L5-L18; L22-L28; L30-L37emergency engine-generator setCaterpillar · 3516C-HD36 units2500 kW eachdiesel500 hourshours/year for all purposes; no single unitp. 5, p. 10
L1-L2emergency engine-generator setCaterpillar · 3516C-HD2 units2500 kW eachdiesel500 hourshours/year for all purposes; no single unitp. 5, p. 10
M1-M16emergency engine-generator setCaterpillar · 3516C16 units2000 kW eachdiesel500 hourshours/year for all purposes; no single unitp. 5, p. 10
L39-L64emergency engine-generator setCaterpillar · 3516C-HD26 units2500 kW eachdiesel500 hourshours/year for all purposes; no single unitp. 5, p. 10
H1emergency engine-generator setCaterpillar · C181 units600 kW eachdiesel500 hourshours/year for all purposes; no single unitp. 5, p. 10
T1-T4emergency engine-generator setCaterpillar · 3516C4 units2000 kW eachdiesel500 hourshours/year for all purposes; no single unitp. 6, p. 10
T5-T8emergency engine-generator setCaterpillar · 3516C4 units2000 kW eachdiesel500 hourshours/year for all purposes; no single unitp. 6, p. 10

Operating scope

Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.

ReferenceLimitBasisSource
D1-D22500 hours/yearhours/year for all purposes; no single unitPermitted operating-hours field transcribed in the verified pilot equipment table.p. 5, p. 10
L3-L4; L19-L21; L29; L38500 hours/yearhours/year for all purposes; no single unitPermitted operating-hours field transcribed in the verified pilot equipment table.p. 5, p. 10
H2500 hours/yearhours/year for all purposes; no single unitPermitted operating-hours field transcribed in the verified pilot equipment table.p. 5, p. 10
L5-L18; L22-L28; L30-L37500 hours/yearhours/year for all purposes; no single unitPermitted operating-hours field transcribed in the verified pilot equipment table.p. 5, p. 10
L1-L2500 hours/yearhours/year for all purposes; no single unitPermitted operating-hours field transcribed in the verified pilot equipment table.p. 5, p. 10
M1-M16500 hours/yearhours/year for all purposes; no single unitPermitted operating-hours field transcribed in the verified pilot equipment table.p. 5, p. 10
L39-L64500 hours/yearhours/year for all purposes; no single unitPermitted operating-hours field transcribed in the verified pilot equipment table.p. 5, p. 10
H1500 hours/yearhours/year for all purposes; no single unitPermitted operating-hours field transcribed in the verified pilot equipment table.p. 5, p. 10
T1-T4500 hours/yearhours/year for all purposes; no single unitPermitted operating-hours field transcribed in the verified pilot equipment table.p. 6, p. 10
T5-T8500 hours/yearhours/year for all purposes; no single unitPermitted operating-hours field transcribed in the verified pilot equipment table.p. 6, p. 10

Permitted emission limits

1 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.

Inspect 1 transcribed limit rows
ReferencePollutantLimitBasis / scopeSource
D1-D22opacity5 percentvisible-emission limitper unitp. 13

DOCUMENT HISTORY

What this document says it changes

significant amendment

Explicitly supersedes the document dated 2024-05-28.

p. 1, p. 3

QA NOTES

Ambiguity stays visible

  • Official PDF cover/permit heading checked in the manual second pass.
  • Value transcribed from official permit equipment/condition table; no totals calculated.
  • Directly stated permitted limit; not an actual emissions value.
← Return to evidence index