Page-cited permit extraction

Chantilly Technology Partners, LLC/H5 VA

Fairfax Co., Virginia

QA status Machine-extractedRelease dated July 29, 2026

EVIDENCE NOTE

What the public record says

A machine-extracted candidate of equipment groups and permit limits stated in Virginia DEQ permit 72375-9, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.

Primary sourceVirginia DEQ permit document

Virginia Department of Environmental Quality

Open original source ↗

Summary fields cite p. 1, p. 3.

What this record does not establish

The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.

How to read the status

Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.

MACHINE-EXTRACTED CANDIDATE

Equipment and limits,
kept separate from actual use.

These page-cited rows are machine-extracted and still require a second manual review. Verify every reused value against the linked official PDF. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.

Permitted equipment

6 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.

ReferenceEquipment / modelCount / ratingFuel / controlsStated operating fieldSource
IAD32-Gen4 and IAD32- Gen5emergency engine generator setMitsubishi2 units2000 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
A-G1 through A-G3emergency engine generator setCaterpillar · 3516B3 units2000 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
B-EG1 through B-EG4emergency engine generator setCummins · model 24 units2000 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
B-EG105emergency engine generator setCummins · 275DQHAA1 units275 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
C110-GB, C120-GB, and C-GRemergency engine generator setCummins · 2000DQKAB3 units2000 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
C-House Genemergency engine generator setCummins · 275DQHAA1 units275 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.

Operating scope

Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.

ReferenceLimitBasisSource
A-G1 through A-G3240 hours/yeared on-site and ending when the affected unit is fully integrated with the source’s electrical system. (9VAC5-80-1180) [3/10/2026] 5. Operating Hours – a. The emergency diesel engine gen-sets (Ref. Nos. A-G1 through A-G3), combined, shall not operate more than 240 hours per year for all purposes (as provided in Condition 4). b. The emergency diesel engine gen-sets (Ref. Nos. B-EG1 through B-EG4), combined, shall not operate more than 320 hours per year for all purposes (as provided in ConditionMachine-extracted normative operating-hours statement; second review pending.p. 8
A-G1 through A-G3320 hours/yeargine gen-sets (Ref. Nos. A-G1 through A-G3), combined, shall not operate more than 240 hours per year for all purposes (as provided in Condition 4). b. The emergency diesel engine gen-sets (Ref. Nos. B-EG1 through B-EG4), combined, shall not operate more than 320 hours per year for all purposes (as provided in Condition 4). c. The emergency diesel engine gen-set (Ref. No. B-EG105) shall not operate more than 80 hours per year for all purposes (as provided in Condition 4). d. The emergency diesMachine-extracted normative operating-hours statement; second review pending.p. 8
B-EG1 through B-EG480 hours/yearThe emergency diesel engine gen-sets (Ref. Nos. B-EG1 through B-EG4), combined, shall not operate more than 320 hours per year for all purposes (as provided in Condition 4). c. The emergency diesel engine gen-set (Ref. No. B-EG105) shall not operate more than 80 hours per year for all purposes (as provided in Condition 4). d. The emergency diesel engine gen-sets (Ref. Nos. C110-GB, C120-GB, and C-GR) combined, shall not operate more than 240 hours per year for all purposes (as provided in ConMachine-extracted normative operating-hours statement; second review pending.p. 8
B-EG105240 hours/yearmergency diesel engine gen-set (Ref. No. B-EG105) shall not operate more than 80 hours per year for all purposes (as provided in Condition 4). d. The emergency diesel engine gen-sets (Ref. Nos. C110-GB, C120-GB, and C-GR) combined, shall not operate more than 240 hours per year for all purposes (as provided in Condition 4). e. The emergency diesel engine gen-set (Ref. No. C-House Gen) shall not operate more than 80 hours per year for all purposes (as provided in Condition 4). f. The emergencyMachine-extracted normative operating-hours statement; second review pending.p. 8
C110-GB, C120-GB, and C-GR80 hours/yearncy diesel engine gen-sets (Ref. Nos. C110-GB, C120-GB, and C-GR) combined, shall not operate more than 240 hours per year for all purposes (as provided in Condition 4). e. The emergency diesel engine gen-set (Ref. No. C-House Gen) shall not operate more than 80 hours per year for all purposes (as provided in Condition 4). f. The emergency diesel engine gen-sets (Ref. Nos. IAD30-EG4 through IAD30-EG7) combined, shall not operate more than 1,280 hours per year and each emergency diesel engineMachine-extracted normative operating-hours statement; second review pending.p. 8
C-House Gen280 hours/yeary diesel engine gen-set (Ref. No. C-House Gen) shall not operate more than 80 hours per year for all purposes (as provided in Condition 4). f. The emergency diesel engine gen-sets (Ref. Nos. IAD30-EG4 through IAD30-EG7) combined, shall not operate more than 1,280 hours per year and each emergency diesel engine gen-set (Ref. Nos. IAD30-EG4 through IAD30-EG7) shall not operate more than 500 hours per year for all purposes as provided for all purposes (as provided in Condition 4).Machine-extracted normative operating-hours statement; second review pending.p. 8
IAD30-EG4 through IAD30-EG7500 hours/yearndition 4). f. The emergency diesel engine gen-sets (Ref. Nos. IAD30-EG4 through IAD30-EG7) combined, shall not operate more than 1,280 hours per year and each emergency diesel engine gen-set (Ref. Nos. IAD30-EG4 through IAD30-EG7) shall not operate more than 500 hours per year for all purposes as provided for all purposes (as provided in Condition 4).Machine-extracted normative operating-hours statement; second review pending.p. 8
IAD30-EG8 through IAD30-EG12000 hours/yearChantilly Technology Partners, LLC Registration Number: 72375 March 10, 2026 Page 7 g. The emergency diesel engine gen-sets (Ref. Nos. IAD30-EG8 through IAD30-EG12) combined, shall not operate more than 2,000 hours per year and each emergency diesel engine gen-set (Ref. Nos. IAD30-EG8 through IAD30-EG12) shall not operate more than 500 hours per year for all purposes (as provided in Condition 4). h. The emergency diesel engine gen-sets (ReMachine-extracted normative operating-hours statement; second review pending.p. 9
IAD30-EG8 through IAD30-EG12500 hours/year26 Page 7 g. The emergency diesel engine gen-sets (Ref. Nos. IAD30-EG8 through IAD30-EG12) combined, shall not operate more than 2,000 hours per year and each emergency diesel engine gen-set (Ref. Nos. IAD30-EG8 through IAD30-EG12) shall not operate more than 500 hours per year for all purposes (as provided in Condition 4). h. The emergency diesel engine gen-sets (Ref. Nos. IAD32-Gen4 and IAD32-Gen5) combined, shall not operate more than 320 hours per year for all purposes (as provided in CondMachine-extracted normative operating-hours statement; second review pending.p. 9
IAD30-EG8 through IAD30-EG12320 hours/yeargen-set (Ref. Nos. IAD30-EG8 through IAD30-EG12) shall not operate more than 500 hours per year for all purposes (as provided in Condition 4). h. The emergency diesel engine gen-sets (Ref. Nos. IAD32-Gen4 and IAD32-Gen5) combined, shall not operate more than 320 hours per year for all purposes (as provided in Condition 4). i. Each emergency diesel engine gen-set (Ref. Nos. IAD30-EG4 through IAD30-EG12, IAD32-Gen4, and IAD32-Gen5) shall not operate more than 22 hours per year for Scheduled MCRMachine-extracted normative operating-hours statement; second review pending.p. 9
IAD30-EG4 through IAD30-EG12, IAD32-Gen4, and IAD32-Gen522 hours/yearn4 and IAD32-Gen5) combined, shall not operate more than 320 hours per year for all purposes (as provided in Condition 4). i. Each emergency diesel engine gen-set (Ref. Nos. IAD30-EG4 through IAD30-EG12, IAD32-Gen4, and IAD32-Gen5) shall not operate more than 22 hours per year for Scheduled MCRT (as provided in Condition 4.c). The annual limits for hours of operation shall be calculated monthly as the sum of each consecutive 12-month period. Compliance for the consecutive 12-month period shalMachine-extracted normative operating-hours statement; second review pending.p. 9

Permitted emission limits

45 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.

Inspect 45 transcribed limit rows
ReferencePollutantLimitBasis / scopeSource
Rehlko KD2250 Ref. Nos. IAD30- EG4 through IAD30-EG7NOx as NO244.09 lb/hrhourlyp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko KD3000 Ref. Nos. IAD30- EG8 through IAD30-EG12NOx as NO249.85 lb/hrhourlyp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko 2000REOZMD Ref. Nos. IAD32-Gen4 and IAD32-Gen5NOx as NO226.43 lb/hrhourlyp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko KD2250 Ref. Nos. IAD30- EG4 through IAD30-EG7PM0.74 lb/hrhourlyp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko KD3000 Ref. Nos. IAD30- EG8 through IAD30-EG12PM0.93 lb/hrhourlyp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko 2000REOZMD Ref. Nos. IAD32-Gen4 and IAD32-Gen5PM0.50 lb/hrhourlyp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko KD2250 Ref. Nos. IAD30- EG4 through IAD30-EG7PM100.89 lb/hrhourlyp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko KD3000 Ref. Nos. IAD30- EG8 through IAD30-EG12PM101.00 lb/hrhourlyp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko 2000REOZMD Ref. Nos. IAD32-Gen4 and IAD32-Gen5PM100.65 lb/hrhourlyp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko KD2250 Ref. Nos. IAD30- EG4 through IAD30-EG7PM2.50.89 lb/hrhourlyp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko KD3000 Ref. Nos. IAD30- EG8 through IAD30-EG12PM2.51.00 lb/hrhourlyp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko 2000REOZMD Ref. Nos. IAD32-Gen4 and IAD32-Gen5PM2.50.65 lb/hrhourlyp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko KD2250 Ref. Nos. IAD30- EG4 through IAD30-EG7NOx as NO22.48 lb/hrhourlyp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko KD3000 Ref. Nos. IAD30- EG8 through IAD30-EG12NOx as NO213.72 lb/hrhourlyp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko 2000REOZMD Ref. Nos. IAD32-Gen4 and IAD32-Gen5NOx as NO24.81 lb/hrhourlyp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko KD2250 Ref. Nos. IAD30- EG4 through IAD30-EG7VOC1.74 lb/hrhourlyp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko KD3000 Ref. Nos. IAD30- EG8 through IAD30-EG12VOC2.85 lb/hrhourlyp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko 2000REOZMD Ref. Nos. IAD32-Gen4 and IAD32-Gen5VOC1.77 lb/hrhourlyp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko KD2250 Ref. Nos. IAD30- EG4 through IAD30-EG7NOx as NO228.22 tpyannualp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko KD3000 Ref. Nos. IAD30- EG8 through IAD30-EG12NOx as NO249.85 tpyannualp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko 2000REOZMD Ref. Nos. IAD32-Gen4 and IAD32-Gen5NOx as NO24.23 tpyannualp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko KD2250 Ref. Nos. IAD30- EG4 through IAD30-EG7PM0.48 tpyannualp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko KD3000 Ref. Nos. IAD30- EG8 through IAD30-EG12PM0.93 tpyannualp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko 2000REOZMD Ref. Nos. IAD32-Gen4 and IAD32-Gen5PM0.08 tpyannualp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko KD2250 Ref. Nos. IAD30- EG4 through IAD30-EG7PM100.57 tpyannualp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko KD3000 Ref. Nos. IAD30- EG8 through IAD30-EG12PM101.00 tpyannualp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko 2000REOZMD Ref. Nos. IAD32-Gen4 and IAD32-Gen5PM100.10 tpyannualp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko KD2250 Ref. Nos. IAD30- EG4 through IAD30-EG7PM2.50.57 tpyannualp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko KD3000 Ref. Nos. IAD30- EG8 through IAD30-EG12PM2.51.00 tpyannualp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko 2000REOZMD Ref. Nos. IAD32-Gen4 and IAD32-Gen5PM2.50.10 tpyannualp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko KD2250 Ref. Nos. IAD30- EG4 through IAD30-EG7NOx as NO21.59 tpyannualp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko KD3000 Ref. Nos. IAD30- EG8 through IAD30-EG12NOx as NO213.72 tpyannualp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko 2000REOZMD Ref. Nos. IAD32-Gen4 and IAD32-Gen5NOx as NO20.77 tpyannualp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko KD2250 Ref. Nos. IAD30- EG4 through IAD30-EG7VOC1.11 tpyannualp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko KD3000 Ref. Nos. IAD30- EG8 through IAD30-EG12VOC2.85 tpyannualp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Rehlko 2000REOZMD Ref. Nos. IAD32-Gen4 and IAD32-Gen5VOC0.28 tpyannualp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. IAD30-EG4 through IAD30- EG12, IAD32-Gen4, and IAD32-Gen5 (All Units Combined)NOx as NO282.30 tpyannualcombinedp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. IAD30-EG4 through IAD30- EG12, IAD32-Gen4, and IAD32-Gen5 (All Units Combined)PM1.49 tpyannualcombinedp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. IAD30-EG4 through IAD30- EG12, IAD32-Gen4, and IAD32-Gen5 (All Units Combined)PM101.68 tpyannualcombinedp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. IAD30-EG4 through IAD30- EG12, IAD32-Gen4, and IAD32-Gen5 (All Units Combined)PM2.51.68 tpyannualcombinedp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. IAD30-EG4 through IAD30- EG12, IAD32-Gen4, and IAD32-Gen5 (All Units Combined)NOx as NO216.08 tpyannualcombinedp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. IAD30-EG4 through IAD30- EG12, IAD32-Gen4, and IAD32-Gen5 (All Units Combined)VOC4.25 tpyannualcombinedp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
visible emissions5 percent opacityvisiblep. 13Machine-extracted from a page line in an older official PDF; literal context: (Ref. Nos. A-G1 through A-G3, B-EG1 through B-EG4, B-EG105, C110-GB, C120-GB, C-GR, C-House Gen, IAD30-EG4 through IAD30-EG12, IAD32-Gen4, and IAD32-Gen5) shall not exceed five percent (5%) opacity except during one six-minute period in any one hour in which visible emissions shall not exceed ten percent (10%) opacity as determined
visible emissions10 percent opacityvisiblep. 13Machine-extracted from a page line in an older official PDF; literal context: C-GR, C-House Gen, IAD30-EG4 through IAD30-EG12, IAD32-Gen4, and IAD32-Gen5) shall not exceed five percent (5%) opacity except during one six-minute period in any one hour in which visible emissions shall not exceed ten percent (10%) opacity as determined by the EPA Method 9 (reference 40 CFR 60, Appendix A). This requirement applies at all
visible emissions20 percent opacityvisiblep. 13Machine-extracted from a page line in an older official PDF; literal context: times except during startup, shutdown and malfunction. During startup and shutdown, visible emissions shall not exceed ten percent (10%) opacity, except for one (1) six-minute interval not to exceed twenty percent (20%) opacity as determined by EPA Method 9 (reference 40 CFR 60, Appendix A).

DOCUMENT HISTORY

What this document says it changes

amended or superseding permit document

Explicitly supersedes the document dated 2014-04-04.

p. 1, p. 3

QA NOTES

Ambiguity stays visible

  • Machine-extracted candidate. Verify every reused value against the cited official PDF page.
  • Verify table column grouping and any alternative models.
  • Confirm whether the limit is per unit, combined, or limited to testing/maintenance.
  • Confirm multi-row and merged-column header association.
  • Older-PDF text fallback; verify row and unit alignment.