Page-verified permit transcription

Chirisa Richmond LLC

Chesterfield County, Virginia

QA status VerifiedRelease dated July 29, 2026

EVIDENCE NOTE

What the public record says

A manually verified transcription of equipment groups and permit limits stated in Virginia DEQ permit 52432-6, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.

Primary sourceVirginia DEQ permit document

Virginia Department of Environmental Quality

Open original source ↗

Summary fields cite p. 3, p. 4.

What this record does not establish

The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.

How to read the status

Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.

VERIFIED PERMIT TERMS

Equipment and limits,
kept separate from actual use.

This is a conservative transcription of reviewed permit sections, not an exhaustive legal digest. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.

Permitted equipment

10 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.

ReferenceEquipment / modelCount / ratingFuel / controlsStated operating fieldSource
EG-3-Hemergency engine gen-setCummins · 1500DQGAF (QSK50-G5)1 units1500 kW eachdiesel fuel oil unless noted in permitengine design / good operating practiceSee operating-scope tablep. 5
EG-3-01 through EG-3-28 and EG-DD1C-01 through EG-DD1C-04emergency engine gen-setCummins · C3000D6EB (QSK78-G36)32 units3000 kW eachdiesel fuel oil unless noted in permitengine design / good operating practiceSee operating-scope tablep. 5
EG-DD1A-01 through EG-DD1A-24 and EG-DD2A-01 through EG-DD2A-24emergency engine gen-setCaterpillar · C175-2048 units3500 kW eachdiesel fuel oil unless noted in permitengine design / good operating practiceSee operating-scope tablep. 5
EG-DD1B-01 through EG-DD1B-13emergency engine gen-setCummins · 2500DQKAN (QSK60-G26)13 units2500 kW eachdiesel fuel oil unless noted in permitengine design / good operating practiceSee operating-scope tablep. 5
EG-DD2B-01 through EG-DD2B-13emergency engine gen-setCummins / Caterpillar · 2500DQKAN (QSK60-G26) or 3516C13 units2500 kW eachdiesel fuel oil unless noted in permitengine design / good operating practiceSee operating-scope tablep. 5
EG-DD2C-01 through EG-DD2C-04emergency engine gen-setCummins / Caterpillar · C3000D6EB (QSK78-G36) or 3516E4 units3000 kW eachdiesel fuel oil unless noted in permitengine design / good operating practiceSee operating-scope tablep. 5
EG01 through EG05emergency engine gen-setCaterpillar · C175-165 units3000 kW eachdiesel fuel oil unless noted in permitengine design / good operating practiceSee operating-scope tablep. 6
EG06emergency engine gen-setCaterpillar · 3512C1 units1500 kW eachdiesel fuel oil unless noted in permitengine design / good operating practiceSee operating-scope tablep. 6
EG07 through EG15emergency engine gen-setCaterpillar · 3516C9 units2500 kW eachdiesel fuel oil unless noted in permitengine design / good operating practiceSee operating-scope tablep. 6
EG-2-01 through EG-2-31emergency engine gen-setCummins · C3000D6EB (QSK78-G36)31 units3000 kW eachdiesel fuel oil unless noted in permitengine design / good operating practiceSee operating-scope tablep. 6

Operating scope

Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.

ReferenceLimitBasisSource
all permitted engine gen-sets500 hours/year per unitall permitted emergency modes; rolling consecutive 12 monthsCondition 7.p. 8

Permitted emission limits

80 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.

Inspect 80 transcribed limit rows
ReferencePollutantLimitBasis / scopeSource
Caterpillar C175-16NOx as NO2emergency71 lb/hrhourlyper unitemergency operationp. 11
Caterpillar C175-16COemergency1 lb/hrhourlyper unitemergency operationp. 11
Caterpillar C175-16VOCemergency1 lb/hrhourlyper unitemergency operationp. 11
Caterpillar C175-16PMemergency1 lb/hrhourlyper unitemergency operationp. 11
Caterpillar C175-16PM10emergency14.4 lb/hrhourlyper unitemergency operationp. 11
Caterpillar C175-16PM2.5emergency2.4 lb/hrhourlyper unitemergency operationp. 11
Caterpillar 3512CNOx as NO2emergency29.7 lb/hrhourlyper unitemergency operationp. 11
Caterpillar 3512CCOemergency0.5 lb/hrhourlyper unitemergency operationp. 11
Caterpillar 3512CVOCemergency0.5 lb/hrhourlyper unitemergency operationp. 11
Caterpillar 3512CPMemergency0.5 lb/hrhourlyper unitemergency operationp. 11
Caterpillar 3512CPM10emergency4.1 lb/hrhourlyper unitemergency operationp. 11
Caterpillar 3512CPM2.5emergency0.9 lb/hrhourlyper unitemergency operationp. 11
Caterpillar 3516CNOx as NO2emergency48.1 lb/hrhourlyper unitemergency operationp. 11
Caterpillar 3516CCOemergency0.6 lb/hrhourlyper unitemergency operationp. 11
Caterpillar 3516CVOCemergency0.6 lb/hrhourlyper unitemergency operationp. 11
Caterpillar 3516CPMemergency0.6 lb/hrhourlyper unitemergency operationp. 11
Caterpillar 3516CPM10emergency6.1 lb/hrhourlyper unitemergency operationp. 11
Caterpillar 3516CPM2.5emergency1.3 lb/hrhourlyper unitemergency operationp. 11
Cummins C3000D6EBNOx as NO2emergency57.2 lb/hrhourlyper unitemergency operationp. 11
Cummins C3000D6EBCOemergency0.7 lb/hrhourlyper unitemergency operationp. 11
Cummins C3000D6EBVOCemergency0.7 lb/hrhourlyper unitemergency operationp. 11
Cummins C3000D6EBPMemergency0.7 lb/hrhourlyper unitemergency operationp. 11
Cummins C3000D6EBPM10emergency2.5 lb/hrhourlyper unitemergency operationp. 11
Cummins C3000D6EBPM2.5emergency1.1 lb/hrhourlyper unitemergency operationp. 11
Cummins 1500DQGAFNOx as NO2emergency29.4 lb/hrhourlyper unitemergency operationp. 11
Cummins 1500DQGAFCOemergency0.5 lb/hrhourlyper unitemergency operationp. 11
Cummins 1500DQGAFVOCemergency0.5 lb/hrhourlyper unitemergency operationp. 11
Cummins 1500DQGAFPMemergency0.5 lb/hrhourlyper unitemergency operationp. 11
Cummins 1500DQGAFPM10emergency7.9 lb/hrhourlyper unitemergency operationp. 11
Cummins 1500DQGAFPM2.5emergency1.1 lb/hrhourlyper unitemergency operationp. 11
Caterpillar C175-20NOx as NO2emergency68.4 lb/hrhourlyper unitemergency operationp. 11
Caterpillar C175-20COemergency0.8 lb/hrhourlyper unitemergency operationp. 11
Caterpillar C175-20VOCemergency0.8 lb/hrhourlyper unitemergency operationp. 11
Caterpillar C175-20PMemergency0.8 lb/hrhourlyper unitemergency operationp. 11
Caterpillar C175-20PM10emergency23.6 lb/hrhourlyper unitemergency operationp. 11
Caterpillar C175-20PM2.5emergency1.5 lb/hrhourlyper unitemergency operationp. 11
Cummins 2500DQKANNOx as NO2emergency47.2 lb/hrhourlyper unitemergency operationp. 11
Cummins 2500DQKANCOemergency0.9 lb/hrhourlyper unitemergency operationp. 11
Cummins 2500DQKANVOCemergency0.9 lb/hrhourlyper unitemergency operationp. 11
Cummins 2500DQKANPMemergency0.9 lb/hrhourlyper unitemergency operationp. 11
Cummins 2500DQKANPM10emergency6.5 lb/hrhourlyper unitemergency operationp. 11
Cummins 2500DQKANPM2.5emergency0.6 lb/hrhourlyper unitemergency operationp. 11
Caterpillar 3516ENOx as NO2emergency58.2 lb/hrhourlyper unitemergency operationp. 11
Caterpillar 3516ECOemergency1 lb/hrhourlyper unitemergency operationp. 11
Caterpillar 3516EVOCemergency1 lb/hrhourlyper unitemergency operationp. 11
Caterpillar 3516EPMemergency1 lb/hrhourlyper unitemergency operationp. 11
Caterpillar 3516EPM10emergency9.9 lb/hrhourlyper unitemergency operationp. 11
Caterpillar 3516EPM2.5emergency0.6 lb/hrhourlyper unitemergency operationp. 11
Condition 8 / EG01-EG15NOx as NO2all operations17.4 tpyannualgroup combinedfuel-throughput groupp. 12
Condition 8 / EG01-EG15COall operations0.7 tpyannualgroup combinedfuel-throughput groupp. 12
Condition 8 / EG01-EG15VOCall operations0.7 tpyannualgroup combinedfuel-throughput groupp. 12
Condition 8 / EG01-EG15PMall operations0.7 tpyannualgroup combinedfuel-throughput groupp. 12
Condition 8 / EG01-EG15PM10all operations7.9 tpyannualgroup combinedfuel-throughput groupp. 12
Condition 8 / EG01-EG15PM2.5all operations1.5 tpyannualgroup combinedfuel-throughput groupp. 12
Condition 9 / EG-2-01-EG-2-31NOx as NO2all operations16.4 tpyannualgroup combinedfuel-throughput groupp. 12
Condition 9 / EG-2-01-EG-2-31COall operations0.5 tpyannualgroup combinedfuel-throughput groupp. 12
Condition 9 / EG-2-01-EG-2-31VOCall operations0.5 tpyannualgroup combinedfuel-throughput groupp. 12
Condition 9 / EG-2-01-EG-2-31PMall operations0.5 tpyannualgroup combinedfuel-throughput groupp. 12
Condition 9 / EG-2-01-EG-2-31PM10all operations2.6 tpyannualgroup combinedfuel-throughput groupp. 12
Condition 9 / EG-2-01-EG-2-31PM2.5all operations1.0 tpyannualgroup combinedfuel-throughput groupp. 12
Condition 10 / EG-3 groupNOx as NO2all operations16.7 tpyannualgroup combinedfuel-throughput groupp. 12
Condition 10 / EG-3 groupCOall operations0.5 tpyannualgroup combinedfuel-throughput groupp. 12
Condition 10 / EG-3 groupVOCall operations0.5 tpyannualgroup combinedfuel-throughput groupp. 12
Condition 10 / EG-3 groupPMall operations0.5 tpyannualgroup combinedfuel-throughput groupp. 12
Condition 10 / EG-3 groupPM10all operations4.3 tpyannualgroup combinedfuel-throughput groupp. 12
Condition 10 / EG-3 groupPM2.5all operations1.3 tpyannualgroup combinedfuel-throughput groupp. 12
Condition 11 / DD1 groupNOx as NO2all operations23 tpyannualgroup combinedfuel-throughput groupp. 12
Condition 11 / DD1 groupCOall operations0.7 tpyannualgroup combinedfuel-throughput groupp. 12
Condition 11 / DD1 groupVOCall operations0.7 tpyannualgroup combinedfuel-throughput groupp. 12
Condition 11 / DD1 groupPMall operations0.7 tpyannualgroup combinedfuel-throughput groupp. 12
Condition 11 / DD1 groupPM10all operations12.9 tpyannualgroup combinedfuel-throughput groupp. 12
Condition 11 / DD1 groupPM2.5all operations1.3 tpyannualgroup combinedfuel-throughput groupp. 12
Condition 12 / DD2 groupNOx as NO2all operations23 tpyannualgroup combinedfuel-throughput groupp. 12
Condition 12 / DD2 groupCOall operations0.7 tpyannualgroup combinedfuel-throughput groupp. 12
Condition 12 / DD2 groupVOCall operations0.7 tpyannualgroup combinedfuel-throughput groupp. 12
Condition 12 / DD2 groupPMall operations0.7 tpyannualgroup combinedfuel-throughput groupp. 12
Condition 12 / DD2 groupPM10all operations12.9 tpyannualgroup combinedfuel-throughput groupp. 12
Condition 12 / DD2 groupPM2.5all operations1.3 tpyannualgroup combinedfuel-throughput groupp. 12
all permitted engine gen-setsvisible emissionsstated opacity limit10 percent opacityvisibleper exhaust/sourcenormal operation except startup/shutdown/malfunctionp. 12
all permitted engine gen-setsvisible emissionsstated opacity limit20 percent opacityvisibleper exhaust/sourceone six-minute period in any one hourp. 12

DOCUMENT HISTORY

What this document says it changes

combined minor NSR permit

Explicitly supersedes the document dated 2025-07-07.

p. 3, p. 4

QA NOTES

Ambiguity stays visible

  • Transcribed from exact official PDF; source page is 1-based PDF position.
← Return to evidence index