Page-cited permit extraction

CLOP Ashland VA LLC

Hanover Co., Virginia

QA status Second-reviewedRelease dated July 29, 2026

EVIDENCE NOTE

What the public record says

A machine extraction that passed a second manual review of equipment groups and permit limits stated in Virginia DEQ permit 53197-2, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.

Primary sourceVirginia DEQ permit document

Virginia Department of Environmental Quality

Open original source ↗

Summary fields cite p. 1, p. 3.

What this record does not establish

The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.

How to read the status

Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.

SECOND-REVIEWED EXTRACTION

Equipment and limits,
kept separate from actual use.

This is a conservative transcription of reviewed permit sections, not an exhaustive legal digest. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.

Permitted equipment

7 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.

ReferenceEquipment / modelCount / ratingFuel / controlsStated operating fieldSource
00GEN-1emergency engine generator setKohler1 units3000 kW eachSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
01GEN-1emergency engine generator setKohler1 units3000 kW eachSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
02GEN-1emergency engine generator setKohler1 units3000 kW eachSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
03GEN-1emergency engine generator setKohler1 units3000 kW eachSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
04GEN-1emergency engine generator setKohler1 units3000 kW eachSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
05GEN-1emergency engine generator setKohler1 units3000 kW eachSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
HGENemergency engine generator setKohler1 units500 kW eachSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.

Operating scope

Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.

ReferenceLimitBasisSource
500 hours/yearerations under the scenarios above, shall not exceed the limits stated in Conditions 9, 10 and 11. (9VAC5-80-1180) [July 21, 2026] 6. Operating Hours – Each of the emergency engine-generator sets (00GEN-1 through 05GEN-1, and HGEN) shall not operate more than 500 hours per year, including up to 100 hours per year for maintenance checks and readiness testing, calculated monthly as the sum of each consecutive 12-month period. Compliance for the consecutive 12-month period shall be demonstrated mMachine-extracted normative operating-hours statement; second review pending.p. 7
100 hours/yearshall not exceed the limits stated in Conditions 9, 10 and 11. (9VAC5-80-1180) [July 21, 2026] 6. Operating Hours – Each of the emergency engine-generator sets (00GEN-1 through 05GEN-1, and HGEN) shall not operate more than 500 hours per year, including up to 100 hours per year for maintenance checks and readiness testing, calculated monthly as the sum of each consecutive 12-month period. Compliance for the consecutive 12-month period shall be demonstrated monthly by adding the total for the mMachine-extracted normative operating-hours statement; second review pending.p. 7

Permitted emission limits

26 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.

Inspect 26 transcribed limit rows
ReferencePollutantLimitBasis / scopeSource
two emergency engine-generator sets 00GEN-1 and 01GEN-1PM1.0 lb/hrhourlyper unitp. 8Machine-extracted from a page line in an older official PDF; literal context: sets 00GEN-1 and 01GEN-1 shall not exceed the limits specified below: Each unit Each unit Combined PM 1.0 lb/hr 0.3 tons/yr 0.5 tons/yr PM10 1.0 lb/hr 0.3 tons/yr 0.5 tons/yr
two emergency engine-generator sets 00GEN-1 and 01GEN-1PM0.3 lb/hrhourlyper unitp. 8Machine-extracted from a page line in an older official PDF; literal context: sets 00GEN-1 and 01GEN-1 shall not exceed the limits specified below: Each unit Each unit Combined PM 1.0 lb/hr 0.3 tons/yr 0.5 tons/yr PM10 1.0 lb/hr 0.3 tons/yr 0.5 tons/yr
two emergency engine-generator sets 00GEN-1 and 01GEN-1PM0.5 lb/hrhourlyper unitp. 8Machine-extracted from a page line in an older official PDF; literal context: sets 00GEN-1 and 01GEN-1 shall not exceed the limits specified below: Each unit Each unit Combined PM 1.0 lb/hr 0.3 tons/yr 0.5 tons/yr PM10 1.0 lb/hr 0.3 tons/yr 0.5 tons/yr
two emergency engine-generator sets 00GEN-1 and 01GEN-1NOx as NO257.0 lb/hrhourlyp. 8Machine-extracted from a page line in an older official PDF; literal context: PM10 1.0 lb/hr 0.3 tons/yr 0.5 tons/yr PM2.5 1.0 lb/hr 0.3 tons/yr 0.5 tons/yr Nitrogen Oxides (as NO ) 57.0 lb/hr 14.3 tons/yr 28.5 tons/yr 2
two emergency engine-generator sets 00GEN-1 and 01GEN-1NOx as NO214.3 lb/hrhourlyp. 8Machine-extracted from a page line in an older official PDF; literal context: PM10 1.0 lb/hr 0.3 tons/yr 0.5 tons/yr PM2.5 1.0 lb/hr 0.3 tons/yr 0.5 tons/yr Nitrogen Oxides (as NO ) 57.0 lb/hr 14.3 tons/yr 28.5 tons/yr 2
two emergency engine-generator sets 00GEN-1 and 01GEN-1NOx as NO228.5 lb/hrhourlyp. 8Machine-extracted from a page line in an older official PDF; literal context: PM10 1.0 lb/hr 0.3 tons/yr 0.5 tons/yr PM2.5 1.0 lb/hr 0.3 tons/yr 0.5 tons/yr Nitrogen Oxides (as NO ) 57.0 lb/hr 14.3 tons/yr 28.5 tons/yr 2
two emergency engine-generator sets 00GEN-1 and 01GEN-1NOx as NO213.8 lb/hrhourlyp. 8Machine-extracted from a page line in an older official PDF; literal context: Nitrogen Oxides (as NO ) 57.0 lb/hr 14.3 tons/yr 28.5 tons/yr 2 Carbon Monoxide 13.8 lb/hr 3.5 tons/yr 6.9 tons/yr Volatile Organic Compounds 2.9 lb/hr 0.8 tons/yr 1.5 tons/yr
two emergency engine-generator sets 00GEN-1 and 01GEN-1NOx as NO23.5 lb/hrhourlyp. 8Machine-extracted from a page line in an older official PDF; literal context: Nitrogen Oxides (as NO ) 57.0 lb/hr 14.3 tons/yr 28.5 tons/yr 2 Carbon Monoxide 13.8 lb/hr 3.5 tons/yr 6.9 tons/yr Volatile Organic Compounds 2.9 lb/hr 0.8 tons/yr 1.5 tons/yr
two emergency engine-generator sets 00GEN-1 and 01GEN-1NOx as NO26.9 lb/hrhourlyp. 8Machine-extracted from a page line in an older official PDF; literal context: Nitrogen Oxides (as NO ) 57.0 lb/hr 14.3 tons/yr 28.5 tons/yr 2 Carbon Monoxide 13.8 lb/hr 3.5 tons/yr 6.9 tons/yr Volatile Organic Compounds 2.9 lb/hr 0.8 tons/yr 1.5 tons/yr
two emergency engine-generator sets 00GEN-1 and 01GEN-1VOC2.9 lb/hrhourlyp. 8Machine-extracted from a page line in an older official PDF; literal context: 2 Carbon Monoxide 13.8 lb/hr 3.5 tons/yr 6.9 tons/yr Volatile Organic Compounds 2.9 lb/hr 0.8 tons/yr 1.5 tons/yr These emissions are derived from the estimated overall emission contribution from
two emergency engine-generator sets 00GEN-1 and 01GEN-1VOC0.8 lb/hrhourlyp. 8Machine-extracted from a page line in an older official PDF; literal context: 2 Carbon Monoxide 13.8 lb/hr 3.5 tons/yr 6.9 tons/yr Volatile Organic Compounds 2.9 lb/hr 0.8 tons/yr 1.5 tons/yr These emissions are derived from the estimated overall emission contribution from
two emergency engine-generator sets 00GEN-1 and 01GEN-1VOC1.5 lb/hrhourlyp. 8Machine-extracted from a page line in an older official PDF; literal context: 2 Carbon Monoxide 13.8 lb/hr 3.5 tons/yr 6.9 tons/yr Volatile Organic Compounds 2.9 lb/hr 0.8 tons/yr 1.5 tons/yr These emissions are derived from the estimated overall emission contribution from
four emergency engine-generator sets 02GEN-1 through 05GEN-1PM1.1 lb/hrhourlyper unitp. 8Machine-extracted from a page line in an older official PDF; literal context: sets 02GEN-1 through 05GEN-1 shall not exceed the limits specified below: Each unit Each unit Combined PM 1.1 lb/hr 0.3 tons/yr 1.1 tons/yr PM10 1.3 lb/hr 0.4 tons/yr 1.3 tons/yr
four emergency engine-generator sets 02GEN-1 through 05GEN-1PM0.3 lb/hrhourlyper unitp. 8Machine-extracted from a page line in an older official PDF; literal context: sets 02GEN-1 through 05GEN-1 shall not exceed the limits specified below: Each unit Each unit Combined PM 1.1 lb/hr 0.3 tons/yr 1.1 tons/yr PM10 1.3 lb/hr 0.4 tons/yr 1.3 tons/yr
four emergency engine-generator sets 02GEN-1 through 05GEN-1NOx as NO257.0 lb/hrhourlyp. 8Machine-extracted from a page line in an older official PDF; literal context: PM10 1.3 lb/hr 0.4 tons/yr 1.3 tons/yr PM2.5 1.3 lb/hr 0.4 tons/yr 1.3 tons/yr Nitrogen Oxides (as NO ) 57.0 lb/hr 14.3 tons/yr 57.0 tons/yr 2
four emergency engine-generator sets 02GEN-1 through 05GEN-1NOx as NO214.3 lb/hrhourlyp. 8Machine-extracted from a page line in an older official PDF; literal context: PM10 1.3 lb/hr 0.4 tons/yr 1.3 tons/yr PM2.5 1.3 lb/hr 0.4 tons/yr 1.3 tons/yr Nitrogen Oxides (as NO ) 57.0 lb/hr 14.3 tons/yr 57.0 tons/yr 2
four emergency engine-generator sets 02GEN-1 through 05GEN-1NOx as NO23.8 lb/hrhourlyp. 8Machine-extracted from a page line in an older official PDF; literal context: Nitrogen Oxides (as NO ) 57.0 lb/hr 14.3 tons/yr 57.0 tons/yr 2 Carbon Monoxide 3.8 lb/hr 1.0 tons/yr 3.8 tons/yr Volatile Organic Compounds 2.9 lb/hr 0.7 tons/yr 2.9 tons/yr
four emergency engine-generator sets 02GEN-1 through 05GEN-1NOx as NO21.0 lb/hrhourlyp. 8Machine-extracted from a page line in an older official PDF; literal context: Nitrogen Oxides (as NO ) 57.0 lb/hr 14.3 tons/yr 57.0 tons/yr 2 Carbon Monoxide 3.8 lb/hr 1.0 tons/yr 3.8 tons/yr Volatile Organic Compounds 2.9 lb/hr 0.7 tons/yr 2.9 tons/yr
four emergency engine-generator sets 02GEN-1 through 05GEN-1VOC2.9 lb/hrhourlyp. 8Machine-extracted from a page line in an older official PDF; literal context: 2 Carbon Monoxide 3.8 lb/hr 1.0 tons/yr 3.8 tons/yr Volatile Organic Compounds 2.9 lb/hr 0.7 tons/yr 2.9 tons/yr These emissions are derived from the estimated overall emission contribution from
four emergency engine-generator sets 02GEN-1 through 05GEN-1VOC0.7 lb/hrhourlyp. 8Machine-extracted from a page line in an older official PDF; literal context: 2 Carbon Monoxide 3.8 lb/hr 1.0 tons/yr 3.8 tons/yr Volatile Organic Compounds 2.9 lb/hr 0.7 tons/yr 2.9 tons/yr These emissions are derived from the estimated overall emission contribution from
PM0.6 lb/hrhourlyp. 9Machine-extracted from a page line in an older official PDF; literal context: July 21, 2026 Page 7 PM 0.6 lb/hr PM10 0.6 lb/hr
NOx as NO29.8 lb/hrhourlyp. 9Machine-extracted from a page line in an older official PDF; literal context: PM10 0.6 lb/hr PM2.5 0.6 lb/hr Nitrogen Oxides (as NO ) 9.8 lb/hr 2.5 tons/yr 2
NOx as NO22.5 lb/hrhourlyp. 9Machine-extracted from a page line in an older official PDF; literal context: PM10 0.6 lb/hr PM2.5 0.6 lb/hr Nitrogen Oxides (as NO ) 9.8 lb/hr 2.5 tons/yr 2
NOx as NO20.5 lb/hrhourlyp. 9Machine-extracted from a page line in an older official PDF; literal context: Nitrogen Oxides (as NO ) 9.8 lb/hr 2.5 tons/yr 2 Carbon Monoxide 0.5 lb/hr These emissions are derived from the estimated overall emission contribution from
visible emissions20 percent opacityvisiblep. 9Machine-extracted from a page line in an older official PDF; literal context: generator sets (00GEN-1 through 05GEN-1, and HGEN) shall not exceed 10 percent opacity, except during one six-minute period in any one hour in which visible emissions shall not exceed 20 percent opacity as determined by the EPA Method 9 (reference 40 CFR 60, Appendix A). This condition applies at all times except during startup, shutdown, and
visible emissions10 percent opacityvisibleper exhaust/sourcep. 9Machine-extracted normative visible-emission limit; second review pending.

DOCUMENT HISTORY

What this document says it changes

amended or superseding permit document

Explicitly supersedes the document dated 2025-02-14.

p. 1, p. 3

QA NOTES

Ambiguity stays visible

  • Verify table column grouping and any alternative models. New 2026 amended permit; identity, equipment page 5, operating hours page 7, and emission-limit pages 8-9 visually checked.
  • Confirm whether the limit is per unit, combined, or limited to testing/maintenance. New 2026 amended permit; identity, equipment page 5, operating hours page 7, and emission-limit pages 8-9 visually checked.
  • Older-PDF text fallback; verify row and unit alignment. New 2026 amended permit; identity, equipment page 5, operating hours page 7, and emission-limit pages 8-9 visually checked.
  • Confirm normal-operation versus startup/shutdown exception. New 2026 amended permit; identity, equipment page 5, operating hours page 7, and emission-limit pages 8-9 visually checked.
← Return to evidence index