Page-cited permit extraction

Equinix, LLC - CU 1-4

Culpeper Co., Virginia

QA status Machine-extractedRelease dated July 29, 2026

EVIDENCE NOTE

What the public record says

A machine-extracted candidate of equipment groups and permit limits stated in Virginia DEQ permit 41064-8, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.

Primary sourceVirginia DEQ permit document

Virginia Department of Environmental Quality

Open original source ↗

Summary fields cite p. 1, p. 3.

What this record does not establish

The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.

How to read the status

Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.

MACHINE-EXTRACTED CANDIDATE

Equipment and limits,
kept separate from actual use.

These page-cited rows are machine-extracted and still require a second manual review. Verify every reused value against the linked official PDF. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.

Permitted equipment

1 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.

ReferenceEquipment / modelCount / ratingFuel / controlsStated operating fieldSource
emergency engine generator set3 unitsNo reliable per-unit rating transcribeddiesel fuel oilSee operating-scope tablep. 1Machine-extracted from explicit permit prose: Harris: Attached is a permit to construct and operate three additional emergency/standby diesel engine generator sets at Equinix located in Culpeper, Virginia in accordance with the provisions of the Commonwealth

Operating scope

Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.

ReferenceLimitBasisSource
500 hours/yearof all emissions from operations underscenarios in Conditions 4.a. through 4cabove, shall not exceed the limits stated in Condition 11 (gVAC6-60-1160Oand9VAC6-60-260) 6. Operating HoureDEacbenglne-genera^ through OCO-E, and OCO-R) shall not operate more than 500 hours peryear,calculated monthly as the sum of each consecutive twelve month period. Compliance forthe consecutive twelve month period shall be demonstrated monthly by adding the total number of hours operated forthe most recently coMachine-extracted normative operating-hours statement; second review pending.p. 9

Permitted emission limits

6 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.

Inspect 6 transcribed limit rows
ReferencePollutantLimitBasis / scopeSource
each diesel engine-generator set (DCD-D through DCD-E and DCD-R)NOx as NO253.7 tpyannualp. 11Machine-extracted from a page line in an older official PDF; literal context: through DCA-E, DCA-Swing, DCB-A through DCB-H, DCC-A through DCC-F, DCD-A through DCD-E, and DCD-R) shall not exceed the limits specified below: Nitrogen Oxides (as NO2) 53.7 tons per year Carbon Monoxide (CO) 22.0 tons per year
each diesel engine-generator set (DCD-D through DCD-E and DCD-R)NOx as NO222.0 tpyannualp. 11Machine-extracted from a page line in an older official PDF; literal context: DCD-E, and DCD-R) shall not exceed the limits specified below: Nitrogen Oxides (as NO2) 53.7 tons per year Carbon Monoxide (CO) 22.0 tons per year Particulate Matter (PM ) 1.6 tons per year
each diesel engine-generator set (DCD-D through DCD-E and DCD-R)PM1.6 tpyannualp. 11Machine-extracted from a page line in an older official PDF; literal context: Nitrogen Oxides (as NO2) 53.7 tons per year Carbon Monoxide (CO) 22.0 tons per year Particulate Matter (PM ) 1.6 tons per year 10
each diesel engine-generator set (DCD-D through DCD-E and DCD-R)VOC4.2 tpyannualp. 11Machine-extracted from a page line in an older official PDF; literal context: Particulate Matter (PM ) 1.6 tons per year 10 Volatile Organic Compounds (VOC) 4.2 tons per year
PM0.36 lb/hrhourlyp. 13Machine-extracted from a page line in an older official PDF; literal context: whenSCRisnotoperationalx32.14lb/hr^2000lb/ton^ CC^(Total monthly hours of operation of the engine-generator setsx3.04lb/hr)^2000lb/ton PM^o^(Total monthly hours of operation oftbe engine-generatorsetsx0.36lb/hr)^2000lb/ton VOC^(Total monthly hours of operation of the engine-generator setsx0.71lb/hr)^2000lb/ton
VOC0.71 lb/hrhourlyp. 13Machine-extracted from a page line in an older official PDF; literal context: CC^(Total monthly hours of operation of the engine-generator setsx3.04lb/hr)^2000lb/ton PM^o^(Total monthly hours of operation oftbe engine-generatorsetsx0.36lb/hr)^2000lb/ton VOC^(Total monthly hours of operation of the engine-generator setsx0.71lb/hr)^2000lb/ton e. Monthly emissions from diesel engine-generator sets (Ref. Nos. OCO-A through DCO-C) shall

DOCUMENT HISTORY

What this document says it changes

amended or superseding permit document

Explicitly supersedes the document dated 2016-01-13.

p. 1, p. 3

QA NOTES

Ambiguity stays visible

  • Machine-extracted candidate. Verify every reused value against the cited official PDF page.
  • Prose fallback; verify equipment grouping.
  • Confirm whether the limit is per unit, combined, or limited to testing/maintenance.
  • Older-PDF text fallback; verify row and unit alignment.
← Return to evidence index