Page-cited permit extraction

Microsoft Corp - AVC17 Datacenter

Mecklenburg Co., Virginia

QA status Machine-extractedRelease dated July 29, 2026

EVIDENCE NOTE

What the public record says

A machine-extracted candidate of equipment groups and permit limits stated in Virginia DEQ permit 53086-2, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.

Primary sourceVirginia DEQ permit document

Virginia Department of Environmental Quality

Open original source ↗

Summary fields cite p. 3.

What this record does not establish

The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.

How to read the status

Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.

MACHINE-EXTRACTED CANDIDATE

Equipment and limits,
kept separate from actual use.

These page-cited rows are machine-extracted and still require a second manual review. Verify every reused value against the linked official PDF. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.

Permitted equipment

2 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.

ReferenceEquipment / modelCount / ratingFuel / controlsStated operating fieldSource
ENG1-ENG20, ENG22-ENG41, ENG43-ENG72, ENG74-ENG103, ENG105-ENG134engine generator setCummins · C3000 D6e QSK95 series backup130 units3000 kW eachSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
ENG21, ENG42, ENG73, ENG104, ENG135engine generator setCummins · DFEK QSX15 series backup5 units500 kW eachSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.

Operating scope

Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.

ReferenceLimitBasisSource

Permitted emission limits

19 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.

Inspect 19 transcribed limit rows
ReferencePollutantLimitBasis / scopeSource
ENG1-ENG20, ENG22-ENG41, ENG43-ENG72, ENG74-ENG103, ENG105-ENG134 Cummins C3000 D6ePM0.6 lb/hrhourlyper unitp. 7Machine-extracted from an official permit limit table; header grouping requires second review.
ENG21, ENG42, ENG73, ENG104, ENG135 Cummins DFEKPM0.1 lb/hrhourlyper unitp. 7Machine-extracted from an official permit limit table; header grouping requires second review.
ENG1-ENG20, ENG22-ENG41, ENG43-ENG72, ENG74-ENG103, ENG105-ENG134 Cummins C3000 D6ePM0.7 lb/hrhourlyper unitp. 7Machine-extracted from an official permit limit table; header grouping requires second review.
ENG1-ENG20, ENG22-ENG41, ENG43-ENG72, ENG74-ENG103, ENG105-ENG134 Cummins C3000 D6eNOx as NO250.6 lb/hrhourlyper unitp. 7Machine-extracted from an official permit limit table; header grouping requires second review.
ENG21, ENG42, ENG73, ENG104, ENG135 Cummins DFEKNOx as NO29.9 lb/hrhourlyper unitp. 7Machine-extracted from an official permit limit table; header grouping requires second review.
ENG1-ENG20, ENG22-ENG41, ENG43-ENG72, ENG74-ENG103, ENG105-ENG134 Cummins C3000 D6eNOx as NO21.6 lb/hrhourlyper unitp. 7Machine-extracted from an official permit limit table; header grouping requires second review.
ENG21, ENG42, ENG73, ENG104, ENG135 Cummins DFEKNOx as NO22.4 lb/hrhourlyper unitp. 7Machine-extracted from an official permit limit table; header grouping requires second review.
ENG1-ENG20, ENG22-ENG41, ENG43-ENG72, ENG74-ENG103, ENG105-ENG134 Cummins C3000 D6eVOC0.3 lb/hrhourlyper unitp. 7Machine-extracted from an official permit limit table; header grouping requires second review.
ENG21, ENG42, ENG73, ENG104, ENG135 Cummins DFEKVOC0.2 lb/hrhourlyper unitp. 7Machine-extracted from an official permit limit table; header grouping requires second review.
ENG1-ENG20, ENG22-ENG41, ENG43-ENG72, ENG74-ENG103, ENG105-ENG134 Cummins C3000 D6eSO20.2 lb/hrhourlyper unitp. 7Machine-extracted from an official permit limit table; header grouping requires second review.
ENG21, ENG42, ENG73, ENG104, ENG135 Cummins DFEKSO20.01 lb/hrhourlyper unitp. 7Machine-extracted from an official permit limit table; header grouping requires second review.
Annual Emission Limit (all units combined)PM3.4 tpyannualcombinedp. 7Machine-extracted from an official permit limit table; header grouping requires second review.
Annual Emission Limit (all units combined)PM3.8 tpyannualcombinedp. 7Machine-extracted from an official permit limit table; header grouping requires second review.
Annual Emission Limit (all units combined)NOx as NO296.3 tpyannualcombinedp. 7Machine-extracted from an official permit limit table; header grouping requires second review.
Annual Emission Limit (all units combined)NOx as NO28.6 tpyannualcombinedp. 7Machine-extracted from an official permit limit table; header grouping requires second review.
Annual Emission Limit (all units combined)VOC2.2 tpyannualcombinedp. 7Machine-extracted from an official permit limit table; header grouping requires second review.
Annual Emission Limit (all units combined)SO21.1 tpyannualcombinedp. 7Machine-extracted from an official permit limit table; header grouping requires second review.
visible emissions10 percent opacityvisiblep. 8Machine-extracted from a page line in an older official PDF; literal context: (9 VAC 5-80-1180 and 9 VAC 5-50-260) [4/22/2025] 9. Visible Emission Limit - Visible emissions from each engine-generator set exhausts (Ref. Nos. ENG1-ENG135) shall not exceed 10% opacity except during one 6-minute period in any one hour in which visible emissions shall not exceed 20% opacity as determined by
visible emissions20 percent opacityvisiblep. 8Machine-extracted from a page line in an older official PDF; literal context: 9. Visible Emission Limit - Visible emissions from each engine-generator set exhausts (Ref. Nos. ENG1-ENG135) shall not exceed 10% opacity except during one 6-minute period in any one hour in which visible emissions shall not exceed 20% opacity as determined by EPA Method 9 (reference 40 CFR 60, Appendix A). This condition applies at all times

DOCUMENT HISTORY

What this document says it changes

amended or superseding permit document

Explicitly supersedes the document dated 2023-07-11.

p. 3

QA NOTES

Ambiguity stays visible

  • Machine-extracted candidate. Verify every reused value against the cited official PDF page.
  • Verify table column grouping and any alternative models.
  • Confirm multi-row and merged-column header association.
  • Older-PDF text fallback; verify row and unit alignment.
← Return to evidence index