Page-cited permit extraction

Amazon Data Services, Inc. IAD-150 IAD-151 IAD-152

Loudoun Co., Virginia

QA status Machine-extractedRelease dated July 29, 2026

EVIDENCE NOTE

What the public record says

A machine-extracted candidate of equipment groups and permit limits stated in Virginia DEQ permit 74174-1, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.

Primary sourceVirginia DEQ permit document

Virginia Department of Environmental Quality

Open original source ↗

Summary fields cite p. 1, p. 3.

What this record does not establish

The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.

How to read the status

Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.

MACHINE-EXTRACTED CANDIDATE

Equipment and limits,
kept separate from actual use.

These page-cited rows are machine-extracted and still require a second manual review. Verify every reused value against the linked official PDF. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.

Permitted equipment

2 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.

ReferenceEquipment / modelCount / ratingFuel / controlsStated operating fieldSource
emergency engine generator setCaterpillar2 units2500 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from explicit permit prose: Equipment Description Rated Federal Permit Capacity Requirements Date Sixty Two (62) Caterpillar 3,634 bhp 1-62 3516C-HD emergency 2,500 ekW None 8/9/2019 diesel engine gen-sets (each unit) Transitory equipment to be constructed: Standby Delegated Original Reference No
emergency engine generator setCaterpillar · 3516C 22 units2000 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from explicit permit prose: Equipment Description Rated Federal Permit Capacity Requirements Date Two (2) Caterpillar 3516C 2,937 bhp T-1 and T-2 emergency diesel engine 2,000 ekW None 8/9/2019 gen-set (each unit) Specifications included in the above tables are for informational purposes only and do

Operating scope

Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.

ReferenceLimitBasisSource
100 hours/yearual period calculated as the sum of all emissions firom operation under the scenarios above, shall not exceed the limits stated in Condition 14. (9 VAC 5-80-1180) 8. Operating Hours - Each individual emergency diesel engine gen-set shall not operate more than 100 hours per year for planned non-emergency operation and no more than 500 hours per year for all purposes (as provided in Condition 7). Planned non-emergency operation includes scheduled and non-scheduled maintenance, readiness testing,Machine-extracted normative operating-hours statement; second review pending.p. 8
500 hours/yearthe scenarios above, shall not exceed the limits stated in Condition 14. (9 VAC 5-80-1180) 8. Operating Hours - Each individual emergency diesel engine gen-set shall not operate more than 100 hours per year for planned non-emergency operation and no more than 500 hours per year for all purposes (as provided in Condition 7). Planned non-emergency operation includes scheduled and non-scheduled maintenance, readiness testing, and operational training. Planned non-emergency operation cannot be useMachine-extracted normative operating-hours statement; second review pending.p. 8

Permitted emission limits

13 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.

Inspect 13 transcribed limit rows
ReferencePollutantLimitBasis / scopeSource
each Caterpillar 3516C emergency diesel engine gen-set (Ref. Nos.: T1 and T2)NOx as NO297.00 tpyannualp. 10Machine-extracted from a page line in an older official PDF; literal context: engine gen-sets (Ref. Nos. 1 - 62, T1 and T2) included in the Equipment List section of this permit for all purposes shall not exceed the limits specified below: Nitrogen Oxides (as NO2) 97.00 tpy Carbon Monoxide (CO) 51.07 tpy
each Caterpillar 3516C emergency diesel engine gen-set (Ref. Nos.: T1 and T2)NOx as NO251.07 tpyannualp. 10Machine-extracted from a page line in an older official PDF; literal context: permit for all purposes shall not exceed the limits specified below: Nitrogen Oxides (as NO2) 97.00 tpy Carbon Monoxide (CO) 51.07 tpy Volatile Organic Compounds (VOC) 10.69 tpy
each Caterpillar 3516C emergency diesel engine gen-set (Ref. Nos.: T1 and T2)VOC10.69 tpyannualp. 10Machine-extracted from a page line in an older official PDF; literal context: Nitrogen Oxides (as NO2) 97.00 tpy Carbon Monoxide (CO) 51.07 tpy Volatile Organic Compounds (VOC) 10.69 tpy Particulate Matter (PMio) 3.50 tpy
each Caterpillar 3516C emergency diesel engine gen-set (Ref. Nos.: T1 and T2)PM3.50 tpyannualp. 10Machine-extracted from a page line in an older official PDF; literal context: Carbon Monoxide (CO) 51.07 tpy Volatile Organic Compounds (VOC) 10.69 tpy Particulate Matter (PMio) 3.50 tpy Particulate Matter (PM2.5) 3.50 tpy
each Caterpillar 3516C emergency diesel engine gen-set (Ref. Nos.: T1 and T2)PM2.53.50 tpyannualp. 10Machine-extracted from a page line in an older official PDF; literal context: Volatile Organic Compounds (VOC) 10.69 tpy Particulate Matter (PMio) 3.50 tpy Particulate Matter (PM2.5) 3.50 tpy These emissions are derived from the estimated overall emission contribution from
NOx as NO238.7 tpyannualp. 11Machine-extracted from a page line in an older official PDF; literal context: Nos.: 1 - 62) for maintenance checks and readiness testing shall not exceed the limits specified below: Nitrogen Oxides (as NO2) 38.7 tpy Carbon Monoxide (CO) 20.9 tpy I
NOx as NO220.9 tpyannualp. 11Machine-extracted from a page line in an older official PDF; literal context: specified below: Nitrogen Oxides (as NO2) 38.7 tpy Carbon Monoxide (CO) 20.9 tpy I Volatile Organic Compounds (VOC) 4.4 tpy
VOC4.4 tpyannualp. 11Machine-extracted from a page line in an older official PDF; literal context: Nitrogen Oxides (as NO2) 38.7 tpy Carbon Monoxide (CO) 20.9 tpy I Volatile Organic Compounds (VOC) 4.4 tpy Particulate Matter (PMio) 1.4 tpy
PM1.4 tpyannualp. 11Machine-extracted from a page line in an older official PDF; literal context: Carbon Monoxide (CO) 20.9 tpy I Volatile Organic Compounds (VOC) 4.4 tpy Particulate Matter (PMio) 1.4 tpy Particulate Matter (PM2.5) 1.4 tpy
PM2.51.4 tpyannualp. 11Machine-extracted from a page line in an older official PDF; literal context: Volatile Organic Compounds (VOC) 4.4 tpy Particulate Matter (PMio) 1.4 tpy Particulate Matter (PM2.5) 1.4 tpy These emissions are derived from the estimated overall emission contribution from
visible emissions5 percent opacityvisiblep. 11Machine-extracted from a page line in an older official PDF; literal context: (9 VAC 5-80-1180) 16. Visible Emission Limit - Visible emissions from each emergency diesel engine gen-set included in the Equipment List section of this permit shall not exceed 5% opacity except during one 6-minute period in any one hour in which visible emissions shall not exceed
visible emissions10 percent opacityvisiblep. 11Machine-extracted from a page line in an older official PDF; literal context: included in the Equipment List section of this permit shall not exceed 5% opacity except during one 6-minute period in any one hour in which visible emissions shall not exceed 10% opacity as determined by EPA Method 9 (reference 40 CFR 60, Appendix A). This condition applies at all times except during startup, shutdown and malfimction.
visible emissions20 percent opacityvisiblep. 11Machine-extracted from a page line in an older official PDF; literal context: During startup and shutdown, visible emissions from each emergency diesel engine gen-set shall not exceed 10% opacity except during one 6-minute period in any one hour in which visible emissions shall not exceed 20% opacity as determined by EPA Method 9 (reference 40 CFR 60, Appendix A).

DOCUMENT HISTORY

What this document says it changes

permit to construct and operate

No superseded-document date is asserted beyond the cited source wording.

p. 1, p. 3

QA NOTES

Ambiguity stays visible

  • Machine-extracted candidate. Verify every reused value against the cited official PDF page.
  • Prose fallback; verify equipment grouping.
  • Confirm whether the limit is per unit, combined, or limited to testing/maintenance.
  • Older-PDF text fallback; verify row and unit alignment.
← Return to evidence index