Page-cited permit extraction

Amazon Data Services Inc - IAD-163/164/174

Loudoun Co., Virginia

QA status Machine-extractedRelease dated July 29, 2026

EVIDENCE NOTE

What the public record says

A machine-extracted candidate of equipment groups and permit limits stated in Virginia DEQ permit 74227-2, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.

Primary sourceVirginia DEQ permit document

Virginia Department of Environmental Quality

Open original source ↗

Summary fields cite p. 1, p. 3.

What this record does not establish

The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.

How to read the status

Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.

MACHINE-EXTRACTED CANDIDATE

Equipment and limits,
kept separate from actual use.

These page-cited rows are machine-extracted and still require a second manual review. Verify every reused value against the linked official PDF. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.

Permitted equipment

7 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.

ReferenceEquipment / modelCount / ratingFuel / controlsStated operating fieldSource
53 through 78emergency engine generator setCaterpillar · 3516C-HD26 units2500 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
80emergency engine generator setCaterpillar · C181 units600 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
1 through 26emergency engine generator setMTU · 16V4000G94S26 units2500 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
27 through 52emergency engine generator setCaterpillar · 3516C-HD26 units2500 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
79emergency engine generator setCaterpillar · C181 units600 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
81emergency engine generator setMTU · 12V1600G80S1 units600 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
T1 and T2emergency engine generator setCaterpillar · 3516C transitory2 units2000 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.

Operating scope

Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.

ReferenceLimitBasisSource
1 through 52, 79, 81, T1, and T229 hours/yearunit (which involves fuel combustion) shall be minimized to the maximum extent practical. (9VAC5-80-1180) [6/21/2024] 7. Operating Hours – Each individual emergency diesel engine gen-set (Ref. Nos. 1 through 52, 79, 81, T1, and T2) shall not operate more than 29 hours per year for scheduled maintenance checks and readiness testing (Scheduled MCRT, as provided in Condition 4.c). Each individual emergency diesel engine gen-set (Ref. Nos. 53 through 78 and 80) shall not operate more than 35 hourMachine-extracted normative operating-hours statement; second review pending.p. 8
53 through 78 and 8035 hours/year) shall not operate more than 29 hours per year for scheduled maintenance checks and readiness testing (Scheduled MCRT, as provided in Condition 4.c). Each individual emergency diesel engine gen-set (Ref. Nos. 53 through 78 and 80) shall not operate more than 35 hours per year for scheduled maintenance checks and readiness testing (Scheduled MCRT, as provided in Condition 4.c). Each individual emergency diesel engine gen-set (Ref. Nos. 1 through 81, T1, and T2) shall not operate more than 500Machine-extracted normative operating-hours statement; second review pending.p. 8
1 through 81, T1, and T2500 hours/yearall not operate more than 35 hours per year for scheduled maintenance checks and readiness testing (Scheduled MCRT, as provided in Condition 4.c). Each individual emergency diesel engine gen-set (Ref. Nos. 1 through 81, T1, and T2) shall not operate more than 500 hours per year for all purposes (as provided in Condition 4) combined. The annual limits for hours of operation shall be calculated monthly as the sum of each consecutive 12-month period. Compliance for the consecutive 12-month periodMachine-extracted normative operating-hours statement; second review pending.p. 8

Permitted emission limits

32 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.

Inspect 32 transcribed limit rows
ReferencePollutantLimitBasis / scopeSource
Ref. Nos. 1 through 26NOx as NO247.77 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 27 through 78NOx as NO248.06 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 79 and 80NOx as NO29.58 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. 81NOx as NO211.53 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. 81NOx as NO238.85 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 1 through 26NOx as NO29.81 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 27 through 78NOx as NO26.09 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 79 and 80NOx as NO21.59 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. 81NOx as NO21.04 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. 81NOx as NO23.96 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 1 through 26VOC1.70 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 27 through 78VOC1.21 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 79 and 80VOC0.33 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. 81VOC0.42 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. 81VOC1.15 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 1 through 26PM100.69 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 27 through 78PM100.41 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 79 and 80PM100.11 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. 81PM100.19 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. 81PM100.58 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 1 through 26PM2.50.69 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 27 through 78PM2.50.41 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 79 and 80PM2.50.11 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. 81PM2.50.19 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. 81PM2.50.58 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. T1 and T2NOx as NO22.88 tpyannualp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 1 through 81, T1, and T2NOx as NO295.98 tpyannualp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. T1 and T2NOx as NO21.54 tpyannualp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 1 through 81, T1, and T2NOx as NO251.60 tpyannualp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 1 through 81, T1, and T2VOC10.84 tpyannualp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 1 through 81, T1, and T2PM103.58 tpyannualp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 1 through 81, T1, and T2PM2.53.58 tpyannualp. 11Machine-extracted from an official permit limit table; header grouping requires second review.

DOCUMENT HISTORY

What this document says it changes

amended or superseding permit document

Explicitly supersedes the document dated 2021-12-15.

p. 1, p. 3

QA NOTES

Ambiguity stays visible

  • Machine-extracted candidate. Verify every reused value against the cited official PDF page.
  • Verify table column grouping and any alternative models.
  • Confirm whether the limit is per unit, combined, or limited to testing/maintenance.
  • Confirm multi-row and merged-column header association.
← Return to evidence index