Caterpillar 3516C-HD Ref. Nos. 1 through 96 | NOx as NO2— | 48.07 lb/hrhourly | per unit— | p. 10 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Caterpillar 3516C Ref. No. T1 | NOx as NO2— | 38.85 lb/hrhourly | —— | p. 10 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Caterpillar 3516C-HD Ref. Nos. 1 through 96 | NOx as NO2— | 6.01 lb/hrhourly | per unit— | p. 10 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Caterpillar 3516C Ref. No. T1 | NOx as NO2— | 4.04 lb/hrhourly | —— | p. 10 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Caterpillar 3516C-HD Ref. Nos. 1 through 96 | VOC— | 1.20 lb/hrhourly | per unit— | p. 10 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Caterpillar 3516C Ref. No. T1 | VOC— | 1.14 lb/hrhourly | —— | p. 10 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Caterpillar 3516C-HD Ref. Nos. 1 through 96 | PM— | 0.41 lb/hrhourly | per unit— | p. 10 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Caterpillar 3516C Ref. No. T1 | PM— | 0.57 lb/hrhourly | —— | p. 10 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Caterpillar C18 750ekW (Ref. No. 97) | NOx as NO2— | 14.20 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Caterpillar C18 600ekW (Ref. No. 98) | NOx as NO2— | 9.51 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Caterpillar 3512C 1,600ekW (Ref. No. 99) | NOx as NO2— | 30.75 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Caterpillar C18 750ekW (Ref. No. 97) | NOx as NO2— | 4.73 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Caterpillar C18 600ekW (Ref. No. 98) | NOx as NO2— | 1.59 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Caterpillar 3512C 1,600ekW (Ref. No. 99) | NOx as NO2— | 5.78 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Caterpillar C18 750ekW (Ref. No. 97) | VOC— | 1.91 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Caterpillar C18 600ekW (Ref. No. 98) | VOC— | 0.33 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Caterpillar 3512C 1,600ekW (Ref. No. 99) | VOC— | 0.87 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Caterpillar C18 750ekW (Ref. No. 97) | PM10— | 0.32 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Caterpillar C18 600ekW (Ref. No. 98) | PM10— | 0.11 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Caterpillar 3512C 1,600ekW (Ref. No. 99) | PM10— | 0.44 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Caterpillar C18 750ekW (Ref. No. 97) | PM2.5— | 0.32 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Caterpillar C18 600ekW (Ref. No. 98) | PM2.5— | 0.11 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Caterpillar 3512C 1,600ekW (Ref. No. 99) | PM2.5— | 0.44 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
(Ref. Nos. 1 through 99) All Operations (99 Units Combined) | NOx as NO2— | 98.89 tpyannual | combined— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
(Ref. Nos. 1 through 99) All Operations (99 Units Combined) | NOx as NO2— | 57.83 tpyannual | combined— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
(Ref. Nos. 1 through 99) All Operations (99 Units Combined) | VOC— | 13.42 tpyannual | combined— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
(Ref. Nos. 1 through 99) All Operations (99 Units Combined) | PM10— | 3.55 tpyannual | combined— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
(Ref. Nos. 1 through 99) All Operations (99 Units Combined) | PM2.5— | 3.55 tpyannual | combined— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
(Ref. Nos. 1 through 99 and T1) All Operations (100 Units Combined) | NOx as NO2— | 99.18 tpyannual | combined— | p. 12 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
(Ref. Nos. 1 through 99 and T1) All Operations (100 Units Combined) | NOx as NO2— | 57.99 tpyannual | combined— | p. 12 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
(Ref. Nos. 1 through 99 and T1) All Operations (100 Units Combined) | VOC— | 13.46 tpyannual | combined— | p. 12 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
(Ref. Nos. 1 through 99 and T1) All Operations (100 Units Combined) | PM10— | 3.56 tpyannual | combined— | p. 12 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
(Ref. Nos. 1 through 99 and T1) All Operations (100 Units Combined) | PM2.5— | 3.56 tpyannual | combined— | p. 12 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |