Caterpillar 3516E (Ref. Nos. 1 through 166) Uncontrolled | NOx as NO2uncontrolled | 53.48 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Controlled by SCR | NOx as NO2controlled | 4.44 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Caterpillar 3516E (Ref. Nos. 1 through 166) Uncontrolled | PMuncontrolled | 0.20 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Caterpillar 3516E (Ref. Nos. 1 through 166) Uncontrolled | PM10uncontrolled | 0.20 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Caterpillar 3516E (Ref. Nos. 1 through 166) Uncontrolled | PM2.5uncontrolled | 0.20 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Caterpillar 3516E (Ref. Nos. 1 through 166) Uncontrolled | NOx as NO2uncontrolled | 3.10 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Caterpillar 3516E (Ref. Nos. 1 through 166) Uncontrolled | VOCuncontrolled | 0.49 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Caterpillar 3516E (Ref. Nos. 1 through 166) Uncontrolled | SO2uncontrolled | 0.04 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
CAT C32 Ref. Nos. 167 through 171 | NOx as NO2— | 19.52 lb/hrhourly | —— | p. 12 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
CAT 3516C Ref. Nos. T1 and T2 | NOx as NO2— | 38.85 lb/hrhourly | —— | p. 12 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
CAT C32 Ref. Nos. 167 through 171 | PM— | 0.23 lb/hrhourly | —— | p. 12 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
CAT 3516C Ref. Nos. T1 and T2 | PM— | 0.57 lb/hrhourly | —— | p. 12 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
CAT C32 Ref. Nos. 167 through 171 | PM10— | 0.23 lb/hrhourly | —— | p. 12 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
CAT 3516C Ref. Nos. T1 and T2 | PM10— | 0.57 lb/hrhourly | —— | p. 12 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
CAT C32 Ref. Nos. 167 through 171 | PM2.5— | 0.23 lb/hrhourly | —— | p. 12 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
CAT 3516C Ref. Nos. T1 and T2 | PM2.5— | 0.57 lb/hrhourly | —— | p. 12 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
CAT C32 Ref. Nos. 167 through 171 | NOx as NO2— | 2.78 lb/hrhourly | —— | p. 12 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
CAT 3516C Ref. Nos. T1 and T2 | NOx as NO2— | 3.95 lb/hrhourly | —— | p. 12 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
CAT C32 Ref. Nos. 167 through 171 | VOC— | 0.34 lb/hrhourly | —— | p. 12 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
CAT 3516C Ref. Nos. T1 and T2 | VOC— | 1.14 lb/hrhourly | —— | p. 12 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
CAT C32 Ref. Nos. 167 through 171 | SO2— | 0.02 lb/hrhourly | —— | p. 12 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
CAT 3516C Ref. Nos. T1 and T2 | SO2— | 0.03 lb/hrhourly | —— | p. 12 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
All Units Ref. Nos. 1 through 171, T1, and T2 | NOx as NO2— | 96.03 tpyannual | combined— | p. 12 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
All Units Ref. Nos. 1 through 171, T1, and T2 | PM— | 4.78 tpyannual | combined— | p. 12 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
All Units Ref. Nos. 1 through 171, T1, and T2 | PM10— | 4.78 tpyannual | combined— | p. 12 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
All Units Ref. Nos. 1 through 171, T1, and T2 | PM2.5— | 4.78 tpyannual | combined— | p. 12 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
All Units Ref. Nos. 1 through 171, T1, and T2 | NOx as NO2— | 69.92 tpyannual | combined— | p. 12 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
All Units Ref. Nos. 1 through 171, T1, and T2 | VOC— | 11.02 tpyannual | combined— | p. 12 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
All Units Ref. Nos. 1 through 171, T1, and T2 | SO2— | 0.87 tpyannual | combined— | p. 12 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
| visible emissions— | 5 percent opacityvisible | —— | p. 13 ↗Machine-extracted from a page line in an older official PDF; literal context: 17. Visible Emission Limit – a. Visible emissions from each non-emergency engine gen-set (Ref. Nos. 1 through 166) shall not exceed 5% opacity as determined by EPA Method 9 (reference 40 CFR 60, Appendix A). This requirement applies at all times except during startup, shutdown |
| visible emissions— | 10 percent opacityvisible | —— | p. 13 ↗Machine-extracted from a page line in an older official PDF; literal context: b. Visible emissions from each emergency engine gen-set (Ref. Nos. 167 through 171, T1, and T2) shall not exceed 5% opacity except during one six-minute period in any one hour in which visible emissions shall not exceed 10% opacity as determined by the EPA Method 9 (reference 40 CFR 60, Appendix A). This requirement applies at |
| visible emissions— | 20 percent opacityvisible | —— | p. 13 ↗Machine-extracted from a page line in an older official PDF; literal context: During startup and shutdown, visible emissions from each engine gen-set shall not exceed 10% opacity except during one (1) six-minute period in any one-hour in which visible emissions shall not exceed 20% opacity as determined by EPA Method 9 (reference 40 CFR 60, Appendix A). |