Page-cited permit extraction

Corporate Office Properties, L.P. - Park Center

Fairfax Co., Virginia

QA status Machine-extractedRelease dated July 29, 2026

EVIDENCE NOTE

What the public record says

A machine-extracted candidate of equipment groups and permit limits stated in Virginia DEQ permit 74074-6, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.

Primary sourceVirginia DEQ permit document

Virginia Department of Environmental Quality

Open original source ↗

Summary fields cite p. 1, p. 3.

What this record does not establish

The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.

How to read the status

Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.

MACHINE-EXTRACTED CANDIDATE

Equipment and limits,
kept separate from actual use.

These page-cited rows are machine-extracted and still require a second manual review. Verify every reused value against the linked official PDF. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.

Permitted equipment

2 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.

ReferenceEquipment / modelCount / ratingFuel / controlsStated operating fieldSource
8 through 11emergency engine generator setCaterpillar · 3516C4 units2500 kW eachdiesel fuel oilSee operating-scope tablep. 4Machine-extracted from an official document equipment table; column grouping requires second review.
4 and 5emergency engine generator setCaterpillar · 3512C2 units1500 kW eachdiesel fuel oilSee operating-scope tablep. 4Machine-extracted from an official document equipment table; column grouping requires second review.

Operating scope

Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.

ReferenceLimitBasisSource
4 and 5100 hours/yearCorporate Office Properties, L. P. Registration Number: 74074 May 18, 2022 Page 5 5. Operating Hours – Each individual emergency diesel engine gen-set (Ref. Nos. 4 and 5) shall not operate more than 100 hours per year for unscheduled maintenance, testing, operational training, scheduled maintenance checks, and readiness testing (as provided in Conditions 4.c and 4.d) and no more than 500 hours per year for all purposes (as provided iMachine-extracted normative operating-hours statement; second review pending.p. 7
4 and 5500 hours/yeary diesel engine gen-set (Ref. Nos. 4 and 5) shall not operate more than 100 hours per year for unscheduled maintenance, testing, operational training, scheduled maintenance checks, and readiness testing (as provided in Conditions 4.c and 4.d) and no more than 500 hours per year for all purposes (as provided in Condition 4) combined. Each individual emergency diesel engine gen-set (Ref. Nos. 8 through 11) shall not operate more than 500 hours per year for all purposes (as provided in ConditionMachine-extracted normative operating-hours statement; second review pending.p. 7
8 through 11500 hours/yearcks, and readiness testing (as provided in Conditions 4.c and 4.d) and no more than 500 hours per year for all purposes (as provided in Condition 4) combined. Each individual emergency diesel engine gen-set (Ref. Nos. 8 through 11) shall not operate more than 500 hours per year for all purposes (as provided in Condition 4) combined. The annual limits for hours of operation shall be calculated monthly as the sum of each consecutive 12-month period. Compliance for the consecutive 12-month periodMachine-extracted normative operating-hours statement; second review pending.p. 7

Permitted emission limits

17 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.

Inspect 17 transcribed limit rows
ReferencePollutantLimitBasis / scopeSource
Caterpillar 3512C Ref. Nos. 4 and 5NOx as NO229.18 lb/hrhourlyper unitp. 8Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3512C Ref. Nos. 4 and 5 (units combined)NOx as NO214.59 tpyannualcombinedp. 8Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3512C Ref. Nos. 4 and 5NOx as NO24.36 lb/hrhourlyper unitp. 8Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3512C Ref. Nos. 4 and 5 (units combined)NOx as NO22.18 tpyannualcombinedp. 8Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3516C Ref. Nos. 8 through 11NOx as NO248.07 lb/hrhourlyper unitp. 8Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3516C Ref. Nos. 8 through 11 (units combined)NOx as NO248.07 tpyannualcombinedp. 8Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3516C Ref. Nos. 8 through 11NOx as NO26.01 lb/hrhourlyper unitp. 8Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3516C Ref. Nos. 8 through 11 (units combined)NOx as NO26.01 tpyannualcombinedp. 8Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3516C Ref. Nos. 8 through 11VOC1.20 lb/hrhourlyper unitp. 8Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3516C Ref. Nos. 8 through 11 (units combined)VOC1.20 tpyannualcombinedp. 8Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3516C Ref. Nos. 8 through 11PM100.61 lb/hrhourlyper unitp. 8Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3516C Ref. Nos. 8 through 11 (units combined)PM100.61 tpyannualcombinedp. 8Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3516C Ref. Nos. 8 through 11PM2.50.61 lb/hrhourlyper unitp. 8Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3516C Ref. Nos. 8 through 11 (units combined)PM2.50.61 tpyannualcombinedp. 8Machine-extracted from an official permit limit table; header grouping requires second review.
visible emissions5 percent opacityvisiblep. 9Machine-extracted from a page line in an older official PDF; literal context: Page 7 10. Visible Emission Limit – Visible emissions from each emergency diesel engine gen-set (Ref. Nos. 4, 5, and 8 through 11) exhaust shall not exceed 5% opacity except during one 6- minute period in any one hour in which visible emissions shall not exceed 10% opacity as
visible emissions10 percent opacityvisiblep. 9Machine-extracted from a page line in an older official PDF; literal context: 10. Visible Emission Limit – Visible emissions from each emergency diesel engine gen-set (Ref. Nos. 4, 5, and 8 through 11) exhaust shall not exceed 5% opacity except during one 6- minute period in any one hour in which visible emissions shall not exceed 10% opacity as determined by EPA Method 9 (reference 40 CFR 60, Appendix A). This condition applies
visible emissions20 percent opacityvisiblep. 9Machine-extracted from a page line in an older official PDF; literal context: During startup and shutdown, visible emissions from each emergency diesel engine gen-set shall not exceed 10% opacity except during one 6-minute period in any one hour in which visible emissions shall not exceed 20% opacity as determined by EPA Method 9 (reference 40 CFR 60, Appendix A).

DOCUMENT HISTORY

What this document says it changes

amended or superseding permit document

Explicitly supersedes the document dated 2018-01-10.

p. 1, p. 3

QA NOTES

Ambiguity stays visible

  • Machine-extracted candidate. Verify every reused value against the cited official PDF page.
  • Verify table column grouping and any alternative models.
  • Confirm whether the limit is per unit, combined, or limited to testing/maintenance.
  • Confirm multi-row and merged-column header association.
  • Older-PDF text fallback; verify row and unit alignment.
← Return to evidence index