Page-cited permit extraction

CyrusOne Kincora

Loudoun Co., Virginia

QA status Machine-extractedRelease dated July 29, 2026

EVIDENCE NOTE

What the public record says

A machine-extracted candidate of equipment groups and permit limits stated in Virginia DEQ permit 74114-3, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.

Primary sourceVirginia DEQ permit document

Virginia Department of Environmental Quality

Open original source ↗

Summary fields cite p. 1, p. 3.

What this record does not establish

The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.

How to read the status

Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.

MACHINE-EXTRACTED CANDIDATE

Equipment and limits,
kept separate from actual use.

These page-cited rows are machine-extracted and still require a second manual review. Verify every reused value against the linked official PDF. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.

Permitted equipment

5 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.

ReferenceEquipment / modelCount / ratingFuel / controlsStated operating fieldSource
A50, B50, C50, D50, R50, A55, B55, C55, D55, R55, A60, B60, C60, D60, R60emergency engine generator setCaterpillar / MTU15 units2250 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
House 3emergency engine generator setMTU · 16V4000G84S1 units1750 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
20A3, 20B3, 20C3, 20D3, 30BR1, 35BR1, 45AR1, 45BR2, House 2emergency engine generator setMTU9 units2250 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
40AR1, 40B1, 40C1, 40D1emergency engine generator setCummins · DQKAF4 units2250 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
A10, B10, C10, D10, E10, F10, G10, H10, A15, B15, C15, D15, E15, F15, G15, H15, A20, B20, C20, D20, E20, F20, G20, H20, A25, B25, C25, D25, E25, F25, G25, H25, FLEX1, FLEX2, FLEX3, FLEX4, FLEX5, FLEX6, FLEX7, FLEX8, A30, B30, C30, D30, E30, F30, G30, H30, A35, B35, C35, D35, E35, F35, G35, H35, A40, B40, C40, D40, E40, F40, G40, H40, A45, B45, C45, D45, E45, F45, G45, H45, House 1emergency engine generator setMTU73 units2250 kW eachdiesel fuel oilSee operating-scope tablep. 6Machine-extracted from an official document equipment table; column grouping requires second review.

Operating scope

Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.

ReferenceLimitBasisSource
s.18 hours/yearC40, D40, E40, F40, G40, H40, A45, B45, C45, D45, E45, F45, G45, H45, A50, B50, C50, D50, R50, A55, B55, C55, D55, R55, A60, B60, C60, D60, R60, House 1, House 2, House 3, FLEX1, FLEX2, FLEX3, FLEX4, FLEX5, FLEX6, FLEX7, and FLEX8) shall not operate more than 18 hours per year for scheduled maintenance checks and readiness testing (Scheduled MCRT) (as provided in Condition 9c.). b. Each individual emergency diesel engine gen-set (Ref. Nos.: 20A3, 20B3, 20C3, 20D3, 30BR1, 35BR1, 40AR1, 40B1, 4Machine-extracted normative operating-hours statement; second review pending.p. 11
500 hours/yearCyrusOne Kincora Registration Number: 74114 September 6, 2022 Page 10 A55, B55, C55, D55, R55, A60, B60, C60, D60, R60, House 1, House 2, House 3, FLEX1, FLEX2, FLEX3, FLEX4, FLEX5, FLEX6, FLEX7, and FLEX8) shall not operate more than 500 hours per year for all purposes (as provided in Condition 9) combined. The annual limits for hours of operation shall be calculated monthly as the sum of each 12- month period. Compliance for each consecutive 12-month period shall beMachine-extracted normative operating-hours statement; second review pending.p. 12

Permitted emission limits

32 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.

Inspect 32 transcribed limit rows
ReferencePollutantLimitBasis / scopeSource
MTU 16V4000G83NOx as NO244.07 lb/hrhourlyper unitp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3516CNOx as NO243.29 lb/hrhourlyper unitp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 16V4000G83NOx as NO27.16 lb/hrhourlyper unitp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3516CNOx as NO24.04 lb/hrhourlyper unitp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 16V4000G83VOC0.91 lb/hrhourlyper unitp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3516CVOC1.19 lb/hrhourlyper unitp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 16V4000G83PM100.75 lb/hrhourlyper unitp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3516CPM100.43 lb/hrhourlyper unitp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 16V4000G83PM2.50.75 lb/hrhourlyper unitp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3516CPM2.50.43 lb/hrhourlyper unitp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 16V4000G84SNOx as NO233.88 lb/hrhourlyper unitp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 16V4000G84SNOx as NO26.32 lb/hrhourlyper unitp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 16V4000G84SVOC2.07 lb/hrhourlyper unitp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 16V4000G84SPM100.47 lb/hrhourlyper unitp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 16V4000G84SPM2.50.47 lb/hrhourlyper unitp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 16V4000G83NOx as NO244.07 lb/hrhourlyper unitp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 16V4000G83NOx as NO27.16 lb/hrhourlyper unitp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 16V4000G83VOC0.91 lb/hrhourlyper unitp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 16V4000G83PM100.75 lb/hrhourlyper unitp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 16V4000G83PM2.50.75 lb/hrhourlyper unitp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins DQKAFNOx as NO232.69 lb/hrhourlyper unitp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins DQKAFNOx as NO22.17 lb/hrhourlyper unitp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins DQKAFVOC0.47 lb/hrhourlyper unitp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins DQKAFPM100.77 lb/hrhourlyper unitp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins DQKAFPM2.50.77 lb/hrhourlyper unitp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
All OperationsNOx as NO294.61 tpyannualp. 15Machine-extracted from an official permit limit table; header grouping requires second review.
All OperationsNOx as NO236.18 tpyannualp. 15Machine-extracted from an official permit limit table; header grouping requires second review.
All OperationsVOC8.34 tpyannualp. 15Machine-extracted from an official permit limit table; header grouping requires second review.
All OperationsPM105.95 tpyannualp. 15Machine-extracted from an official permit limit table; header grouping requires second review.
All OperationsPM2.55.95 tpyannualp. 15Machine-extracted from an official permit limit table; header grouping requires second review.
visible emissions10 percent opacityvisiblep. 16Machine-extracted from a page line in an older official PDF; literal context: Page 14 During startup and shutdown, visible emissions from each emergency diesel engine gen-set shall not exceed 10% opacity except during one 6-minute period in any one hour in which visible emissions shall not exceed 20% opacity as determined by EPA Method 9 (reference
visible emissions20 percent opacityvisiblep. 16Machine-extracted from a page line in an older official PDF; literal context: During startup and shutdown, visible emissions from each emergency diesel engine gen-set shall not exceed 10% opacity except during one 6-minute period in any one hour in which visible emissions shall not exceed 20% opacity as determined by EPA Method 9 (reference 40 CFR 60, Appendix A).

DOCUMENT HISTORY

What this document says it changes

amended or superseding permit document

Explicitly supersedes the document dated 2019-01-25.

p. 1, p. 3

QA NOTES

Ambiguity stays visible

  • Machine-extracted candidate. Verify every reused value against the cited official PDF page.
  • Verify table column grouping and any alternative models.
  • Confirm whether the limit is per unit, combined, or limited to testing/maintenance.
  • Confirm multi-row and merged-column header association.
  • Older-PDF text fallback; verify row and unit alignment.
← Return to evidence index