Page-verified permit transcription

CyrusOne Sterling IX/X/XI

Loudoun County, Virginia

QA status VerifiedRelease dated July 29, 2026

EVIDENCE NOTE

What the public record says

A manually verified transcription of equipment groups and permit limits stated in Virginia DEQ permit 74173-6, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.

Primary sourceVirginia DEQ permit document

Virginia Department of Environmental Quality

Open original source ↗

Summary fields cite p. 3, p. 4.

What this record does not establish

The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.

How to read the status

Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.

VERIFIED PERMIT TERMS

Equipment and limits,
kept separate from actual use.

This is a conservative transcription of reviewed permit sections, not an exhaustive legal digest. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.

Permitted equipment

9 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.

ReferenceEquipment / modelCount / ratingFuel / controlsStated operating fieldSource
Engine Group 3Cnon-emergency diesel engine-generator setCummins or MTU · QSK60-G19 or 16V4000G84S29 units2250 kW eachdieselSCR+cDPFSee operating-scope tablep. 6Permit allows manufacturer/model alternatives.
Engine Group 4non-emergency diesel engine-generator setCummins or MTU · QSK60-G19 or 16V4000G84S19 units2250 kW eachdieselSCR+cDPFSee operating-scope tablep. 6Permit allows manufacturer/model alternatives.
Engine Group 5 / NVA11_Houseemergency diesel engine-generator setCummins · QSK38-G17 / C1250DE1 units1250 kW eachdieselSee operating-scope tablep. 6
Engine Group 1emergency diesel engine-generator setMTU · 16V4000G84S / 16V4000 DS225016 units2250 kW eachdieselSee operating-scope tablep. 7
House Gen / H-GEN-1Aemergency diesel engine-generator setMTU · 16V4000G74S / 16V4000 DS20001 units2000 kW eachdieselSee operating-scope tablep. 7
Engine Group 2Aemergency diesel engine-generator setCummins · QSK60-G19 / DQKAN2 units2250 kW eachdieselSee operating-scope tablep. 7
Engine Group 2Bemergency diesel engine-generator setCummins · QSK60-G19 / DQKAN9 units2250 kW eachdieselSee operating-scope tablep. 7
Engine Group 3Aemergency diesel engine-generator setCaterpillar · 3516C1 units2500 kW eachdieselSee operating-scope tablep. 7
Engine Group 3Bemergency diesel engine-generator setCummins · QSK60-G19 / DQKAN4 units2250 kW eachdieselSee operating-scope tablep. 7

Operating scope

Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.

ReferenceLimitBasisSource

Permitted emission limits

2 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.

Inspect 2 transcribed limit rows
ReferencePollutantLimitBasis / scopeSource
Engine Groups 3C and 4NOx as NO2controlled3.53 lb/hrhourly; Cummins QSK60-G19per unitp. 16
Engine Groups 3C and 4NOx as NO2uncontrolled42.36 lb/hrhourly; Cummins QSK60-G19per unitp. 16

DOCUMENT HISTORY

What this document says it changes

permit amendment

Explicitly supersedes the document dated 2024-11-19.

p. 3, p. 4

QA NOTES

Ambiguity stays visible

  • Official PDF cover/permit heading checked in the manual second pass.
  • Permit allows manufacturer/model alternatives. — Value transcribed from official permit equipment/condition table; no totals calculated.
  • Value transcribed from official permit equipment/condition table; no totals calculated.
  • Directly stated permitted limit; not an actual emissions value.
← Return to evidence index