Page-verified permit transcription
Equinix LLC Loudoun County, Virginia
QA status VerifiedRelease dated July 29, 2026
EVIDENCE NOTE
What the public record says A manually verified transcription of equipment groups and permit limits stated in Virginia DEQ permit 73233-8, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.
What this record does not establish The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.
How to read the status Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.
DOCUMENT FIELDS
Permittee named in document Equinix, LLC
Permit number 73233-8
Permit action permit amendment
Document date March 19, 2024
Facility address 21691, 21701, 21711, 21715 and 21721 Filigree Court; Ashburn, VA 20147
Application complete —
Explicitly supersedes 2015-03-31
Locality Loudoun County
Regional office Northern Regional Office
Regulator Virginia Department of Environmental Quality VERIFIED PERMIT TERMS
Equipment and limits, kept separate from actual use. This is a conservative transcription of reviewed permit sections, not an exhaustive legal digest. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.
Permitted equipment 7 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.
Reference Equipment / model Count / rating Fuel / controls Stated operating field Source DC1EG-1-DC1EG-3engine-generator set Caterpillar · 3412C / SR4B 3 units 800 kW each diesel — See operating-scope table — p. 5 ↗ DC1EG-4engine-generator set Caterpillar · 3412C / SR4B 1 units 750 kW each diesel — See operating-scope table — p. 5 ↗ DC2EG-1-DC2EG-6engine-generator set Caterpillar · 3516B / SR4B 6 units 2000 kW each diesel — 500 hours hours/year; each unit; consecutive 12-month period p. 5 ↗ , p. 9 ↗ DC2EG-7; DC2EG-Rengine-generator set Caterpillar · 3516C 2 units 2000 kW each diesel — 500 hours hours/year; each unit; consecutive 12-month period p. 5 ↗ , p. 9 ↗ DC4EG-A-DC4EG-E; DC4EG-R; DC4EG-Sengine-generator set Caterpillar · 3516C / SR5 7 units 2500 kW each diesel — 500 hours hours/year; each unit; consecutive 12-month period p. 6 ↗ , p. 9 ↗ DC5EG-A-DC5EG-E; DC5EG-R; DC5EG-Sengine-generator set Caterpillar · 3516C / SR5 7 units 2500 kW each diesel SCR (Miratech) 500 hours hours/year; each unit; consecutive 12-month period p. 6 ↗ , p. 9 ↗ DC6EG-A-DC6EG-E; DC6EG-Rengine-generator set Caterpillar · C175-16 / SR5 6 units 3000 kW each diesel SCR (Miratech) 500 hours hours/year; each unit; consecutive 12-month period p. 6 ↗ , p. 9 ↗
Operating scope Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.
Reference Limit Basis Source DC2EG-1-DC2EG-6500 hours/year hours/year; each unit; consecutive 12-month period Permitted operating-hours field transcribed in the verified pilot equipment table. p. 5 ↗ , p. 9 ↗ DC2EG-7; DC2EG-R500 hours/year hours/year; each unit; consecutive 12-month period Permitted operating-hours field transcribed in the verified pilot equipment table. p. 5 ↗ , p. 9 ↗ DC4EG-A-DC4EG-E; DC4EG-R; DC4EG-S500 hours/year hours/year; each unit; consecutive 12-month period Permitted operating-hours field transcribed in the verified pilot equipment table. p. 6 ↗ , p. 9 ↗ DC5EG-A-DC5EG-E; DC5EG-R; DC5EG-S500 hours/year hours/year; each unit; consecutive 12-month period Permitted operating-hours field transcribed in the verified pilot equipment table. p. 6 ↗ , p. 9 ↗ DC6EG-A-DC6EG-E; DC6EG-R500 hours/year hours/year; each unit; consecutive 12-month period Permitted operating-hours field transcribed in the verified pilot equipment table. p. 6 ↗ , p. 9 ↗
Permitted emission limits 2 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.
Inspect 2 transcribed limit rows Reference Pollutant Limit Basis / scope Source DC5EG-A-DC5EG-E; DC5EG-R; DC5EG-SNOx as NO2 with SCR 4.81 lb/hr hourly per unit — p. 12 ↗ DC5EG-A-DC5EG-E; DC5EG-R; DC5EG-SNOx as NO2 without SCR 48.11 lb/hr hourly per unit — p. 12 ↗
DOCUMENT HISTORY
What this document says it changes permit amendment Explicitly supersedes the document dated 2015-03-31.
p. 3 ↗ , p. 4 ↗ QA NOTES
Ambiguity stays visible Official PDF cover/permit heading checked in the manual second pass. Value transcribed from official permit equipment/condition table; no totals calculated. Directly stated permitted limit; not an actual emissions value.