QA status Machine-extractedRelease dated July 29, 2026
EVIDENCE NOTE
What the public record says
A machine-extracted candidate of equipment groups and permit limits stated in Virginia DEQ permit 74147-1, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.
The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.
How to read the status
Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.
MACHINE-EXTRACTED CANDIDATE
Equipment and limits, kept separate from actual use.
These page-cited rows are machine-extracted and still require a second manual review. Verify every reused value against the linked official PDF. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.
Permitted equipment
1 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.
p. 4 ↗Machine-extracted from explicit permit prose: Equipment Description Rated Capacity Delegated Federal Requirements 2,922 bhp EG-1 through Eight (8) Cummins QSK60-G6 2,000 ekW None EG-8 emergency diesel engine gen-sets (each unit) Specifications included in the table above are for informational purposes only and do n
Operating scope
Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.
Reference
Limit
Basis
Source
EG-1 through EG-8
150 hours/year
Equinix, LLC Registration Number: 74147 December 21 2005, as amended February 26, 2020 Page 4 OPERATING LIMITATIONS 4. Operating Hours - Each Cummins QSK60-G6 emergency diesel engine gen-set (Ref. Nos. EG-1 through EG-8) shall not operate more than 150 hours per year, calculated monthly as the sum of each consecutive 12-month period. Compliance for the consecutive 12-month period shall be demonstrated monthly by adding the total for the most recently completed calendar month to theMachine-extracted normative operating-hours statement; second review pending.
p. 7 ↗Machine-extracted from a page line in an older official PDF; literal context: diesel engine gen-sets (Ref. Nos. EG-1 through EG-8) shall not exceed the limits specified below: Nitrogen Oxides (as N02) 35.43 Ib/hr (each) 21.26 tons/yr (combined) Carbon Monoxide (CO) 8.37 Ib/hr (each) 5.02 tons/yr (combined)
p. 7 ↗Machine-extracted from a page line in an older official PDF; literal context: Nitrogen Oxides (as N02) 35.43 Ib/hr (each) 21.26 tons/yr (combined) Carbon Monoxide (CO) 8.37 Ib/hr (each) 5.02 tons/yr (combined) Volatile Organic Compounds (VOCs) 2.58 Ib/hr (each) 1.55 tons/yr (combined) These emissions are derived from the estimated overall emission contribution from
p. 7 ↗Machine-extracted from a page line in an older official PDF; literal context: (9 VAC 5-80-1180a nd 9 VAC 5-50-260) 8. Visible Emission Limit - Visible emissions from each Cummins QSK60-G6 emergency diesel engine gen-set (Ref. Nos. EG-1 through EG-8) shall not exceed 20 percent opacity except during one 6-minute period in any one hour in which visible emissions shall not
p. 7 ↗Machine-extracted from a page line in an older official PDF; literal context: diesel engine gen-set (Ref. Nos. EG-1 through EG-8) shall not exceed 20 percent opacity except during one 6-minute period in any one hour in which visible emissions shall not exceed 30 percent opacity as determined by EPA Method 9 (reference 40 CFR 60, Appendix A). This condition applies at all times except during startup, shutdown and
visible emissions—
30 percent opacityvisible
per exhaust/source—
p. 7 ↗Machine-extracted normative visible-emission limit; second review pending.
DOCUMENT HISTORY
What this document says it changes
amended or superseding permit document
No superseded-document date is asserted beyond the cited source wording.