Page-cited permit extraction

Freddie Mac Corporation

Fairfax Co., Virginia

QA status Machine-extractedRelease dated July 29, 2026

EVIDENCE NOTE

What the public record says

A machine-extracted candidate of equipment groups and permit limits stated in Virginia DEQ permit 73105-2, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.

Primary sourceVirginia DEQ permit document

Virginia Department of Environmental Quality

Open original source ↗

Summary fields cite p. 1, p. 3.

What this record does not establish

The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.

How to read the status

Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.

MACHINE-EXTRACTED CANDIDATE

Equipment and limits,
kept separate from actual use.

These page-cited rows are machine-extracted and still require a second manual review. Verify every reused value against the linked official PDF. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.

Permitted equipment

1 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.

ReferenceEquipment / modelCount / ratingFuel / controlsStated operating fieldSource
engine generator set4 unitsNo reliable per-unit rating transcribeddiesel fuel oilSee operating-scope tablep. 1Machine-extracted from explicit permit prose: Becker: Attached is a permit to modify and operate four diesel engine-generators sets at your corporate data center in Herndon, Virginia, in accordance with the provisions of the C

Operating scope

Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.

ReferenceLimitBasisSource
1400 hours/yearection and shall be in operation when its respective diesel engine-generator set is operating. (9 VAC 5-80-1180 D) OPERATING LIMITATIONS 4. Operating Hours - The combined operating hours for ihe diesei engine-generator sets (Ref. No.'s 1 - 4) shall not exceed 1400 hours per year, calculated monthly as the sum of each consecutive twelve month period. Compliance for the consecutive twelve month period shall be demonstrated monthly by adding the total for the most recently completed calendar monthMachine-extracted normative operating-hours statement; second review pending.p. 5

Permitted emission limits

6 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.

Inspect 6 transcribed limit rows
ReferencePollutantLimitBasis / scopeSource
diesel engine-generator sets (Ref. No.'s 1 - 4)NOx as NO224.4 tpyannualp. 6Machine-extracted from a page line in an older official PDF; literal context: (Ref. No.'s 1 - 4) shall not exceed the limits specified below: Each Engine-Generator Set All Engine-Generator Sets Nitrogen Oxides 41.16 Ibs/hr 24.4 tons/yr (as N0 )
NOx as NO21.56 tpyannualp. 7Machine-extracted from a page line in an older official PDF; literal context: July 26, 2007 Page 5 Carbon Monoxide 4.01 Ibs/hr 1.56 tons/yr Sulfur Dioxide 11.52 Ibs/hr 8.06 tons/yr
SO28.06 tpyannualp. 7Machine-extracted from a page line in an older official PDF; literal context: Page 5 Carbon Monoxide 4.01 Ibs/hr 1.56 tons/yr Sulfur Dioxide 11.52 Ibs/hr 8.06 tons/yr The hourly emission rates are derived from the manufacturer's not-to-exceed data at
visible emissions10 percent opacityvisiblep. 7Machine-extracted from a page line in an older official PDF; literal context: (9 VAC 5-80-1180) 10. Visible Emission Limit - Visible emissions from each diesel engine-generator set (Ref. No.'s 1-4) shall not exceed 10% opacity except during one six-minute period in any one hour in which visible emissions shall not exceed 20% opacity as
visible emissions20 percent opacityvisiblep. 7Machine-extracted from a page line in an older official PDF; literal context: 10. Visible Emission Limit - Visible emissions from each diesel engine-generator set (Ref. No.'s 1-4) shall not exceed 10% opacity except during one six-minute period in any one hour in which visible emissions shall not exceed 20% opacity as determined by the EPA Method 9 (reference 40 CFR 60, Appendix A). This
visible emissions30 percent opacityvisiblep. 7Machine-extracted from a page line in an older official PDF; literal context: During start-up and shut-down times, visible emissions from each diesel engine- generator (Ref. No.'s 1 - 4 ) shall not exceed 20% except during one six-minute period in any one hour in which visible emissions shall not exceed 30% opacity as determined by the EPA Method 9 (reference 40 CFR 60, Appendix A).

DOCUMENT HISTORY

What this document says it changes

permit to modify and operate

No superseded-document date is asserted beyond the cited source wording.

p. 1, p. 3

QA NOTES

Ambiguity stays visible

  • Machine-extracted candidate. Verify every reused value against the cited official PDF page.
  • Prose fallback; verify equipment grouping.
  • Confirm whether the limit is per unit, combined, or limited to testing/maintenance.
  • Older-PDF text fallback; verify row and unit alignment.
← Return to evidence index