Page-cited permit extraction

Herndon Technology Partners LLC

Fairfax Co., Virginia

QA status Machine-extractedRelease dated July 29, 2026

EVIDENCE NOTE

What the public record says

A machine-extracted candidate of equipment groups and permit limits stated in Virginia DEQ permit 74332-1, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.

Primary sourceVirginia DEQ permit document

Virginia Department of Environmental Quality

Open original source ↗

Summary fields cite p. 1, p. 3.

What this record does not establish

The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.

How to read the status

Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.

MACHINE-EXTRACTED CANDIDATE

Equipment and limits,
kept separate from actual use.

These page-cited rows are machine-extracted and still require a second manual review. Verify every reused value against the linked official PDF. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.

Permitted equipment

2 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.

ReferenceEquipment / modelCount / ratingFuel / controlsStated operating fieldSource
GEN-1 through GEN-28emergency engine generator setMTU · 20V4000G94S28 units3000 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
GEN-H01emergency engine generator setMTU · 12V4000G84S1 units1750 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.

Operating scope

Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.

ReferenceLimitBasisSource
GEN-1 through GEN-28136 hours/yearh unit (which involves fuel combustion) shall be minimized to the maximum extent practical. (9VAC5-80-1180) [January 30, 2026] 7. Operating Hours – a. The emergency diesel engine gen-sets (Ref. Nos. GEN-1 through GEN-28) combined shall not operate more than 3,136 hours per year for all purposes (as provided in Condition 3) combined, and each individual emergency diesel engine gen-set (Ref. Nos. GEN-1 through GEN-28) shall not operate more than 500 hours per year for all purposes (as provided iMachine-extracted normative operating-hours statement; second review pending.p. 7
GEN-1 through GEN-28500 hours/year(Ref. Nos. GEN-1 through GEN-28) combined shall not operate more than 3,136 hours per year for all purposes (as provided in Condition 3) combined, and each individual emergency diesel engine gen-set (Ref. Nos. GEN-1 through GEN-28) shall not operate more than 500 hours per year for all purposes (as provided in Condition 3) combined.Machine-extracted normative operating-hours statement; second review pending.p. 7
GEN-H01112 hours/yearHerndon Technology Partners LLC Registration Number: 74332 January 30, 2026 Page 6 b. The emergency diesel engine gen-set (Ref. Nos. GEN-H01) shall not operate more than 112 hours per year for all purposes (as provided in Condition 3) combined. c. Each individual emergency diesel engine gen-set (Ref. Nos. GEN-1 through GEN-28 and Ref. Nos. GEN-H01) shall not operate more than 29 hours per year for SchedulMachine-extracted normative operating-hours statement; second review pending.p. 8
GEN-H0129 hours/yearet (Ref. Nos. GEN-H01) shall not operate more than 112 hours per year for all purposes (as provided in Condition 3) combined. c. Each individual emergency diesel engine gen-set (Ref. Nos. GEN-1 through GEN-28 and Ref. Nos. GEN-H01) shall not operate more than 29 hours per year for Scheduled MCRT (as provided in Condition 3.c). The annual limits for hours of operation shall be calculated monthly as the sum of each consecutive 12-month period. Compliance for the consecutive 12-month period shalMachine-extracted normative operating-hours statement; second review pending.p. 8

Permitted emission limits

30 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.

Inspect 30 transcribed limit rows
ReferencePollutantLimitBasis / scopeSource
MTU 20V4000G94S (Ref. Nos. GEN-1 through GEN-28)NOx as NO261.78 lb/hrhourlyper unitp. 9Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 12V4000G84S (Ref. Nos. GEN-H01)NOx as NO233.90 lb/hrhourlyp. 9Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 20V4000G94S (Ref. Nos. GEN-1 through GEN-28)NOx as NO29.39 lb/hrhourlyper unitp. 9Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 12V4000G84S (Ref. Nos. GEN-H01)NOx as NO25.47 lb/hrhourlyp. 9Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 20V4000G94S (Ref. Nos. GEN-1 through GEN-28)VOC2.67 lb/hrhourlyper unitp. 9Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 12V4000G84S (Ref. Nos. GEN-H01)VOC1.05 lb/hrhourlyp. 9Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 20V4000G94S (Ref. Nos. GEN-1 through GEN-28)PM0.98 lb/hrhourlyper unitp. 9Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 12V4000G84S (Ref. Nos. GEN-H01)PM0.50 lb/hrhourlyp. 9Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 20V4000G94S (Ref. Nos. GEN-1 through GEN-28)PM100.98 lb/hrhourlyper unitp. 9Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 12V4000G84S (Ref. Nos. GEN-H01)PM100.50 lb/hrhourlyp. 9Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 20V4000G94S (Ref. Nos. GEN-1 through GEN-28)PM2.50.98 lb/hrhourlyper unitp. 9Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 12V4000G84S (Ref. Nos. GEN-H01)PM2.50.50 lb/hrhourlyp. 9Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 20V4000G94S (Ref. Nos. GEN-1 through GEN-28)NOx as NO296.88 tpyannualp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 12V4000G84S (Ref. Nos. GEN-H01)NOx as NO21.90 tpyannualp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
All units (Ref. Nos. GEN-1 through GEN-28 and GEN-H01)NOx as NO298.78 tpyannualcombinedp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 20V4000G94S (Ref. Nos. GEN-1 through GEN-28)NOx as NO214.72 tpyannualp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 12V4000G84S (Ref. Nos. GEN-H01)NOx as NO20.31 tpyannualp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
All units (Ref. Nos. GEN-1 through GEN-28 and GEN-H01)NOx as NO215.03 tpyannualcombinedp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 20V4000G94S (Ref. Nos. GEN-1 through GEN-28)VOC4.19 tpyannualp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 12V4000G84S (Ref. Nos. GEN-H01)VOC0.06 tpyannualp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
All units (Ref. Nos. GEN-1 through GEN-28 and GEN-H01)VOC4.25 tpyannualcombinedp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 20V4000G94S (Ref. Nos. GEN-1 through GEN-28)PM1.53 tpyannualp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 12V4000G84S (Ref. Nos. GEN-H01)PM0.03 tpyannualp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
All units (Ref. Nos. GEN-1 through GEN-28 and GEN-H01)PM1.56 tpyannualcombinedp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 20V4000G94S (Ref. Nos. GEN-1 through GEN-28)PM101.53 tpyannualp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 12V4000G84S (Ref. Nos. GEN-H01)PM100.03 tpyannualp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
All units (Ref. Nos. GEN-1 through GEN-28 and GEN-H01)PM101.56 tpyannualcombinedp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 20V4000G94S (Ref. Nos. GEN-1 through GEN-28)PM2.51.53 tpyannualp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
MTU 12V4000G84S (Ref. Nos. GEN-H01)PM2.50.03 tpyannualp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
All units (Ref. Nos. GEN-1 through GEN-28 and GEN-H01)PM2.51.56 tpyannualcombinedp. 10Machine-extracted from an official permit limit table; header grouping requires second review.

DOCUMENT HISTORY

What this document says it changes

permit to construct and operate

No superseded-document date is asserted beyond the cited source wording.

p. 1, p. 3

QA NOTES

Ambiguity stays visible

  • Machine-extracted candidate. Verify every reused value against the cited official PDF page.
  • Verify table column grouping and any alternative models.
  • Confirm whether the limit is per unit, combined, or limited to testing/maintenance.
  • Confirm multi-row and merged-column header association.
← Return to evidence index