A manually verified transcription of equipment groups and permit limits stated in Virginia DEQ permit 73935-7, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.
The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.
How to read the status
Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.
VERIFIED PERMIT TERMS
Equipment and limits, kept separate from actual use.
This is a conservative transcription of reviewed permit sections, not an exhaustive legal digest. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.
Permitted equipment
4 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.
Reference
Equipment / model
Count / rating
Fuel / controls
Stated operating field
Source
A00
emergency engine-generator setKohler or Caterpillar or Cummins · KD900 or C32 or 900DQFAC
1 units1000 kW each
diesel—
24 hourshours/year scheduled maintenance/readiness testing; each unit
p. 5 ↗, p. 8 ↗Permit allows manufacturer/model alternatives.
A01-A42
emergency engine-generator setKohler or Caterpillar or Cummins · KD2250 or 3516C or DQKAF
42 units2250 kW each
diesel—
24 hourshours/year scheduled maintenance/readiness testing; each unit
p. 5 ↗, p. 8 ↗Permit allows manufacturer/model alternatives.
B01-B20
emergency engine-generator setKohler · KD2250
20 units2250 kW each
diesel—
100 hourshours/year maintenance/readiness testing; each unit