Page-verified permit transcription

NTT Global Data Centers Americas, Inc.

Loudoun County, Virginia

QA status VerifiedRelease dated July 29, 2026

EVIDENCE NOTE

What the public record says

A manually verified transcription of equipment groups and permit limits stated in Virginia DEQ permit 74120-7, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.

Primary sourceVirginia DEQ permit document

Virginia Department of Environmental Quality

Open original source ↗

Summary fields cite p. 3, p. 4.

What this record does not establish

The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.

How to read the status

Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.

VERIFIED PERMIT TERMS

Equipment and limits,
kept separate from actual use.

This is a conservative transcription of reviewed permit sections, not an exhaustive legal digest. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.

Permitted equipment

9 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.

ReferenceEquipment / modelCount / ratingFuel / controlsStated operating fieldSource
VA7emergency engine-generator setCummins · QSK95-G1224 units3250 kW eachdiesel500 hourshours/year for all purposes; no single unitp. 5, p. 10
Gen7Hemergency engine-generator setCummins · QSK50-G51 units1500 kW eachdiesel500 hourshours/year for all purposes; no single unitp. 5, p. 10
VA3emergency engine-generator setKohler · KD45V2025 units1500 kW eachdiesel500 hourshours/year for all purposes; no single unitp. 5, p. 10Permit states de-rated capacity.
VA4emergency engine-generator setKohler · KD83V1620 units3250 kW eachdiesel500 hourshours/year for all purposes; no single unitp. 5, p. 10
Gen4Hemergency engine-generator setKohler · KD45V201 units1500 kW eachdiesel500 hourshours/year for all purposes; no single unitp. 6, p. 10Permit states de-rated capacity.
VA5emergency engine-generator setKohler · KD83V1620 units3250 kW eachdiesel500 hourshours/year for all purposes; no single unitp. 6, p. 10
Gen5Hemergency engine-generator setKohler · KD45V201 units1500 kW eachdiesel500 hourshours/year for all purposes; no single unitp. 6, p. 10Permit states de-rated capacity.
VA6emergency engine-generator setCummins · QSK95-G1216 units3250 kW eachdiesel500 hourshours/year for all purposes; no single unitp. 6, p. 10
Gen6Hemergency engine-generator setCummins · QSK50-G51 units1500 kW eachdiesel500 hourshours/year for all purposes; no single unitp. 6, p. 10

Operating scope

Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.

ReferenceLimitBasisSource
VA7500 hours/yearhours/year for all purposes; no single unitPermitted operating-hours field transcribed in the verified pilot equipment table.p. 5, p. 10
Gen7H500 hours/yearhours/year for all purposes; no single unitPermitted operating-hours field transcribed in the verified pilot equipment table.p. 5, p. 10
VA3500 hours/yearhours/year for all purposes; no single unitPermitted operating-hours field transcribed in the verified pilot equipment table.p. 5, p. 10
VA4500 hours/yearhours/year for all purposes; no single unitPermitted operating-hours field transcribed in the verified pilot equipment table.p. 5, p. 10
Gen4H500 hours/yearhours/year for all purposes; no single unitPermitted operating-hours field transcribed in the verified pilot equipment table.p. 6, p. 10
VA5500 hours/yearhours/year for all purposes; no single unitPermitted operating-hours field transcribed in the verified pilot equipment table.p. 6, p. 10
Gen5H500 hours/yearhours/year for all purposes; no single unitPermitted operating-hours field transcribed in the verified pilot equipment table.p. 6, p. 10
VA6500 hours/yearhours/year for all purposes; no single unitPermitted operating-hours field transcribed in the verified pilot equipment table.p. 6, p. 10
Gen6H500 hours/yearhours/year for all purposes; no single unitPermitted operating-hours field transcribed in the verified pilot equipment table.p. 6, p. 10

Permitted emission limits

5 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.

Inspect 5 transcribed limit rows
ReferencePollutantLimitBasis / scopeSource
VA3NOx as NO211.25 tpyannualgroup totalp. 13
VA4 and Gen4HNOx as NO220.85 tpyannualgroup totalp. 13
VA5 and Gen5HNOx as NO220.85 tpyannualgroup totalp. 13
VA6 and Gen6HNOx as NO216.96 tpyannualgroup totalp. 13
VA7 and Gen7HNOx as NO223.29 tpyannualgroup totalp. 13

DOCUMENT HISTORY

What this document says it changes

permit amendment

Explicitly supersedes the document dated 2022-11-17.

p. 3, p. 4

QA NOTES

Ambiguity stays visible

  • Official PDF cover/permit heading checked in the manual second pass.
  • Value transcribed from official permit equipment/condition table; no totals calculated.
  • Permit states de-rated capacity. — Value transcribed from official permit equipment/condition table; no totals calculated.
  • Directly stated permitted limit; not an actual emissions value.