QA status Machine-extractedRelease dated July 29, 2026
EVIDENCE NOTE
What the public record says
A machine-extracted candidate of equipment groups and permit limits stated in Virginia DEQ permit 74094-1, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.
The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.
How to read the status
Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.
MACHINE-EXTRACTED CANDIDATE
Equipment and limits, kept separate from actual use.
These page-cited rows are machine-extracted and still require a second manual review. Verify every reused value against the linked official PDF. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.
Permitted equipment
1 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.
Reference
Equipment / model
Count / rating
Fuel / controls
Stated operating field
Source
emergency engine generator setCummins · QSK60- 2
13 units2250 kW each
diesel fuel oil—
See operating-scope table—
p. 4 ↗Machine-extracted from explicit permit prose: 21M thru Thirteen (13) Cummins QSK60- 2,250 kW/ None 23M, 21U G14NR2 model diesel engine 3,280 bhp thru 24U, emergency gen-sets (each) 24M, and 25U thru 29U Specifications included in the above table are for informational purpo
Operating scope
Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.
Reference
Limit
Basis
Source
21Mthru23M 24M,and 250 thru 290
300 hours/year
normalevente^emaltothelSOserviceterritorythatmay require ISO action. c. For periodic maintenance, testing, and operational training. (9^AC5-60-1160) 6 Operating r^ours^Eachengine-generatorset(Ref.Nos.21Mthru23M 24M,and 250 thru 290) shall not operate morethan 300 hours peryear,calculated monthly as the sum ofeach consecutive 12 month period. Compliancefortheconsecutive 12 month period shall bedemonstrated monthly by addingthetotalforthemostrecently completed calendarmonthto the individual monMachine-extracted normative operating-hours statement; second review pending.
p. 7 ↗Machine-extracted from a page line in an older official PDF; literal context: Pollutant Each Engine 13 Engines PM/Pr\1irVPIvl2.5 0.65 Ib/hr 1.27 tons/yr NO, 43.35 Ib/hr 84.53 tons/yr
p. 7 ↗Machine-extracted from a page line in an older official PDF; literal context: PM/Pr\1irVPIvl2.5 0.65 Ib/hr 1.27 tons/yr NO, 43.35 Ib/hr 84.53 tons/yr CO 2.89 Ib/hr 5.64 tons/yr VOC 0.58 Ib/hr 1.13 tons/yr
p. 7 ↗Machine-extracted from a page line in an older official PDF; literal context: NO, 43.35 Ib/hr 84.53 tons/yr CO 2.89 Ib/hr 5.64 tons/yr VOC 0.58 Ib/hr 1.13 tons/yr These emissions are derived from the estimated overall emission contribution from
p. 7 ↗Machine-extracted from a page line in an older official PDF; literal context: (9 VAC 5-80-1180 and 9 VAC 5-50-260) 10. Visible Emission Limit - Visible emissions from each engine-generator set exhaust (Ref. Nos. 21M thru 23M, 21U thru 24U, 24M, and 25U thru 29U) shall not exceed 5% opacity except during one 6-minute period in any one hour in which visible emissions shall not
p. 7 ↗Machine-extracted from a page line in an older official PDF; literal context: Nos. 21M thru 23M, 21U thru 24U, 24M, and 25U thru 29U) shall not exceed 5% opacity except during one 6-minute period in any one hour in which visible emissions shall not exceed 10% opacity as determined by EPA Method 9 (reference 40 CFR 60, Appendix A). This condition applies at all times except during startup, shutdown and malfunction.
DOCUMENT HISTORY
What this document says it changes
permit to construct and operate
No superseded-document date is asserted beyond the cited source wording.