Ref. No. Gen01 | NOx as NO2— | 10.86 lb/hrhourly | —— | p. 10 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. No. Gen01 | NOx as NO2— | 56.34 lb/hrhourly | —— | p. 10 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. Nos. Gen21 through Gen37 | NOx as NO2— | 48.06 lb/hrhourly | per unit— | p. 10 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. No. Gen 38 | NOx as NO2— | 24.09 lb/hrhourly | —— | p. 10 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. No. Gen01 | NOx as NO2— | 1.14 lb/hrhourly | —— | p. 10 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. No. Gen01 | NOx as NO2— | 8.45 lb/hrhourly | —— | p. 10 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. Nos. Gen21 through Gen37 | NOx as NO2— | 6.09 lb/hrhourly | per unit— | p. 10 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. No. Gen 38 | NOx as NO2— | 2.10 lb/hrhourly | —— | p. 10 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. No. Gen01 | PM10— | 0.19 lb/hrhourly | —— | p. 10 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. No. Gen01 | PM10— | 0.94 lb/hrhourly | —— | p. 10 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. Nos. Gen21 through Gen37 | PM10— | 0.58 lb/hrhourly | per unit— | p. 10 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. No. Gen 38 | PM10— | 0.27 lb/hrhourly | —— | p. 10 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. No. Gen01 | PM2.5— | 0.19 lb/hrhourly | —— | p. 10 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. No. Gen01 | PM2.5— | 0.94 lb/hrhourly | —— | p. 10 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. Nos. Gen21 through Gen37 | PM2.5— | 0.58 lb/hrhourly | per unit— | p. 10 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. No. Gen 38 | PM2.5— | 0.27 lb/hrhourly | —— | p. 10 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. No. Gen01 | VOC— | 0.38 lb/hrhourly | —— | p. 10 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. No. Gen01 | VOC— | 2.12 lb/hrhourly | —— | p. 10 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. Nos. Gen21 through Gen37 | VOC— | 1.21 lb/hrhourly | per unit— | p. 10 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. No. Gen 38 | VOC— | 0.40 lb/hrhourly | —— | p. 10 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. No. Gen01 | NOx as NO2— | 0.55 tpyannual | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. Nos. Gen02 through Gen20 | NOx as NO2— | 2.87 tpyannual | per unit— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. Nos. Gen01 through Gen20 (all units combined) | NOx as NO2— | 55.15 tpyannual | combined— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. Nos. Gen01 through Gen20 (all units combined) | NOx as NO2— | 42.90 tpyannual | combined— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. No. Gen01 | NOx as NO2— | 0.06 tpyannual | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. Nos. Gen02 through Gen20 | NOx as NO2— | 0.43 tpyannual | per unit— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. Nos. Gen01 through Gen20 (all units combined) | NOx as NO2— | 23.10 tpyannual | combined— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. No. Gen01 | PM10— | 0.01 tpyannual | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. Nos. Gen02 through Gen20 | PM10— | 0.05 tpyannual | per unit— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. Nos. Gen01 through Gen20 (all units combined) | PM10— | 1.74 tpyannual | combined— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. No. Gen01 | PM2.5— | 0.01 tpyannual | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. Nos. Gen02 through Gen20 | PM2.5— | 0.05 tpyannual | per unit— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. Nos. Gen01 through Gen20 (all units combined) | PM2.5— | 1.74 tpyannual | combined— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. No. Gen01 | VOC— | 0.02 tpyannual | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. Nos. Gen02 through Gen20 | VOC— | 0.11 tpyannual | per unit— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. Nos. Gen01 through Gen20 (all units combined) | VOC— | 2.11 tpyannual | combined— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. Nos. Gen01 through Gen20 (all units combined) | VOC— | 4.83 tpyannual | combined— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. Nos. CT01 through CT11 (all units combined) | PM— | 5.83 tpyannual | combined— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
Ref. Nos. CT01 through CT11 (all units combined) | PM10— | 3.73 tpyannual | combined— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |