Page-verified permit transcription

QTS Richmond V LLC

Henrico County, Virginia

QA status VerifiedRelease dated July 29, 2026

EVIDENCE NOTE

What the public record says

A manually verified transcription of equipment groups and permit limits stated in Virginia DEQ permit 53259-1, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.

Primary sourceVirginia DEQ permit document

Virginia Department of Environmental Quality

Open original source ↗

Summary fields cite p. 3, p. 4.

What this record does not establish

The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.

How to read the status

Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.

VERIFIED PERMIT TERMS

Equipment and limits,
kept separate from actual use.

This is a conservative transcription of reviewed permit sections, not an exhaustive legal digest. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.

Permitted equipment

2 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.

ReferenceEquipment / modelCount / ratingFuel / controlsStated operating fieldSource
GEN001-GEN247emergency engine gen-setCaterpillar / MTU · 3516C / 20V4000 DS2500 / 16V4000 DS2250247 units2500 or 2250 kW eachdiesel fuel oil unless noted in permitturbocharged engine and aftercoolerSee operating-scope tablep. 4Permit allows any of three listed models; count is collective, not per model.
HGEN001-HGEN008emergency engine gen-setCaterpillar · C328 units1250 kW eachdiesel fuel oil unless noted in permitturbocharged engine and aftercoolerSee operating-scope tablep. 4

Operating scope

Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.

ReferenceLimitBasisSource
GEN001-GEN247 and HGEN001-HGEN008500 hours/year per unitall purposes; rolling consecutive 12 monthsCondition 6 continues on PDF page 7.p. 6

Permitted emission limits

32 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.

Inspect 32 transcribed limit rows
ReferencePollutantLimitBasis / scopeSource
GEN001-GEN247 / Caterpillar 3516CNOx as NO2emergency48.1 lb/hrhourlyper unitemergency operationp. 8
GEN001-GEN247 / Caterpillar 3516CPMemergency0.4 lb/hrhourlyper unitemergency operationp. 8
GEN001-GEN247 / Caterpillar 3516CPM10emergency0.6 lb/hrhourlyper unitemergency operationp. 8
GEN001-GEN247 / Caterpillar 3516CPM2.5emergency0.6 lb/hrhourlyper unitemergency operationp. 8
GEN001-GEN247 / Caterpillar 3516CCOemergency6.1 lb/hrhourlyper unitemergency operationp. 8
GEN001-GEN247 / Caterpillar 3516CVOCemergency1.2 lb/hrhourlyper unitemergency operationp. 8
GEN001-GEN247 / MTU 20V4000 DS2500NOx as NO2emergency48.5 lb/hrhourlyper unitemergency operationp. 8
GEN001-GEN247 / MTU 20V4000 DS2500PMemergency1.0 lb/hrhourlyper unitemergency operationp. 8
GEN001-GEN247 / MTU 20V4000 DS2500PM10emergency1.2 lb/hrhourlyper unitemergency operationp. 8
GEN001-GEN247 / MTU 20V4000 DS2500PM2.5emergency1.2 lb/hrhourlyper unitemergency operationp. 8
GEN001-GEN247 / MTU 20V4000 DS2500COemergency11.9 lb/hrhourlyper unitemergency operationp. 8
GEN001-GEN247 / MTU 20V4000 DS2500VOCemergency2.3 lb/hrhourlyper unitemergency operationp. 8
GEN001-GEN247 / MTU 16V4000 DS2250NOx as NO2emergency44.4 lb/hrhourlyper unitemergency operationp. 8
GEN001-GEN247 / MTU 16V4000 DS2250PMemergency0.8 lb/hrhourlyper unitemergency operationp. 8
GEN001-GEN247 / MTU 16V4000 DS2250PM10emergency1.0 lb/hrhourlyper unitemergency operationp. 8
GEN001-GEN247 / MTU 16V4000 DS2250PM2.5emergency1.0 lb/hrhourlyper unitemergency operationp. 8
GEN001-GEN247 / MTU 16V4000 DS2250COemergency12.0 lb/hrhourlyper unitemergency operationp. 8
GEN001-GEN247 / MTU 16V4000 DS2250VOCemergency1.8 lb/hrhourlyper unitemergency operationp. 8
HGEN001-HGEN008 / Caterpillar C32NOx as NO2emergency24.09 lb/hrhourlyper unitemergency operationp. 8
HGEN001-HGEN008 / Caterpillar C32PMemergency0.24 lb/hrhourlyper unitemergency operationp. 8
HGEN001-HGEN008 / Caterpillar C32PM10emergency0.26 lb/hrhourlyper unitemergency operationp. 8
HGEN001-HGEN008 / Caterpillar C32PM2.5emergency0.26 lb/hrhourlyper unitemergency operationp. 8
HGEN001-HGEN008 / Caterpillar C32COemergency1.67 lb/hrhourlyper unitemergency operationp. 8
HGEN001-HGEN008 / Caterpillar C32VOCemergency0.4 lb/hrhourlyper unitemergency operationp. 8
GEN001-GEN247 and HGEN001-HGEN008PMall operations4.5 tpyannualall units combinedall permitted emergency modesp. 8
GEN001-GEN247 and HGEN001-HGEN008PM10all operations4.9 tpyannualall units combinedall permitted emergency modesp. 8
GEN001-GEN247 and HGEN001-HGEN008PM2.5all operations4.9 tpyannualall units combinedall permitted emergency modesp. 8
GEN001-GEN247 and HGEN001-HGEN008NOx as NO2all operations99.0 tpyannualall units combinedall permitted emergency modesp. 8
GEN001-GEN247 and HGEN001-HGEN008COall operations34.3 tpyannualall units combinedall permitted emergency modesp. 8
GEN001-GEN247 and HGEN001-HGEN008VOCall operations18.6 tpyannualall units combinedall permitted emergency modesp. 8
GEN001-GEN247 and HGEN001-HGEN008visible emissionsstated opacity limit10 percent opacityvisibleper exhaust/sourcenormal operation except startup/shutdown/malfunctionp. 9
GEN001-GEN247 and HGEN001-HGEN008visible emissionsstated opacity limit20 percent opacityvisibleper exhaust/sourceone six-minute period in any one hourp. 9

DOCUMENT HISTORY

What this document says it changes

new minor NSR permit

No superseded-document date is asserted beyond the cited source wording.

p. 3, p. 4

QA NOTES

Ambiguity stays visible

  • Transcribed from exact official PDF; source page is 1-based PDF position.
← Return to evidence index