Page-cited permit extraction

SI NVA01 ABS, LLC

Loudoun Co., Virginia

QA status Machine-extractedRelease dated July 29, 2026

EVIDENCE NOTE

What the public record says

A machine-extracted candidate of equipment groups and permit limits stated in Virginia DEQ permit 74079-5, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.

Primary sourceVirginia DEQ permit document

Virginia Department of Environmental Quality

Open original source ↗

Summary fields cite p. 1.

What this record does not establish

The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.

How to read the status

Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.

MACHINE-EXTRACTED CANDIDATE

Equipment and limits,
kept separate from actual use.

These page-cited rows are machine-extracted and still require a second manual review. Verify every reused value against the linked official PDF. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.

Permitted equipment

7 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.

ReferenceEquipment / modelCount / ratingFuel / controlsStated operating fieldSource
13 through 17engine generator setCaterpillar · 3516E5 units3000 kW eachdiesel fuel oilSee operating-scope tablep. 4Machine-extracted from an official document equipment table; column grouping requires second review.
10 through 12engine generator setCummins · 2500DQKAN3 units2500 or 2000 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
1 through 9engine generator setCaterpillar · Diesel 3516A9 units1750 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
Twoboiler2 unitsNo reliable per-unit rating transcribedSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
engine generator set unitsNo reliable per-unit rating transcribedSee operating-scope tablep. 12Machine-extracted from an official document equipment table; column grouping requires second review.
Pollutantemergency engine generator set1 unitsNo reliable per-unit rating transcribeddiesel fuel oilSee operating-scope tablep. 13Machine-extracted from an official document equipment table; column grouping requires second review.
engine generator set unitsNo reliable per-unit rating transcribedSee operating-scope tablep. 13Machine-extracted from an official document equipment table; column grouping requires second review.

Operating scope

Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.

ReferenceLimitBasisSource
1 through 9200 hours/yearliance with this condition shall be demonstrated utilizing the electric output data from the required monitoring device in Condition 3. (9 VAC 5-80-1180) 11. Operating Hours – Each diesel engine-generator set (Ref. Nos. 1 through 9) shall operate no more than 200 hours per year, calculated monthly as the sum of each consecutive 12 month period. Each diesel engine-generator set equipped with SCR (Ref. Nos. 1, 3, 4, 5, 6, 7 & 9) shall not operate without urea injection for more than 50 hours perMachine-extracted normative operating-hours statement; second review pending.p. 9
1, 3, 4, 5, 6, 7 & 950 hours/yearugh 9) shall operate no more than 200 hours per year, calculated monthly as the sum of each consecutive 12 month period. Each diesel engine-generator set equipped with SCR (Ref. Nos. 1, 3, 4, 5, 6, 7 & 9) shall not operate without urea injection for more than 50 hours per year, calculated monthly as the sum of each consecutive 12 month period. Compliance for the consecutive 12 month period shall be demonstrated monthly by adding the total for the most recently completed calendar month to theMachine-extracted normative operating-hours statement; second review pending.p. 9
10 through 1736 hours/yearhe total for the most recently completed calendar month to the individual monthly totals for the preceding 11 months. (9 VAC 5-80-1180) 12. Operating Hours – Each individual emergency diesel engine gen-set (Ref. Nos. 10 through 17) shall not operate more than 36 hours per year for scheduled maintenance and readiness testing (Scheduled MCRT). Each individual emergency diesel engine gen-set (Ref. Nos. 10 through 12) shall not operate more than 400 hours per year for all purposes (as provided inMachine-extracted normative operating-hours statement; second review pending.p. 9
10 through 17400 hours/yearesel engine gen-set (Ref. Nos. 10 through 17) shall not operate more than 36 hours per year for scheduled maintenance and readiness testing (Scheduled MCRT). Each individual emergency diesel engine gen-set (Ref. Nos. 10 through 12) shall not operate more than 400 hours per year for all purposes (as provided in Condition 9) combined. Each individual emergency diesel engine gen-set (Ref. Nos. 13 through 17) shall not operate more than 300 hours per year for all purposes (as provided in ConditionMachine-extracted normative operating-hours statement; second review pending.p. 9
10 through 12300 hours/yearrgency diesel engine gen-set (Ref. Nos. 10 through 12) shall not operate more than 400 hours per year for all purposes (as provided in Condition 9) combined. Each individual emergency diesel engine gen-set (Ref. Nos. 13 through 17) shall not operate more than 300 hours per year for all purposes (as provided in Condition 9) combined. The annual limits for hours of operation shall be calculated monthly as the sum of each consecutive 12-month period. Compliance for the consecutive 12-month periodMachine-extracted normative operating-hours statement; second review pending.p. 9

Permitted emission limits

24 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.

Inspect 24 transcribed limit rows
ReferencePollutantLimitBasis / scopeSource
Cummins 2500DQKAN (Ref. Nos. 10 through 12)NOx as NO236.56 lb/hrhourlyper unitp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3516E (Ref. Nos. 13 through 17)NOx as NO258.11 lb/hrhourlyper unitp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins 2500DQKAN (Ref. Nos. 10 through 12)NOx as NO25.03 lb/hrhourlyper unitp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3516E (Ref. Nos. 13 through 17)NOx as NO211.51 lb/hrhourlyper unitp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins 2500DQKAN (Ref. Nos. 10 through 12)VOC0.63 lb/hrhourlyper unitp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3516E (Ref. Nos. 13 through 17)VOC0.56 lb/hrhourlyper unitp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins 2500DQKAN (Ref. Nos. 10 through 12)PM101.78 lb/hrhourlyper unitp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3516E (Ref. Nos. 13 through 17)PM100.95 lb/hrhourlyper unitp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins 2500DQKAN (Ref. Nos. 10 through 12)PM2.51.78 lb/hrhourlyper unitp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3516E (Ref. Nos. 13 through 17)PM2.50.95 lb/hrhourlyper unitp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins 2500DQKAN (Ref. Nos. 10 through 12) All OperationsNOx as NO27.31 tpyannualper unitp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3516E (Ref. Nos. 13 through 17) All OperationsNOx as NO28.72 tpyannualper unitp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Cummins 2500DQKAN (Ref. Nos. 10 through 12) All OperationsNOx as NO21.01 tpyannualper unitp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3516E (Ref. Nos. 13 through 17) All OperationsNOx as NO21.73 tpyannualper unitp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Emergency Diesel Engine Gen-sets Ref. Nos. 10 through 17) All Operations (All Units Combined)NOx as NO265.52 tpyannualcombinedp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Emergency Diesel Engine Gen-sets Ref. Nos. 10 through 17) All Operations (All Units Combined)NOx as NO211.65 tpyannualcombinedp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Emergency Diesel Engine Gen-sets Ref. Nos. 10 through 17) All Operations (All Units Combined)VOC0.80 tpyannualcombinedp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Emergency Diesel Engine Gen-sets Ref. Nos. 10 through 17) All Operations (All Units Combined)PM101.78 tpyannualcombinedp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Emergency Diesel Engine Gen-sets Ref. Nos. 10 through 17) All Operations (All Units Combined)PM2.51.78 tpyannualcombinedp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Emergency Diesel Engine Gen-sets (Ref. Nos. 1 through 17) All Operations (All Units Combined)NOx as NO295.62 tpyannualcombinedp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Emergency Diesel Engine Gen-sets (Ref. Nos. 1 through 17) All Operations (All Units Combined)NOx as NO224.05 tpyannualcombinedp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Emergency Diesel Engine Gen-sets (Ref. Nos. 1 through 17) All Operations (All Units Combined)VOC1.90 tpyannualcombinedp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Emergency Diesel Engine Gen-sets (Ref. Nos. 1 through 17) All Operations (All Units Combined)PM102.28 tpyannualcombinedp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Emergency Diesel Engine Gen-sets (Ref. Nos. 1 through 17) All Operations (All Units Combined)PM2.52.28 tpyannualcombinedp. 13Machine-extracted from an official permit limit table; header grouping requires second review.

DOCUMENT HISTORY

What this document says it changes

amended or superseding permit document

Explicitly supersedes the document dated 2020-08-20.

p. 1

QA NOTES

Ambiguity stays visible

  • Machine-extracted candidate. Verify every reused value against the cited official PDF page.
  • Verify table column grouping and any alternative models.
  • Confirm whether the limit is per unit, combined, or limited to testing/maintenance.
  • Confirm multi-row and merged-column header association.
← Return to evidence index