(Ref. Nos. EG-01 through EG- 42) Kohler KD3000 | NOx as NO2— | 56.97 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
CAT C175-16 | NOx as NO2— | 58.51 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
(Ref. No. EG- 43) Kohler KD1600 | NOx as NO2— | 20.02 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
(Ref. No. EG- 44) Kohler KD1250 | NOx as NO2— | 15.87 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
(Ref. Nos. EG-01 through EG- 42) Kohler KD3000 | NOx as NO2— | 13.72 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
CAT C175-16 | NOx as NO2— | 6.05 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
(Ref. No. EG- 43) Kohler KD1600 | NOx as NO2— | 5.23 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
(Ref. No. EG- 44) Kohler KD1250 | NOx as NO2— | 5.98 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
(Ref. Nos. EG-01 through EG- 42) Kohler KD3000 | VOC— | 2.85 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
CAT C175-16 | VOC— | 2.87 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
(Ref. No. EG- 43) Kohler KD1600 | VOC— | 0.14 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
(Ref. No. EG- 44) Kohler KD1250 | VOC— | 0.09 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
(Ref. Nos. EG-01 through EG- 42) Kohler KD3000 | PM10— | 1.00 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
CAT C175-16 | PM10— | 1.50 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
(Ref. No. EG- 43) Kohler KD1600 | PM10— | 0.56 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
(Ref. No. EG- 44) Kohler KD1250 | PM10— | 0.45 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
(Ref. Nos. EG-01 through EG- 42) Kohler KD3000 | PM2.5— | 1.00 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
CAT C175-16 | PM2.5— | 1.50 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
(Ref. No. EG- 43) Kohler KD1600 | PM2.5— | 0.56 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
(Ref. No. EG- 44) Kohler KD1250 | PM2.5— | 0.45 lb/hrhourly | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
(Ref. Nos. EG-01 through EG-44) | NOx as NO2— | 99.17 tpyannual | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
(Ref. Nos. EG-01 through EG-44) | NOx as NO2— | 23.25 tpyannual | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
(Ref. Nos. EG-01 through EG-44) | VOC— | 4.86 tpyannual | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
(Ref. Nos. EG-01 through EG-44) | PM10— | 2.54 tpyannual | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
(Ref. Nos. EG-01 through EG-44) | PM2.5— | 2.54 tpyannual | —— | p. 11 ↗Machine-extracted from an official permit limit table; header grouping requires second review. |
| visible emissions— | 5 percent opacityvisible | —— | p. 12 ↗Machine-extracted from a page line in an older official PDF; literal context: Page 10 14. Visible Emission Limit – Visible emissions from each emergency diesel engine gen-set (Ref. Nos. EG-01 through EG-44) exhaust shall not exceed 5% opacity except during one (1) six-minute period in any one-hour in which visible emissions shall not exceed 10% |
| visible emissions— | 10 percent opacityvisible | —— | p. 12 ↗Machine-extracted from a page line in an older official PDF; literal context: 14. Visible Emission Limit – Visible emissions from each emergency diesel engine gen-set (Ref. Nos. EG-01 through EG-44) exhaust shall not exceed 5% opacity except during one (1) six-minute period in any one-hour in which visible emissions shall not exceed 10% opacity as determined by EPA Method 9 (reference 40 CFR 60, Appendix A). This |
| visible emissions— | 20 percent opacityvisible | —— | p. 12 ↗Machine-extracted from a page line in an older official PDF; literal context: During startup and shutdown, visible emissions from each emergency diesel engine gen-set shall not exceed 10% opacity except during one (1) six-minute period in any one-hour in which visible emissions shall not exceed 20% opacity as determined by EPA Method 9 (reference 40 CFR 60, Appendix A). |