Page-cited permit extraction

U.S. Customs and Border Protection

Fairfax Co., Virginia

QA status Machine-extractedRelease dated July 29, 2026

EVIDENCE NOTE

What the public record says

A machine-extracted candidate of equipment groups and permit limits stated in Virginia DEQ permit 74060-2, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.

Primary sourceVirginia DEQ permit document

Virginia Department of Environmental Quality

Open original source ↗

Summary fields cite p. 1, p. 3.

What this record does not establish

The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.

How to read the status

Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.

MACHINE-EXTRACTED CANDIDATE

Equipment and limits,
kept separate from actual use.

These page-cited rows are machine-extracted and still require a second manual review. Verify every reused value against the linked official PDF. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.

Permitted equipment

1 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.

ReferenceEquipment / modelCount / ratingFuel / controlsStated operating fieldSource
emergency engine generator set3 units1000 kW eachdiesel fuel oilSee operating-scope tablep. 1Machine-extracted from explicit permit prose: Delsignore: Attached is a permit to construct and operate three (3) 1,000 kW emergency diesel engine generators in accordance with the provisions of the Commonwealth of Virginia State Air Pollution Control Board

Operating scope

Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.

ReferenceLimitBasisSource
EO-2,EO-3, and EO-4500 hours/yearh period,calculated as the sum of all emissions from operations underthe scenarios above, shall not exceed the limits stated in Condition 10. (9VAC5-60-1160) 7. Operating r^ours^Eachengine-generatorset(Ref. Nos. EO-2,EO-3, and EO-4)shall not operate more than 500 hours peryear,calculated monthly as the sum of each consecutive 12month period. Compliance forthe consecutive 12month period shall be demonstrated monthly by adding the total forthe most recently completed calendar month to the indivMachine-extracted normative operating-hours statement; second review pending.p. 7

Permitted emission limits

7 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.

Inspect 7 transcribed limit rows
ReferencePollutantLimitBasis / scopeSource
each engine-generator set (Ref. Nos. EG-2, EG-3, and EG-4)NOx as NO214.5 tpyannualp. 8Machine-extracted from a page line in an older official PDF; literal context: generator sets (Ref. Nos. EG-2, EG-3, and EG-4) shall not exceed the limits specified below: Nitrogen Oxides (as N0 ) 14.5 tpy 2
each engine-generator set (Ref. Nos. EG-2, EG-3, and EG-4)NOx as NO22.1 tpyannualp. 8Machine-extracted from a page line in an older official PDF; literal context: Nitrogen Oxides (as N0 ) 14.5 tpy 2 Carbon Monoxide 2.1 tpy These emissions are derived from the estimated overall emission contribution from
each engine-generator set (Ref. Nos. EG-2, EG-3, and EG-4)visible emissions5 percent opacityvisiblep. 8Machine-extracted from a page line in an older official PDF; literal context: (9 VAC 5-80-1180 and 9 VAC 5-50-260) 11. Visible Emission Limit - Visible emissions from each engine-generator set (Ref. Nos. EG- 2, EG-3, and EG-4) shall not exceed 5 percent opacity except during one 6-minute period in any one hour in which visible emissions shall not exceed 10 percent opacity as determined
each engine-generator set (Ref. Nos. EG-2, EG-3, and EG-4)visible emissions10 percent opacityvisiblep. 8Machine-extracted from a page line in an older official PDF; literal context: 11. Visible Emission Limit - Visible emissions from each engine-generator set (Ref. Nos. EG- 2, EG-3, and EG-4) shall not exceed 5 percent opacity except during one 6-minute period in any one hour in which visible emissions shall not exceed 10 percent opacity as determined by EPA Method 9 (reference 40 CFR 60, Appendix A). This condition applies at all times
each engine-generator set (Ref. Nos. EG-2, EG-3, and EG-4)visible emissions20 percent opacityvisiblep. 8Machine-extracted from a page line in an older official PDF; literal context: During start-up and shut-down times, visible emissions from the engines shall not exceed 10 percent opacity except during one 6-minute period in any one hour in which visible emissions shall not exceed 20 percent opacity. (9 VAC 5-80-1180)
visible emissions10 percent opacityvisibleper exhaust/sourcep. 8Machine-extracted normative visible-emission limit; second review pending.
visible emissions20 percent opacityvisibleper exhaust/sourcep. 8Machine-extracted normative visible-emission limit; second review pending.

DOCUMENT HISTORY

What this document says it changes

permit to construct and operate

No superseded-document date is asserted beyond the cited source wording.

p. 1, p. 3

QA NOTES

Ambiguity stays visible

  • Machine-extracted candidate. Verify every reused value against the cited official PDF page.
  • Prose fallback; verify equipment grouping.
  • Confirm whether the limit is per unit, combined, or limited to testing/maintenance.
  • Older-PDF text fallback; verify row and unit alignment.
  • Confirm normal-operation versus startup/shutdown exception.
← Return to evidence index