QA status Machine-extractedRelease dated July 29, 2026
EVIDENCE NOTE
What the public record says
A machine-extracted candidate of equipment groups and permit limits stated in Virginia DEQ permit 73643-1, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.
The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.
How to read the status
Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.
MACHINE-EXTRACTED CANDIDATE
Equipment and limits, kept separate from actual use.
These page-cited rows are machine-extracted and still require a second manual review. Verify every reused value against the linked official PDF. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.
Permitted equipment
1 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.
Reference
Equipment / model
Count / rating
Fuel / controls
Stated operating field
Source
engine generator set—
20 unitsNo reliable per-unit rating transcribed
diesel fuel oil—
See operating-scope table—
p. 1 ↗Machine-extracted from explicit permit prose: Corbin: Attached is a permit to construct and operate a critical power data center facility with twenty-two diesel fired engine driven generator sets in accordance with the provisions ofthe Commonwealth of Virginia State Air Pollution Control B
Operating scope
Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.
Reference
Limit
Basis
Source
Permitted emission limits
5 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.
Inspect 5 transcribed limit rows
Reference
Pollutant
Limit
Basis / scope
Source
each diesel engine- generator set
NOx as NO2—
71.0 tpyannual
——
p. 10 ↗Machine-extracted from a page line in an older official PDF; literal context: 12. Facility wide Emission Limits - Total annual emissions from the facility shall not exceed the limits specified below: Nitrogen Oxides (as N0 ) 71.0 tons/yr 2
each diesel engine- generator set
NOx as NO2—
33.0 tpyannual
——
p. 10 ↗Machine-extracted from a page line in an older official PDF; literal context: Nitrogen Oxides (as N0 ) 71.0 tons/yr 2 Carbon Monoxide (CO) 33.0 tons/yr Sulfur Dioxide (S0 ) 9.0 tons/yr
each diesel engine- generator set
SO2—
9.0 tpyannual
——
p. 10 ↗Machine-extracted from a page line in an older official PDF; literal context: 2 Carbon Monoxide (CO) 33.0 tons/yr Sulfur Dioxide (S0 ) 9.0 tons/yr 2
each diesel engine- generator set
PM10—
4.0 tpyannual
——
p. 10 ↗Machine-extracted from a page line in an older official PDF; literal context: Sulfur Dioxide (S0 ) 9.0 tons/yr 2 Particulate Matter (PM10) 4.0 tons/yr Volatile Organic Compounds (VOC) 5.0 tons/yr
each diesel engine- generator set
VOC—
5.0 tpyannual
——
p. 10 ↗Machine-extracted from a page line in an older official PDF; literal context: 2 Particulate Matter (PM10) 4.0 tons/yr Volatile Organic Compounds (VOC) 5.0 tons/yr The total annual emissions from the diesel engine-generator sets shall be calculated
DOCUMENT HISTORY
What this document says it changes
permit to construct and operate
No superseded-document date is asserted beyond the cited source wording.