Page-verified permit transcription

Amazon Data Services Inc IAD-110/111/112/113

Prince William County, Virginia

QA status VerifiedRelease dated July 29, 2026

EVIDENCE NOTE

What the public record says

A manually verified transcription of equipment groups and permit limits stated in Virginia DEQ permit 74342-1, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.

Primary sourceVirginia DEQ permit document

Virginia Department of Environmental Quality

Open original source ↗

Summary fields cite p. 1, p. 3.

What this record does not establish

The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.

How to read the status

Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.

VERIFIED PERMIT TERMS

Equipment and limits,
kept separate from actual use.

This is a conservative transcription of reviewed permit sections, not an exhaustive legal digest. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.

Permitted equipment

7 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.

ReferenceEquipment / modelCount / ratingFuel / controlsStated operating fieldSource
1-52non-emergency engine-generator setCaterpillar · 3516E52 units2750 kW eachdieselSCR+cDPFSee operating-scope tablep. 5
53emergency engine-generator setCaterpillar · C181 units750 kW eachdieselSee operating-scope tablep. 5
54emergency engine-generator setCaterpillar · C181 units600 kW eachdieselSee operating-scope tablep. 5
55-98non-emergency engine-generator setMTU · 20V4000G74S / DS280044 units2800 kW eachdieselSCR+cDPFSee operating-scope tablep. 5
99-100emergency engine-generator setMTU · 16V2000G86S / DS10002 units750 kW eachdieselSee operating-scope tablep. 5Permit states 1,000 kW model de-rated to 750 ekW.
101emergency engine-generator setCaterpillar · C131 units400 kW eachdieselSee operating-scope tablep. 5
T1-T2emergency engine-generator setCaterpillar · 3516C2 units2000 kW eachdieselSee operating-scope tablep. 5

Operating scope

Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.

ReferenceLimitBasisSource

Permitted emission limits

6 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.

Inspect 6 transcribed limit rows
ReferencePollutantLimitBasis / scopeSource
53NOx as NO214.34 lb/hrhourlyper unitp. 13
54NOx as NO29.58 lb/hrhourlyper unitp. 13
99-100NOx as NO213.29 lb/hrhourlyper unitp. 13
101NOx as NO26.69 lb/hrhourlyper unitp. 13
T1-T2NOx as NO238.85 lb/hrhourlyper unitp. 13
1-52; 55-98opacity5 percentvisible-emission limitper unitp. 15

DOCUMENT HISTORY

What this document says it changes

new minor NSR permit

No superseded-document date is asserted beyond the cited source wording.

p. 1, p. 3

QA NOTES

Ambiguity stays visible

  • Official PDF cover/permit heading checked in the manual second pass.
  • Value transcribed from official permit equipment/condition table; no totals calculated.
  • Permit states 1,000 kW model de-rated to 750 ekW. — Value transcribed from official permit equipment/condition table; no totals calculated.
  • Directly stated permitted limit; not an actual emissions value.
← Return to evidence index