Page-cited permit extraction

Amazon Data Services, Inc. IAD-73 IAD-74 IAD-602 IAD-193 IAD-194

Prince William Co., Virginia

QA status Machine-extractedRelease dated July 29, 2026

EVIDENCE NOTE

What the public record says

A machine-extracted candidate of equipment groups and permit limits stated in Virginia DEQ permit 74081-4, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.

Primary sourceVirginia DEQ permit document

Virginia Department of Environmental Quality

Open original source ↗

Summary fields cite p. 1, p. 3.

What this record does not establish

The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.

How to read the status

Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.

MACHINE-EXTRACTED CANDIDATE

Equipment and limits,
kept separate from actual use.

These page-cited rows are machine-extracted and still require a second manual review. Verify every reused value against the linked official PDF. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.

Permitted equipment

6 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.

ReferenceEquipment / modelCount / ratingFuel / controlsStated operating fieldSource
3, 4, 17 through 20, 34through 36emergency engine generator setCaterpillar · 3516C9 units2500 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
37 through 76emergency engine generator setCaterpillar · 3516E40 units2750 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
78 through 80emergency engine generator setCaterpillar · C183 units750 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
77emergency engine generator setCaterpillar · C181 units750 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
1, 2, 5 through 16, and 21 through 33emergency engine generator setCaterpillar · 3516C- HD27 units2500 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
T1 through T6emergency engine generator setCaterpillar · 3516 C6 units2000 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.

Operating scope

Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.

ReferenceLimitBasisSource
3, 4, 17 through 20, and 34 through 8035 hours/year(which involves fuel combustion) shall be minimized to the maximum extent practical. (9VAC5-80-1180) [7/8/2024] 7. Operating Hours – Each individual emergency diesel engine gen-set (Ref. Nos. 3, 4, 17 through 20, and 34 through 80) shall not operate more than 35 hours per year for scheduled maintenance checks and readiness testing (Scheduled MCRT, as provided in Condition 3.c). Each individual emergency diesel engine gen-set (Ref. Nos. 1 through 80 and T1 through T6) shall not operate more thMachine-extracted normative operating-hours statement; second review pending.p. 8
1 through 80 and T1 through T6500 hours/yeart operate more than 35 hours per year for scheduled maintenance checks and readiness testing (Scheduled MCRT, as provided in Condition 3.c). Each individual emergency diesel engine gen-set (Ref. Nos. 1 through 80 and T1 through T6) shall not operate more than 500 hours per year for all purposes (as provided in Condition 3) combined. The annual limits for hours of operation shall be calculated monthly as the sum of each consecutive 12-month period. Compliance for the consecutive 12-month periodMachine-extracted normative operating-hours statement; second review pending.p. 8

Permitted emission limits

30 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.

Inspect 30 transcribed limit rows
ReferencePollutantLimitBasis / scopeSource
Ref. Nos. Ref. Nos. 1, 2, 5 through 16, 21 through 33NOx as NO248.07 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 3, 4, 17 through 20, and 34 through 36NOx as NO248.06 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 37 through 76NOx as NO253.48 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos.77 through 80NOx as NO214.34 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. T1 through T6NOx as NO238.85 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. Ref. Nos. 1, 2, 5 through 16, 21 through 33NOx as NO26.01 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 3, 4, 17 through 20, and 34 through 36NOx as NO26.09 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 37 through 76NOx as NO210.34 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos.77 through 80NOx as NO24.73 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. T1 through T6NOx as NO23.96 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. Ref. Nos. 1, 2, 5 through 16, 21 through 33VOC1.20 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 3, 4, 17 through 20, and 34 through 36VOC1.21 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 37 through 76VOC0.89 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos.77 through 80VOC1.91 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. T1 through T6VOC1.13 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. Ref. Nos. 1, 2, 5 through 16, 21 through 33PM100.41 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 3, 4, 17 through 20, and 34 through 36PM100.40 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 37 through 76PM100.62 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos.77 through 80PM100.32 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. T1 through T6PM100.57 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. Ref. Nos. 1, 2, 5 through 16, 21 through 33PM2.50.41 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 3, 4, 17 through 20, and 34 through 36PM2.50.40 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 37 through 76PM2.50.62 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos.77 through 80PM2.50.32 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. T1 through T6PM2.50.57 lb/hrhourlyp. 10Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 1 through 80 and T1 through T6NOx as NO296.03 tpyannualp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 1 through 80 and T1 through T6NOx as NO269.13 tpyannualp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 1 through 80 and T1 through T6VOC20.74 tpyannualp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 1 through 80 and T1 through T6PM106.03 tpyannualp. 11Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 1 through 80 and T1 through T6PM2.56.03 tpyannualp. 11Machine-extracted from an official permit limit table; header grouping requires second review.

DOCUMENT HISTORY

What this document says it changes

amended or superseding permit document

Explicitly supersedes the document dated 2015-03-06.

p. 1, p. 3

QA NOTES

Ambiguity stays visible

  • Machine-extracted candidate. Verify every reused value against the cited official PDF page.
  • Verify table column grouping and any alternative models.
  • Confirm whether the limit is per unit, combined, or limited to testing/maintenance.
  • Confirm multi-row and merged-column header association.
← Return to evidence index