Page-cited permit extraction

Bank of America-Sandston

Henrico Co., Virginia

QA status Machine-extractedRelease dated July 29, 2026

EVIDENCE NOTE

What the public record says

A machine-extracted candidate of equipment groups and permit limits stated in Virginia DEQ permit 52403-9, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.

Primary sourceVirginia DEQ permit document

Virginia Department of Environmental Quality

Open original source ↗

Summary fields cite p. 1, p. 3.

What this record does not establish

The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.

How to read the status

Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.

MACHINE-EXTRACTED CANDIDATE

Equipment and limits,
kept separate from actual use.

These page-cited rows are machine-extracted and still require a second manual review. Verify every reused value against the linked official PDF. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.

Permitted equipment

6 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.

ReferenceEquipment / modelCount / ratingFuel / controlsStated operating fieldSource
42-47emergency engine generator set6 units563 kW eachdiesel fuel oilSee operating-scope tablep. 4Machine-extracted from an official document equipment table; column grouping requires second review.
1-5engine generator setCummins · DQKAC1 units2446 kW eachdiesel fuel oilSee operating-scope tablep. 4Machine-extracted from an official document equipment table; column grouping requires second review.
14, 15 and 18- 21emergency engine generator setCaterpillar · diesel units1645 kW eachdiesel fuel oilSee operating-scope tablep. 4Machine-extracted from an official document equipment table; column grouping requires second review.
26-31 and 34- 39emergency engine generator set units563 kW eachdiesel fuel oilSee operating-scope tablep. 4Machine-extracted from an official document equipment table; column grouping requires second review.
6and 7boiler unitsNo reliable per-unit rating transcribedSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
12emergency engine generator setCummins · diesel1 units250 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.

Operating scope

Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.

ReferenceLimitBasisSource
1-51000 hours/yeare manufacturer. In addition, the permittee may only change those settings that are permitted by the manufacturer which do not increase air emissions. (9 VAC 5-80-1180) 5. Operating Hours – Each engine-generator set (Ref. Nos. 1-5), shall not operate more than 1000 hours per year, calculated monthly as the sum of each consecutive 12-month period. Compliance for the consecutive 12-month period shall be demonstrated monthly by adding the total for the most recently completed calendar month to theMachine-extracted normative operating-hours statement; second review pending.p. 6
14, 15 and 18-21500 hours/yearhe total for the most recently completed calendar month to the individual monthly totals for the preceding 11 months. (9 VAC 5-80-1180 and 9 VAC 5-50-260) 6. Operating Hours – Each engine-generator set (Ref. Nos. 14, 15 and 18-21), shall not operate more than 500 hours per year and all engine-generator sets referenced in this condition shall not operate more than 2,130 hours per year combined, calculated monthly as the sum of each consecutive 12-month period. Compliance for the consecutive 12-Machine-extracted normative operating-hours statement; second review pending.p. 6
14, 15 and 18-21130 hours/year1 months. (9 VAC 5-80-1180 and 9 VAC 5-50-260) 6. Operating Hours – Each engine-generator set (Ref. Nos. 14, 15 and 18-21), shall not operate more than 500 hours per year and all engine-generator sets referenced in this condition shall not operate more than 2,130 hours per year combined, calculated monthly as the sum of each consecutive 12-month period. Compliance for the consecutive 12-month period shall be demonstrated monthly by adding the total for the most recently completed calendar montMachine-extracted normative operating-hours statement; second review pending.p. 6
26-31, 34-39, 42-47500 hours/yearthly by adding the total for the most recently completed calendar month to the individual monthly totals for the preceding 11 months. (9 VAC 5-80-1180) 7. Operating Hours – Each engine-generator set (Ref. Nos. 26-31, 34-39, 42-47), shall not operate more than 500 hours per year and all engine-generator sets referenced in this condition shall not operate more than 6,390 hours per year combined, calculated monthly as the sum of each consecutive 12-month period. Compliance for the consecutive 12-Machine-extracted normative operating-hours statement; second review pending.p. 6
26-31, 34-39, 42-47390 hours/yearthe preceding 11 months. (9 VAC 5-80-1180) 7. Operating Hours – Each engine-generator set (Ref. Nos. 26-31, 34-39, 42-47), shall not operate more than 500 hours per year and all engine-generator sets referenced in this condition shall not operate more than 6,390 hours per year combined, calculated monthly as the sum of each consecutive 12-month period. Compliance for the consecutive 12-month period shall be demonstrated monthly by adding the total for the most recently completed calendar montMachine-extracted normative operating-hours statement; second review pending.p. 6

Permitted emission limits

20 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.

Inspect 20 transcribed limit rows
ReferencePollutantLimitBasis / scopeSource
engine-generator sets (Ref. Nos. 1-5)PM0.7 lb/hrhourlyper unitp. 7Machine-extracted from a page line in an older official PDF; literal context: Nos. 1-5) shall not exceed the limits specified below: Each Unit Combined Units PM 0.7 lb/hr 1.7 tons/yr PM10 0.7 lb/hr 1.7 tons/yr
engine-generator sets (Ref. Nos. 1-5)PM1.7 lb/hrhourlyper unitp. 7Machine-extracted from a page line in an older official PDF; literal context: Nos. 1-5) shall not exceed the limits specified below: Each Unit Combined Units PM 0.7 lb/hr 1.7 tons/yr PM10 0.7 lb/hr 1.7 tons/yr
engine-generator sets (Ref. Nos. 1-5)NOx as NO25.4 lb/hrhourlyp. 7Machine-extracted from a page line in an older official PDF; literal context: PM 0.7 lb/hr 1.7 tons/yr PM10 0.7 lb/hr 1.7 tons/yr Nitrogen Oxides (as NO ) 5.4 lb/hr 13.5 tons/yr 2
engine-generator sets (Ref. Nos. 1-5)NOx as NO213.5 lb/hrhourlyp. 7Machine-extracted from a page line in an older official PDF; literal context: PM 0.7 lb/hr 1.7 tons/yr PM10 0.7 lb/hr 1.7 tons/yr Nitrogen Oxides (as NO ) 5.4 lb/hr 13.5 tons/yr 2
engine-generator sets (Ref. Nos. 1-5)NOx as NO218.9 lb/hrhourlyp. 7Machine-extracted from a page line in an older official PDF; literal context: Nitrogen Oxides (as NO ) 5.4 lb/hr 13.5 tons/yr 2 Carbon Monoxide 18.9 lb/hr 47.2 tons/yr Volatile Organic Compounds 2.2 lb/hr 5.4 tons/yr
engine-generator sets (Ref. Nos. 1-5)NOx as NO247.2 lb/hrhourlyp. 7Machine-extracted from a page line in an older official PDF; literal context: Nitrogen Oxides (as NO ) 5.4 lb/hr 13.5 tons/yr 2 Carbon Monoxide 18.9 lb/hr 47.2 tons/yr Volatile Organic Compounds 2.2 lb/hr 5.4 tons/yr
engine-generator sets (Ref. Nos. 1-5)VOC2.2 lb/hrhourlyp. 7Machine-extracted from a page line in an older official PDF; literal context: 2 Carbon Monoxide 18.9 lb/hr 47.2 tons/yr Volatile Organic Compounds 2.2 lb/hr 5.4 tons/yr These emissions are derived from the estimated overall emission contribution from operating
engine-generator sets (Ref. Nos. 1-5)VOC5.4 lb/hrhourlyp. 7Machine-extracted from a page line in an older official PDF; literal context: 2 Carbon Monoxide 18.9 lb/hr 47.2 tons/yr Volatile Organic Compounds 2.2 lb/hr 5.4 tons/yr These emissions are derived from the estimated overall emission contribution from operating
engine-generator sets (Ref. Nos. 14, 15, 18- 21)NOx as NO233.7 tpyannualper unitp. 7Machine-extracted from a page line in an older official PDF; literal context: Nos. 14, 15, 18- 21) shall not exceed the limits specified below: Each Unit Combined Units Nitrogen Oxides (as NO ) 6.0 g/hp-hr 33.7 tons/yr 2
engine-generator sets (Ref. Nos. 14, 15, 18- 21)NOx as NO24.3 lb/hrhourlyp. 7Machine-extracted from a page line in an older official PDF; literal context: Nitrogen Oxides (as NO ) 6.0 g/hp-hr 33.7 tons/yr 2 Carbon Monoxide 4.3 lb/hr 4.6 tons/yr Volatile Organic Compounds 1.4 lb/hr 1.5 tons/yr
engine-generator sets (Ref. Nos. 14, 15, 18- 21)NOx as NO24.6 lb/hrhourlyp. 7Machine-extracted from a page line in an older official PDF; literal context: Nitrogen Oxides (as NO ) 6.0 g/hp-hr 33.7 tons/yr 2 Carbon Monoxide 4.3 lb/hr 4.6 tons/yr Volatile Organic Compounds 1.4 lb/hr 1.5 tons/yr
engine-generator sets (Ref. Nos. 14, 15, 18- 21)VOC1.4 lb/hrhourlyp. 7Machine-extracted from a page line in an older official PDF; literal context: 2 Carbon Monoxide 4.3 lb/hr 4.6 tons/yr Volatile Organic Compounds 1.4 lb/hr 1.5 tons/yr These emissions are derived from the estimated overall emission contribution from operating
engine-generator sets (Ref. Nos. 14, 15, 18- 21)VOC1.5 lb/hrhourlyp. 7Machine-extracted from a page line in an older official PDF; literal context: 2 Carbon Monoxide 4.3 lb/hr 4.6 tons/yr Volatile Organic Compounds 1.4 lb/hr 1.5 tons/yr These emissions are derived from the estimated overall emission contribution from operating
engine-generator sets (Ref. Nos. 26-31, 34-39, and 42-47)NOx as NO226.3 tpyannualper unitp. 8Machine-extracted from a page line in an older official PDF; literal context: Nos. 26-31, 34-39, and 42-47) shall not exceed the limits specified below: Each Unit Combined Units Nitrogen Oxides (as NO ) 4.9 g/hp-hr 26.3 tons/yr 2
engine-generator sets (Ref. Nos. 26-31, 34-39, and 42-47)NOx as NO20.8 lb/hrhourlyp. 8Machine-extracted from a page line in an older official PDF; literal context: Nitrogen Oxides (as NO ) 4.9 g/hp-hr 26.3 tons/yr 2 Carbon Monoxide 0.8 lb/hr 2.6 tons/yr Volatile Organic Compounds 0.5 lb/hr 1.6 tons/yr
engine-generator sets (Ref. Nos. 26-31, 34-39, and 42-47)NOx as NO22.6 lb/hrhourlyp. 8Machine-extracted from a page line in an older official PDF; literal context: Nitrogen Oxides (as NO ) 4.9 g/hp-hr 26.3 tons/yr 2 Carbon Monoxide 0.8 lb/hr 2.6 tons/yr Volatile Organic Compounds 0.5 lb/hr 1.6 tons/yr
engine-generator sets (Ref. Nos. 26-31, 34-39, and 42-47)VOC0.5 lb/hrhourlyp. 8Machine-extracted from a page line in an older official PDF; literal context: 2 Carbon Monoxide 0.8 lb/hr 2.6 tons/yr Volatile Organic Compounds 0.5 lb/hr 1.6 tons/yr These emissions are derived from the estimated overall emission contribution from operating
engine-generator sets (Ref. Nos. 26-31, 34-39, and 42-47)VOC1.6 lb/hrhourlyp. 8Machine-extracted from a page line in an older official PDF; literal context: 2 Carbon Monoxide 0.8 lb/hr 2.6 tons/yr Volatile Organic Compounds 0.5 lb/hr 1.6 tons/yr These emissions are derived from the estimated overall emission contribution from operating
engine-generator sets (Ref. Nos. 26-31, 34-39, and 42-47)visible emissions10 percent opacityvisiblep. 8Machine-extracted from a page line in an older official PDF; literal context: (9 VAC 5-80-1180 and 9 VAC 5-50-260) 13. Visible Emission Limit - Visible emissions from each engine-generator set exhaust (Ref. Nos. 1-5, 14, 15, 18-21, 26-31, 34-39, and 42-47) each shall not exceed 10% opacity except during one six-minute period in any one hour in which visible emissions shall not exceed
engine-generator sets (Ref. Nos. 26-31, 34-39, and 42-47)visible emissions20 percent opacityvisiblep. 8Machine-extracted from a page line in an older official PDF; literal context: Nos. 1-5, 14, 15, 18-21, 26-31, 34-39, and 42-47) each shall not exceed 10% opacity except during one six-minute period in any one hour in which visible emissions shall not exceed 20% opacity as determined by the EPA Method 9 (reference 40 CFR 60, Appendix A). This condition applies at all times except during startup, shutdown, and malfunction.

DOCUMENT HISTORY

What this document says it changes

amended or superseding permit document

Explicitly supersedes the document dated 2020-01-13.

p. 1, p. 3

QA NOTES

Ambiguity stays visible

  • Machine-extracted candidate. Verify every reused value against the cited official PDF page.
  • Verify table column grouping and any alternative models.
  • Confirm whether the limit is per unit, combined, or limited to testing/maintenance.
  • Older-PDF text fallback; verify row and unit alignment.