Page-cited permit extraction

Corporate Office Properties Trust (COPT - DC6)

Prince William Co., Virginia

QA status Machine-extractedRelease dated July 29, 2026

EVIDENCE NOTE

What the public record says

A machine-extracted candidate of equipment groups and permit limits stated in Virginia DEQ permit 73683-12, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.

Primary sourceVirginia DEQ permit document

Virginia Department of Environmental Quality

Open original source ↗

Summary fields cite p. 1, p. 3.

What this record does not establish

The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.

How to read the status

Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.

MACHINE-EXTRACTED CANDIDATE

Equipment and limits,
kept separate from actual use.

These page-cited rows are machine-extracted and still require a second manual review. Verify every reused value against the linked official PDF. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.

Permitted equipment

8 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.

ReferenceEquipment / modelCount / ratingFuel / controlsStated operating fieldSource
G4 thru G6emergency engine generator setMTU · 16V40003 units2000 kW eachdiesel fuel oilselective catalytic reduction (SCR)See operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
G1engine generator setMTU · 20V4000G431 units2500 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
G2, G3, and RPU11 thru RPU15engine generator setMTU · 16V40007 units2050 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
GE1, GE2, and GER1engine generator setMTU · 20V4000G433 units2500 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
GE3, GE4, GE5engine generator setMTU · 20V4000G433 units2500 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
GM1 and GMRengine generator setMTU · 16V40002 units2050 kW eachdiesel fuel oilSee operating-scope tablep. 6Machine-extracted from an official document equipment table; column grouping requires second review.
GM2engine generator setMTU · 16V40001 units2050 kW eachdiesel fuel oilSee operating-scope tablep. 6Machine-extracted from an official document equipment table; column grouping requires second review.
GEN1emergency engine generator setCaterpillar · 3516C1 units2000 kW eachdiesel fuel oilSee operating-scope tablep. 6Machine-extracted from an official document equipment table; column grouping requires second review.

Operating scope

Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.

ReferenceLimitBasisSource
RPU11 thru RPU15, G1 thru G3, GE1 thru GE5, GM1, GM2, GMR, GER1, and GEN1100 hours/year180) 12. Operating Hours – In addition to the fuel throughput limitation specified in Conditions 17 and 18, each individual diesel engine gen-set (Ref. Nos. RPU11 thru RPU15, G1 thru G3, GE1 thru GE5, GM1, GM2, GMR, GER1, and GEN1) shall not operate more than 100 hours per year for unscheduled maintenance, testing, operational training, and scheduled maintenance checks and readiness testing (as provided in Conditions 7.c and 7.d) and no more than 500 hours per year for all purposes (as provideMachine-extracted normative operating-hours statement; second review pending.p. 11
500 hours/yearthru GE5, GM1, GM2, GMR, GER1, and GEN1) shall not operate more than 100 hours per year for unscheduled maintenance, testing, operational training, and scheduled maintenance checks and readiness testing (as provided in Conditions 7.c and 7.d) and no more than 500 hours per year for all purposes (as provided in Condition 7) combined. The annual limits for hours of operation shall be calculated monthly as the sum of each consecutive 12-month period. Compliance for the consecutive 12-month periodMachine-extracted normative operating-hours statement; second review pending.p. 11
G4 thru G6500 hours/yearg the total for the most recently completed calendar month to the individual monthly totals for the preceding 11 months. (9 VAC 5-80-1180) 13. Operating Hours – Each individual emergency diesel engine gen-set (Ref. Nos. G4 thru G6) shall not operate more than 500 hours per year for all purposes (as provided in Condition 7) combined. Each individual emergency diesel engine gen-set (Ref. Nos. G4Machine-extracted normative operating-hours statement; second review pending.p. 11
23 hours/yearCorporate Office Properties Trust (COPT) Registration Number: 73683 August 24, 2021 Page 10 thru G6) shall not operate more than 23 hours per year for scheduled maintenance checks and readiness testing (Scheduled MCRT, as provided in Condition 7.d). The annual limits for hours of operation shall be calculated monthly as the sum of each consecutive 12-month period.Machine-extracted normative operating-hours statement; second review pending.p. 12

Permitted emission limits

45 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.

Inspect 45 transcribed limit rows
ReferencePollutantLimitBasis / scopeSource
Ref. Nos. GM1, GM2, GMR, RPU11-RPU15, G2 and G3NOx as NO241.4 lb/hrhourlyper unitp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. G1, GE1 – GE5, and GER1NOx as NO244.7 lb/hrhourlyper unitp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. GM1, GM2, GMR, RPU11-RPU15, G2 and G3NOx as NO26.1 lb/hrhourlyper unitp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. G1, GE1 – GE5, and GER1NOx as NO26.1 lb/hrhourlyper unitp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. GM1, GM2, GMR, RPU11-RPU15, G2 and G3VOC0.9 lb/hrhourlyper unitp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. G1, GE1 – GE5, and GER1VOC1.36 lb/hrhourlyper unitp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. GM1, GM2, GMR, RPU11-RPU15, G2 and G3PM100.75 lb/hrhourlyper unitp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. G1, GE1 – GE5, and GER1PM100.8 lb/hrhourlyper unitp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. GM1, GM2, GMR, RPU11-RPU15, G2 and G3PM2.50.75 lb/hrhourlyper unitp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. G1, GE1 – GE5, and GER1PM2.50.8 lb/hrhourlyper unitp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3516C (Ref. No. GEN1)NOx as NO238.85 lb/hrhourlyp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3516C (Ref. No. GEN1)NOx as NO23.95 lb/hrhourlyp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3516C (Ref. No. GEN1)VOC1.13 lb/hrhourlyp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3516C (Ref. No. GEN1)PM100.62 lb/hrhourlyp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
Caterpillar 3516C (Ref. No. GEN1)PM2.50.62 lb/hrhourlyp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. G4 thru G6 UncontrolledNOx as NO2uncontrolled48.6 lb/hrhourlyper unitp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
Controlled with SCRNOx as NO2controlled38.9 lb/hrhourlyp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. G4 thru G6 UncontrolledNOx as NO2uncontrolled8.09 lb/hrhourlyper unitp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
Controlled with SCRNOx as NO2controlled8.90 lb/hrhourlyp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. G4 thru G6 UncontrolledVOCuncontrolled4.10 lb/hrhourlyper unitp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. G4 thru G6 UncontrolledPM10uncontrolled0.96 lb/hrhourlyper unitp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. G4 thru G6 UncontrolledPM2.5uncontrolled0.96 lb/hrhourlyper unitp. 14Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. RPU11 thru RPU15, G1 thru G3, GE1 thru GE5, GM1, GM2, GMR, and GER1 (Combined)NOx as NO249.4 tpyannualcombinedp. 15Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. GEN1NOx as NO28.45 tpyannualp. 15Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. GEN1NOx as NO257.85 tpyannualp. 15Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. G4 thru G6 (Combined)NOx as NO236.40 tpyannualcombinedp. 15Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. RPU11 thru RPU15, G1 thru G3, GE1 thru GE5, GM1, GM2, GMR, and GER1 (Combined)NOx as NO25.62 tpyannualcombinedp. 15Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. GEN1NOx as NO24.49 tpyannualp. 15Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. GEN1NOx as NO210.11 tpyannualp. 15Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. G4 thru G6 (Combined)NOx as NO26.68 tpyannualcombinedp. 15Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. RPU11 thru RPU15, G1 thru G3, GE1 thru GE5, GM1, GM2, GMR, and GER1 (Combined)VOC3.74 tpyannualcombinedp. 15Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. GEN1VOC1.11 tpyannualp. 15Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. GEN1VOC4.85 tpyannualp. 15Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. G4 thru G6 (Combined)VOC3.07 tpyannualcombinedp. 15Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. RPU11 thru RPU15, G1 thru G3, GE1 thru GE5, GM1, GM2, GMR, and GER1 (Combined)PM102.57 tpyannualcombinedp. 15Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. GEN1PM100.54 tpyannualp. 15Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. GEN1PM103.11 tpyannualp. 15Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. G4 thru G6 (Combined)PM100.72 tpyannualcombinedp. 15Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. RPU11 thru RPU15, G1 thru G3, GE1 thru GE5, GM1, GM2, GMR, and GER1 (Combined)PM2.52.57 tpyannualcombinedp. 15Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. GEN1PM2.50.54 tpyannualp. 15Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. GEN1PM2.53.11 tpyannualp. 15Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. G4 thru G6 (Combined)PM2.50.72 tpyannualcombinedp. 15Machine-extracted from an official permit limit table; header grouping requires second review.
visible emissions5 percent opacityvisiblep. 17Machine-extracted from a page line in an older official PDF; literal context: 24. Visible Emission Limit – Visible emissions from each diesel engine gen-set (Ref. Nos. RPU11 thru RPU15, G1 thru G6, GE1 thru GE5, GM1, GM2, GMR, GER1, and GEN1) shall not exceed 5% opacity except during one six-minute period in any one hour in which visible emissions shall not exceed 10% opacity as determined by the EPA Method 9
visible emissions10 percent opacityvisiblep. 17Machine-extracted from a page line in an older official PDF; literal context: RPU11 thru RPU15, G1 thru G6, GE1 thru GE5, GM1, GM2, GMR, GER1, and GEN1) shall not exceed 5% opacity except during one six-minute period in any one hour in which visible emissions shall not exceed 10% opacity as determined by the EPA Method 9 (reference 40 CFR 60, Appendix A). This condition applies at all times except during
visible emissions20 percent opacityvisiblep. 17Machine-extracted from a page line in an older official PDF; literal context: Nos. RPU11 thru RPU15, G1 thru G6, GE1 thru GE5, GM1, GM2, GMR, GER1, and GEN1) shall not exceed 10% opacity except during one six-minute period in any one hour in which visible emissions shall not exceed 20% opacity. (9 VAC 5-80-1180 and 9 VAC 5-50-260)

DOCUMENT HISTORY

What this document says it changes

amended or superseding permit document

Explicitly supersedes the document dated 2018-08-01.

p. 1, p. 3

QA NOTES

Ambiguity stays visible

  • Machine-extracted candidate. Verify every reused value against the cited official PDF page.
  • Verify table column grouping and any alternative models.
  • Confirm whether the limit is per unit, combined, or limited to testing/maintenance.
  • Confirm multi-row and merged-column header association.
  • Older-PDF text fallback; verify row and unit alignment.