QA status Machine-extractedRelease dated July 29, 2026
EVIDENCE NOTE
What the public record says
A machine-extracted candidate of equipment groups and permit limits stated in Virginia DEQ permit 74127-3, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.
The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.
How to read the status
Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.
MACHINE-EXTRACTED CANDIDATE
Equipment and limits, kept separate from actual use.
These page-cited rows are machine-extracted and still require a second manual review. Verify every reused value against the linked official PDF. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.
Permitted equipment
3 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.
Reference
Equipment / model
Count / rating
Fuel / controls
Stated operating field
Source
11
emergency engine generator setKohler · 2000REOZMD
1 units2000 kW each
diesel fuel oil—
See operating-scope table—
p. 5 ↗Machine-extracted from an official document equipment table; column grouping requires second review.
1 through 4
emergency engine generator setKohler · 2000REOZMD
4 units2000 kW each
diesel fuel oil—
See operating-scope table—
p. 5 ↗Machine-extracted from an official document equipment table; column grouping requires second review.
5 through 8, and 10
emergency engine generator setKohler · 2000REOZMD
5 units2000 kW each
diesel fuel oil—
See operating-scope table—
p. 5 ↗Machine-extracted from an official document equipment table; column grouping requires second review.
Operating scope
Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.
Reference
Limit
Basis
Source
1 through 4
100 hours/year
ll emissions from operations under the scenarios above, shall not exceed the limits stated in Condition 10. (9VAC5-80-1180) [1/20/2026] 7. Operating Hours – a. Each individual emergency diesel engine gen-set (Ref. Nos. 1 through 4) shall not operate more than 100 hours per year for scheduled maintenance checks and readiness testing (Scheduled MCRT), unscheduled maintenance, testing, and operational training (as provided in Conditions 6.c and 6.d) and no more than 500 hours per year for all purMachine-extracted normative operating-hours statement; second review pending.
(Ref. Nos. 1 through 4) shall not operate more than 100 hours per year for scheduled maintenance checks and readiness testing (Scheduled MCRT), unscheduled maintenance, testing, and operational training (as provided in Conditions 6.c and 6.d) and no more than 500 hours per year for all purposes (as provided in Condition 6) combined. b. Each individual emergency diesel engine gen-set (Ref. Nos. 5 through 8 and 10) shall not operate more than 30 hours per year for scheduled maintenance checks anMachine-extracted normative operating-hours statement; second review pending.
rational training (as provided in Conditions 6.c and 6.d) and no more than 500 hours per year for all purposes (as provided in Condition 6) combined. b. Each individual emergency diesel engine gen-set (Ref. Nos. 5 through 8 and 10) shall not operate more than 30 hours per year for scheduled maintenance checks and readiness testing (Scheduled MCRT, as provided in Condition 6.c). c. The emergency diesel engine gen-set (Ref. No. 11) shall not operate more than 13 hours per year for scheduled maiMachine-extracted normative operating-hours statement; second review pending.
Ref. Nos. 5 through 8 and 10) shall not operate more than 30 hours per year for scheduled maintenance checks and readiness testing (Scheduled MCRT, as provided in Condition 6.c). c. The emergency diesel engine gen-set (Ref. No. 11) shall not operate more than 13 hours per year for scheduled maintenance checks and readiness testing (Scheduled MCRT, as provided in Condition 6.c). d. Each individual emergency diesel engine gen-set (Ref. Nos. 5 through 8, 10, and 11) shall not operate more than 5Machine-extracted normative operating-hours statement; second review pending.
l not operate more than 13 hours per year for scheduled maintenance checks and readiness testing (Scheduled MCRT, as provided in Condition 6.c). d. Each individual emergency diesel engine gen-set (Ref. Nos. 5 through 8, 10, and 11) shall not operate more than 500 hours per year for all purposes (as provided in Condition 6) combined. The annual limits for hours of operation shall be calculated monthly as the sum of each consecutive 12-month period. Compliance for the consecutive 12-month periodMachine-extracted normative operating-hours statement; second review pending.