Page-cited permit extraction

Microsoft

Fauquier Co., Virginia

QA status Machine-extractedRelease dated July 29, 2026

EVIDENCE NOTE

What the public record says

A machine-extracted candidate of equipment groups and permit limits stated in Virginia DEQ permit 74201-4, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.

Primary sourceVirginia DEQ permit document

Virginia Department of Environmental Quality

Open original source ↗

Summary fields cite p. 1, p. 3.

What this record does not establish

The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.

How to read the status

Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.

MACHINE-EXTRACTED CANDIDATE

Equipment and limits,
kept separate from actual use.

These page-cited rows are machine-extracted and still require a second manual review. Verify every reused value against the linked official PDF. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.

Permitted equipment

5 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.

ReferenceEquipment / modelCount / ratingFuel / controlsStated operating fieldSource
CLOUD-1 through CLOUD-3emergency engine generator setMTU · 20V4000 DS30003 units3000 kW eachdiesel fuel oilselective catalytic reduction (SCR)See operating-scope tablep. 6Machine-extracted from an official document equipment table; column grouping requires second review.
CLOUD-4emergency engine generator setCummins · 500DFEK1 units500 kW eachdiesel fuel oilSee operating-scope tablep. 6Machine-extracted from an official document equipment table; column grouping requires second review.
CLOUD-5 and CLOUD-6emergency engine generator setCummins · C3000 D6e2 units3000 kW eachdiesel fuel oilselective catalytic reduction (SCR)See operating-scope tablep. 6Machine-extracted from an official document equipment table; column grouping requires second review.
CLOUD-7 through CLOUD-12emergency engine generator setCummins · C3000 D6e6 units3000 kW eachdiesel fuel oilselective catalytic reduction (SCR)See operating-scope tablep. 6Machine-extracted from an official document equipment table; column grouping requires second review.
CLOUD-13 and CLOUD-14emergency engine generator setCummins · C3000 D6e2 units3000 kW eachdiesel fuel oilselective catalytic reduction (SCR)See operating-scope tablep. 6Machine-extracted from an official document equipment table; column grouping requires second review.

Operating scope

Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.

ReferenceLimitBasisSource
CLOUD-1 and CLOUD-2240 hours/yearMicrosoft Corporation Registration Number: 74201 February 8, 2023 Page 8 7. Operating Hours – a. The two (2) emergency diesel engine gen-sets (Ref. Nos. CLOUD-1 and CLOUD-2) combined shall not operate more than 240 hours per year when emissions are uncontrolled, calculated monthly as the sum of each consecutive 12-month period (all uses); and b. The two (2) emergency diesel engine gen-sets (Ref. Nos. CLOUD-1 and CLOUD-2) combined shall not operaMachine-extracted normative operating-hours statement; second review pending.p. 10
CLOUD-1 and CLOUD-2760 hours/yearore than 240 hours per year when emissions are uncontrolled, calculated monthly as the sum of each consecutive 12-month period (all uses); and b. The two (2) emergency diesel engine gen-sets (Ref. Nos. CLOUD-1 and CLOUD-2) combined shall not operate more than 760 hours per year when emissions are controlled with SCR, calculated monthly as the sum of each consecutive 12-month period (all uses); and c. The emergency diesel engine gen-set (Ref. No. CLOUD-3) shall not operate more than 380 hours pMachine-extracted normative operating-hours statement; second review pending.p. 10
CLOUD-3380 hours/yearined shall not operate more than 760 hours per year when emissions are controlled with SCR, calculated monthly as the sum of each consecutive 12-month period (all uses); and c. The emergency diesel engine gen-set (Ref. No. CLOUD-3) shall not operate more than 380 hours per year when emissions are uncontrolled, calculated monthly as the sum of each consecutive 12-month period (all uses); and d. The emergency diesel engine gen-set (Ref. No. CLOUD-3) shall not operate more than 120 hours per yearMachine-extracted normative operating-hours statement; second review pending.p. 10
CLOUD-3120 hours/yearo. CLOUD-3) shall not operate more than 380 hours per year when emissions are uncontrolled, calculated monthly as the sum of each consecutive 12-month period (all uses); and d. The emergency diesel engine gen-set (Ref. No. CLOUD-3) shall not operate more than 120 hours per year when emissions are controlled with SCR, calculated monthly as the sum of each consecutive 12-month period (all uses); and e. The ten (10) emergency diesel engine gen-sets (Ref. Nos. CLOUD-5 through CLOUD- 14) combined sMachine-extracted normative operating-hours statement; second review pending.p. 10
CLOUD-5 through CLOUD- 14200 hours/yearrs per year when emissions are controlled with SCR, calculated monthly as the sum of each consecutive 12-month period (all uses); and e. The ten (10) emergency diesel engine gen-sets (Ref. Nos. CLOUD-5 through CLOUD- 14) combined shall not operate more than 1,200 hours per year when emissions are uncontrolled, calculated monthly as the sum of each consecutive 12-month period (all uses); and f. The ten (10) emergency diesel engine gen-sets (Ref. Nos. CLOUD-5 through CLOUD- 14) combined shall noMachine-extracted normative operating-hours statement; second review pending.p. 10
CLOUD-5 through CLOUD- 14800 hours/year200 hours per year when emissions are uncontrolled, calculated monthly as the sum of each consecutive 12-month period (all uses); and f. The ten (10) emergency diesel engine gen-sets (Ref. Nos. CLOUD-5 through CLOUD- 14) combined shall not operate more than 3,800 hours per year when emissions are controlled with SCR, calculated monthly as the sum of each consecutive 12-month period (all uses); and g. The emergency diesel engine gen-set (Ref. No. CLOUD-4) shall not operate more than 500 hours pMachine-extracted normative operating-hours statement; second review pending.p. 10
CLOUD-4500 hours/yeared shall not operate more than 3,800 hours per year when emissions are controlled with SCR, calculated monthly as the sum of each consecutive 12-month period (all uses); and g. The emergency diesel engine gen-set (Ref. No. CLOUD-4) shall not operate more than 500 hours per year, calculated monthly as the sum of each consecutive 12-month period (all uses). Compliance for each consecutive 12-month period shall be demonstrated monthly by adding the total for the most recently completed calendar mMachine-extracted normative operating-hours statement; second review pending.p. 10
CLOUD-1 through CLOUD-1427 hours/yearor the most recently completed calendar month to the individual monthly totals for the preceding 11 months. (9 VAC 5-80-1180) 8. Operating Hours – Each individual emergency diesel engine gen-set (Ref. Nos. CLOUD-1 through CLOUD-14) shall not operate more than 27 hours per year for scheduled maintenance checks and readiness testing (Scheduled MCRT) (as provided in Condition 6c.). Each emergency diesel engine gen-set (Ref. Nos. CLOUD-1 through CLOUD-14) shall not operate more than 500 hours perMachine-extracted normative operating-hours statement; second review pending.p. 10
CLOUD-1 through CLOUD-14500 hours/yearOUD-14) shall not operate more than 27 hours per year for scheduled maintenance checks and readiness testing (Scheduled MCRT) (as provided in Condition 6c.). Each emergency diesel engine gen-set (Ref. Nos. CLOUD-1 through CLOUD-14) shall not operate more than 500 hours per year for all purposes (as provided in Condition 6) combined.Machine-extracted normative operating-hours statement; second review pending.p. 10

Permitted emission limits

2 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.

Inspect 2 transcribed limit rows
ReferencePollutantLimitBasis / scopeSource
visible emissions5 percent opacityvisiblep. 13Machine-extracted from a page line in an older official PDF; literal context: (9 VAC 5-80-1180) 13. Visible Emission Limit – Visible emissions from each emergency diesel engine gen-set (Ref. Nos. CLOUD-1 through CLOUD-14) shall not exceed 5% opacity except during one six-minute period in any one hour in which visible emissions shall not exceed 10% opacity as
visible emissions10 percent opacityvisiblep. 13Machine-extracted from a page line in an older official PDF; literal context: 13. Visible Emission Limit – Visible emissions from each emergency diesel engine gen-set (Ref. Nos. CLOUD-1 through CLOUD-14) shall not exceed 5% opacity except during one six-minute period in any one hour in which visible emissions shall not exceed 10% opacity as determined by EPA Method 9 (reference 40 CFR 60, Appendix A). This condition applies at

DOCUMENT HISTORY

What this document says it changes

amended or superseding permit document

Explicitly supersedes the document dated 2019-04-10.

p. 1, p. 3

QA NOTES

Ambiguity stays visible

  • Machine-extracted candidate. Verify every reused value against the cited official PDF page.
  • Verify table column grouping and any alternative models.
  • Confirm whether the limit is per unit, combined, or limited to testing/maintenance.
  • Older-PDF text fallback; verify row and unit alignment.
← Return to evidence index