Page-cited permit extraction

Remington Technology Park Limited Partnership

Fauquier Co., Virginia

QA status Machine-extractedRelease dated July 29, 2026

EVIDENCE NOTE

What the public record says

A machine-extracted candidate of equipment groups and permit limits stated in Virginia DEQ permit 74172-3, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.

Primary sourceVirginia DEQ permit document

Virginia Department of Environmental Quality

Open original source ↗

Summary fields cite p. 1, p. 3.

What this record does not establish

The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.

How to read the status

Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.

MACHINE-EXTRACTED CANDIDATE

Equipment and limits,
kept separate from actual use.

These page-cited rows are machine-extracted and still require a second manual review. Verify every reused value against the linked official PDF. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.

Permitted equipment

1 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.

ReferenceEquipment / modelCount / ratingFuel / controlsStated operating fieldSource
Gen 1 – Gen 24engine generator setCaterpillar · G3520H natural gas24 units2485 kW eachSee operating-scope tablep. 4Machine-extracted from an official document equipment table; column grouping requires second review.

Operating scope

Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.

ReferenceLimitBasisSource
Gen 1000 hours/yearated as the sum of all emissions from operation under the scenarios above, shall not exceed the limits stated in Condition 14. (9VAC5-80-1180) 10. Operating Hours – The natural gas engine-generator sets (Ref. Nos. Gen 1 – Gen 24) shall not operate more than 2,000 hours per year each, calculated monthly as the sum of each consecutive 12 month period. Compliance for the consecutive 12 month period shall be demonstrated monthly by adding the total for the most recently completed calendar month toMachine-extracted normative operating-hours statement; second review pending.p. 8

Permitted emission limits

14 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.

Inspect 14 transcribed limit rows
ReferencePollutantLimitBasis / scopeSource
each natural gas engine- generator set (Ref. Nos. Gen 1 – Gen 24)NOx as NO27.60 lb/hrhourlyp. 9Machine-extracted from a page line in an older official PDF; literal context: generator set (Ref. Nos. Gen 1 – Gen 24) shall not exceed the limits specified below: Uncontrolled Controlled Nitrogen Oxides (as NO ) 7.60 lb/hr 0.76 lbs/hr 2
each natural gas engine- generator set (Ref. Nos. Gen 1 – Gen 24)NOx as NO20.76 lb/hrhourlyp. 9Machine-extracted from a page line in an older official PDF; literal context: generator set (Ref. Nos. Gen 1 – Gen 24) shall not exceed the limits specified below: Uncontrolled Controlled Nitrogen Oxides (as NO ) 7.60 lb/hr 0.76 lbs/hr 2
each natural gas engine- generator set (Ref. Nos. Gen 1 – Gen 24)NOx as NO211.71 lb/hrhourlyp. 9Machine-extracted from a page line in an older official PDF; literal context: Nitrogen Oxides (as NO ) 7.60 lb/hr 0.76 lbs/hr 2 Carbon Monoxide (CO) 11.71 lb/hr 0.84 lbs/hr Volatile Organic Compounds* (VOC) 3.50 lb/hr 1.27 lbs/hr
each natural gas engine- generator set (Ref. Nos. Gen 1 – Gen 24)NOx as NO20.84 lb/hrhourlyp. 9Machine-extracted from a page line in an older official PDF; literal context: Nitrogen Oxides (as NO ) 7.60 lb/hr 0.76 lbs/hr 2 Carbon Monoxide (CO) 11.71 lb/hr 0.84 lbs/hr Volatile Organic Compounds* (VOC) 3.50 lb/hr 1.27 lbs/hr
each natural gas engine- generator set (Ref. Nos. Gen 1 – Gen 24)VOC3.50 lb/hrhourlyp. 9Machine-extracted from a page line in an older official PDF; literal context: 2 Carbon Monoxide (CO) 11.71 lb/hr 0.84 lbs/hr Volatile Organic Compounds* (VOC) 3.50 lb/hr 1.27 lbs/hr Particulate Matter (PM ) 0.20 lb/hr 0.20 lbs/hr
each natural gas engine- generator set (Ref. Nos. Gen 1 – Gen 24)VOC1.27 lb/hrhourlyp. 9Machine-extracted from a page line in an older official PDF; literal context: 2 Carbon Monoxide (CO) 11.71 lb/hr 0.84 lbs/hr Volatile Organic Compounds* (VOC) 3.50 lb/hr 1.27 lbs/hr Particulate Matter (PM ) 0.20 lb/hr 0.20 lbs/hr
each natural gas engine- generator set (Ref. Nos. Gen 1 – Gen 24)PM0.20 lb/hrhourlyp. 9Machine-extracted from a page line in an older official PDF; literal context: Carbon Monoxide (CO) 11.71 lb/hr 0.84 lbs/hr Volatile Organic Compounds* (VOC) 3.50 lb/hr 1.27 lbs/hr Particulate Matter (PM ) 0.20 lb/hr 0.20 lbs/hr 10
each natural gas engine- generator set (Ref. Nos. Gen 1 – Gen 24)NOx as NO218.24 tpyannualp. 9Machine-extracted from a page line in an older official PDF; literal context: engine-generator sets (Ref. Nos. Gen 1 – Gen 24) for all purposes shall not exceed the limits specified below: Nitrogen Oxides (as NO ) 18.24 tons/yr 2
each natural gas engine- generator set (Ref. Nos. Gen 1 – Gen 24)NOx as NO220.16 tpyannualp. 9Machine-extracted from a page line in an older official PDF; literal context: Nitrogen Oxides (as NO ) 18.24 tons/yr 2 Carbon Monoxide (CO) 20.16 tons/yr Volatile Organic Compounds* (VOC) 30.47 tons/yr
each natural gas engine- generator set (Ref. Nos. Gen 1 – Gen 24)VOC30.47 tpyannualp. 9Machine-extracted from a page line in an older official PDF; literal context: 2 Carbon Monoxide (CO) 20.16 tons/yr Volatile Organic Compounds* (VOC) 30.47 tons/yr Particulate Matter (PM ) 4.80 tons/yr
each natural gas engine- generator set (Ref. Nos. Gen 1 – Gen 24)PM4.80 tpyannualp. 9Machine-extracted from a page line in an older official PDF; literal context: Carbon Monoxide (CO) 20.16 tons/yr Volatile Organic Compounds* (VOC) 30.47 tons/yr Particulate Matter (PM ) 4.80 tons/yr 10
visible emissions5 percent opacityvisiblep. 10Machine-extracted from a page line in an older official PDF; literal context: Page 10 15. Visible Emission Limit – Visible emissions from each natural gas engine-generator sets (Ref. Nos. Gen 1 – Gen 24) exhausts shall not exceed 5% opacity as determined by EPA Method 9 (reference 40 CFR 60, Appendix A). This condition applies at all times except
visible emissions10 percent opacityvisiblep. 10Machine-extracted from a page line in an older official PDF; literal context: during startup, shutdown and malfunction. During startup and shutdown, visible emissions from each natural gas engine-generator sets (Ref. Nos. Gen 1 – Gen 24) shall not exceed 10% opacity except during one 6-minute period in any one hour in which visible emissions shall not exceed 20% opacity as
visible emissions20 percent opacityvisiblep. 10Machine-extracted from a page line in an older official PDF; literal context: During startup and shutdown, visible emissions from each natural gas engine-generator sets (Ref. Nos. Gen 1 – Gen 24) shall not exceed 10% opacity except during one 6-minute period in any one hour in which visible emissions shall not exceed 20% opacity as determined by EPA Method 9 (reference 40 CFR 60, Appendix A).

DOCUMENT HISTORY

What this document says it changes

amended or superseding permit document

Explicitly supersedes the document dated 2019-10-03.

p. 1, p. 3

QA NOTES

Ambiguity stays visible

  • Machine-extracted candidate. Verify every reused value against the cited official PDF page.
  • Verify table column grouping and any alternative models.
  • Confirm whether the limit is per unit, combined, or limited to testing/maintenance.
  • Older-PDF text fallback; verify row and unit alignment.
← Return to evidence index