EVIDENCE NOTE
What the public record says
A machine-extracted candidate of equipment groups and permit limits stated in Virginia DEQ permit 73200-2, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.
The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.
How to read the status
Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.
MACHINE-EXTRACTED CANDIDATE
Equipment and limits, kept separate from actual use.
These page-cited rows are machine-extracted and still require a second manual review. Verify every reused value against the linked official PDF. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.
Permitted equipment
1 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.
Reference
Equipment / model
Count / rating
Fuel / controls
Stated operating field
Source
emergency engine generator set—
7 unitsNo reliable per-unit rating transcribed
diesel fuel oil—
See operating-scope table—
p. 1 ↗Machine-extracted from explicit permit prose: Leland: Attached is a minor amendment to your permit to construct and operate seven diesel engine-driven emergency generators at your computer data center located in Manassas, Virginia, in accordance with the provisions of th
Operating scope
Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.
Reference
Limit
Basis
Source
2279 hours/year
: a. If compliance with the facility-wide NOx emission limit, Condition 10, is determined using the calculation method specified in Condition 11 a, the cumulative hours of operation for all emergency generators (Ref. # EGU 1 through EGU 7) shall be limited to 2279 hours per year, calculated monthly as the sum of each consecutive 12-month period. Compliance for the consecutive 12-month period shall be demonstrated monthly by adding the total for the most recently completed calendar month to theMachine-extracted normative operating-hours statement; second review pending.
5 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.
Inspect 5 transcribed limit rows
Reference
Pollutant
Limit
Basis / scope
Source
NOx as NO2—
46.9 tpyannual
——
p. 5 ↗Machine-extracted from a page line in an older official PDF; literal context: totals for the preceding 11 months b. If compliance with the facility-wide NOx emission limit, Condition 10, is determined using the method specified in Condition 11b, the annual NOx emission limit of 46.9 TPY shall be the limiting factor. Annual NOx emissions shall be calculated on a monthly basis as
NOx as NO2—
46.9 tpyannual
——
p. 7 ↗Machine-extracted from a page line in an older official PDF; literal context: 2 exceed: NOx = 46.9 tons/year. Compliance shall be demonstrated in accordance with Conditions 4 and 11.
visible emissions—
5 percent opacityvisible
——
p. 8 ↗Machine-extracted from a page line in an older official PDF; literal context: (9 VAC 5-80-1180 and 9 VAC 5-50-260) 12. Visible Emission Limit - Visible emissions from each emergency generator (Ref. # EGU1 thru EGU7) shall not exceed 5% opacity except during one six-minute period in any one hour in which visible emissions shall not exceed 10% opacity as determined by the EPA
visible emissions—
10 percent opacityvisible
——
p. 8 ↗Machine-extracted from a page line in an older official PDF; literal context: 12. Visible Emission Limit - Visible emissions from each emergency generator (Ref. # EGU1 thru EGU7) shall not exceed 5% opacity except during one six-minute period in any one hour in which visible emissions shall not exceed 10% opacity as determined by the EPA Method 9 (reference 40 CFR 60, Appendix A). During startup and shutdown, visible .
visible emissions—
20 percent opacityvisible
——
p. 8 ↗Machine-extracted from a page line in an older official PDF; literal context: Method 9 (reference 40 CFR 60, Appendix A). During startup and shutdown, visible . emissions shall not exceed 10% opacity, except for one six-minute interval not to exceed 20% opacity. (9 VAC 5-80-1180, 9 VAC 5-50-260 and 9 VAC 5-170-160)
DOCUMENT HISTORY
What this document says it changes
permit to construct and operate
No superseded-document date is asserted beyond the cited source wording.