Page-cited permit extraction

Gainesville Crossing Data Campus - GCDC

Prince William Co., Virginia

QA status Machine-extractedRelease dated July 29, 2026

EVIDENCE NOTE

What the public record says

A machine-extracted candidate of equipment groups and permit limits stated in Virginia DEQ permit 74241-3, with one-based PDF page citations. Permitted terms do not establish actual operation or emissions.

Primary sourceVirginia DEQ permit document

Virginia Department of Environmental Quality

Open original source ↗

Summary fields cite p. 1, p. 3.

What this record does not establish

The source confirms the document and its stated fields. This profile does not infer actual emissions, compliance history, operating status, facility capacity or environmental impact where those facts are not established by the cited document.

How to read the status

Issued means the agency granted the permit subject to its conditions. It does not mean every permitted unit is operating, that maximum permitted emissions occur, or that later amendments do not exist.

MACHINE-EXTRACTED CANDIDATE

Equipment and limits,
kept separate from actual use.

These page-cited rows are machine-extracted and still require a second manual review. Verify every reused value against the linked official PDF. Page numbers refer to the one-based position in the linked PDF. Blank values are not zero.

Permitted equipment

14 document-defined equipment groups. Counts and per-unit ratings are transcribed; combined capacity is not calculated.

ReferenceEquipment / modelCount / ratingFuel / controlsStated operating fieldSource
1 through 65 Building 1emergency engine generator setMTU · 16V4000 G84S/DS225065 units2250 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
66 through 130 Building 2emergency engine generator setCaterpillar · 3516C65 units2250 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
180 through 228 Building 4emergency engine generator setMTU · 20V4000 DS280049 units2800 kW eachdiesel fuel oilselective catalytic reduction (SCR)See operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
229 through 277 Building 5emergency engine generator setMTU · 20V4000 DS280049 units2800 kW eachdiesel fuel oilselective catalytic reduction (SCR)See operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
SEC1 CSOCemergency engine generator setMTU / John Deere1 units150 kW eachdiesel fuel oilSee operating-scope tablep. 5Machine-extracted from an official document equipment table; column grouping requires second review.
Engine Building Ref. Nos.engine generator set unitsNo reliable per-unit rating transcribedselective catalytic reduction (SCR)See operating-scope tablep. 11Machine-extracted from an official document equipment table; column grouping requires second review.
engine generator set unitsNo reliable per-unit rating transcribedSee operating-scope tablep. 11Machine-extracted from an official document equipment table; column grouping requires second review.
Table 1emergency engine generator set unitsNo reliable per-unit rating transcribeddiesel fuel oilSee operating-scope tablep. 27Machine-extracted from an official document equipment table; column grouping requires second review.
Pollutantengine generator setMTU · 16V4000 DS22501 unitsNo reliable per-unit rating transcribedSee operating-scope tablep. 27Machine-extracted from an official document equipment table; column grouping requires second review.
Table 2emergency engine generator set unitsNo reliable per-unit rating transcribeddiesel fuel oilSee operating-scope tablep. 27Machine-extracted from an official document equipment table; column grouping requires second review.
Pollutantengine generator setMTU · 20V4000 DS28001 unitsNo reliable per-unit rating transcribedSee operating-scope tablep. 27Machine-extracted from an official document equipment table; column grouping requires second review.
131 through 179 Building 3emergency engine generator setMTU · 16V4000 G84S/DS225049 units2250 kW eachdiesel fuel oilSee operating-scope tablep. 30Machine-extracted from an official document equipment table; column grouping requires second review.
Table 1emergency engine generator set unitsNo reliable per-unit rating transcribeddiesel fuel oilSee operating-scope tablep. 48Machine-extracted from an official document equipment table; column grouping requires second review.
Pollutantengine generator setMTU · 16V4000 DS22501 unitsNo reliable per-unit rating transcribedSee operating-scope tablep. 48Machine-extracted from an official document equipment table; column grouping requires second review.

Operating scope

Authorized hours, time windows or an explicit finding that no numeric annual-hour cap was located in the reviewed sections.

ReferenceLimitBasisSource
1 through 130, 180 through 277, and SEC120 hours/yearhen the affected unit is fully integrated with the sources electrical system. (9VAC5-80-1180) [11/21/2025] 9. Operating Hours – a. Each individual emergency diesel engine gen-set (Ref. Nos. 1 through 130, 180 through 277, and SEC1) shall not operate more than 20 hours per year for scheduled maintenance checks and readiness testing (Scheduled MCRT) (as provided in Condition 8.c). b. Each individual emergency diesel engine gen-set (Ref. Nos. 1 through 130 and 180 through 277) shall not operateMachine-extracted normative operating-hours statement; second review pending.p. 9
1 through 130 and 180 through 277500 hours/yearte more than 20 hours per year for scheduled maintenance checks and readiness testing (Scheduled MCRT) (as provided in Condition 8.c). b. Each individual emergency diesel engine gen-set (Ref. Nos. 1 through 130 and 180 through 277) shall not operate more than 500 hours per year for all purposes (as provided in Condition 8) combined.Machine-extracted normative operating-hours statement; second review pending.p. 9
SEC145 hours/yearGainesville Crossing Data Campus (Buildings 1, 2, 4, 5, and CSOC) Registration Number: 74241 November 21, 2025 Page 8 c. The emergency diesel engine gen-set (Ref. No. SEC1) shall not operate more than 45 hours per year for all purposes (as provided in Condition 8) combined. The annual limits for hours of operation shall be calculated monthly as the sum of each consecutive 12-month period. Compliance for the consecutive 12-month periodMachine-extracted normative operating-hours statement; second review pending.p. 10
131 through 17916 hours/yearrted on-site and ending when the affected unit is fully integrated with the sources electrical system. (9VAC5-80-1180) [11/21/2025] 7. Operating Hours – a. Each individual emergency diesel engine gen-set (Ref. Nos. 131 through 179) shall not operate more than 16 hours per year for scheduled maintenance checks and readiness testing (Scheduled MCRT) (as provided in Condition 5.c). b. Each individual emergency diesel engine gen-set (Ref. Nos. 131 through 179) shall not operate more than 500 hourMachine-extracted normative operating-hours statement; second review pending.p. 33
131 through 179500 hours/year9) shall not operate more than 16 hours per year for scheduled maintenance checks and readiness testing (Scheduled MCRT) (as provided in Condition 5.c). b. Each individual emergency diesel engine gen-set (Ref. Nos. 131 through 179) shall not operate more than 500 hours per year for all purposes (as provided in Condition 5) combined. The annual limits for hours of operation shall be calculated monthly as the sum of each consecutive 12-month period. Compliance for the consecutive 12-month periodMachine-extracted normative operating-hours statement; second review pending.p. 33

Permitted emission limits

50 pollutant, unit-group and limit rows. These are permit terms, not measured or actual emissions.

Inspect 50 transcribed limit rows
ReferencePollutantLimitBasis / scopeSource
Ref. Nos. 1 through 65 MTU 16V4000 DS2250NOx as NO243.46 lb/hrhourlyper unitp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 66 through 130 CAT 3516CNOx as NO244.63 lb/hrhourlyper unitp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. SEC1 MTU 6R0113 DS150NOx as NO21.44 lb/hrhourlyp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 1 through 65 MTU 16V4000 DS2250NOx as NO26.95 lb/hrhourlyper unitp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 66 through 130 CAT 3516CNOx as NO22.68 lb/hrhourlyper unitp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. SEC1 MTU 6R0113 DS150NOx as NO20.41 lb/hrhourlyp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 1 through 65 MTU 16V4000 DS2250VOC2.58 lb/hrhourlyper unitp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 66 through 130 CAT 3516CVOC1.16 lb/hrhourlyper unitp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. SEC1 MTU 6R0113 DS150VOC0.052 lb/hrhourlyp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 1 through 65 MTU 16V4000 DS2250PM0.93 lb/hrhourlyper unitp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 66 through 130 CAT 3516CPM0.31 lb/hrhourlyper unitp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. SEC1 MTU 6R0113 DS150PM0.052 lb/hrhourlyp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 1 through 65 MTU 16V4000 DS2250PM100.96 lb/hrhourlyper unitp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 66 through 130 CAT 3516CPM100.47 lb/hrhourlyper unitp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. SEC1 MTU 6R0113 DS150PM100.052 lb/hrhourlyp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 1 through 65 MTU 16V4000 DS2250PM2.50.96 lb/hrhourlyper unitp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 66 through 130 CAT 3516CPM2.50.47 lb/hrhourlyper unitp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. SEC1 MTU 6R0113 DS150PM2.50.052 lb/hrhourlyp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 180 through 277 MTU 20V4000 DS2800NOx as NO27.11 lb/hrhourlyp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 180 through 277 MTU 20V4000 DS2800VOC3.84 lb/hrhourlyp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 180 through 277 MTU 20V4000 DS2800PM1.13 lb/hrhourlyp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 180 through 277 MTU 20V4000 DS2800PM101.28 lb/hrhourlyp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 180 through 277 MTU 20V4000 DS2800PM2.51.28 lb/hrhourlyp. 12Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. SEC1 All OperationsNOx as NO20.032 tpyannualp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 1 through 130 and 180 through 277NOx as NO277.95 tpyannualp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. SEC1 All OperationsNOx as NO20.0092 tpyannualp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 1 through 130 and 180 through 277NOx as NO238.02 tpyannualp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. SEC1 All OperationsVOC0.0012 tpyannualp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 1 through 130 and 180 through 277VOC38.57 tpyannualp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. SEC1 All OperationsPM0.0012 tpyannualp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 1 through 130 and 180 through 277PM13.97 tpyannualp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. SEC1 All OperationsPM100.0012 tpyannualp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 1 through 130 and 180 through 277PM1014.17 tpyannualp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. No. SEC1 All OperationsPM2.50.0012 tpyannualp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 1 through 130 and 180 through 277PM2.514.17 tpyannualp. 13Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 131 through 179 MTU 16V4000 DS2250NOx as NO243.46 lb/hrhourlyper unitp. 35Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 131 through 179 MTU 16V4000 DS2250NOx as NO26.95 lb/hrhourlyper unitp. 35Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 131 through 179 MTU 16V4000 DS2250VOC2.58 lb/hrhourlyper unitp. 35Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 131 through 179 MTU 16V4000 DS2250PM0.93 lb/hrhourlyper unitp. 35Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 131 through 179 MTU 16V4000 DS2250PM100.96 lb/hrhourlyper unitp. 35Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 131 through 179 MTU 16V4000 DS2250PM2.50.96 lb/hrhourlyper unitp. 35Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 131 through 179 All Operations (All Units Combined)NOx as NO216.69 tpyannualcombinedp. 35Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 131 through 179 All Operations (All Units Combined)NOx as NO28.24 tpyannualcombinedp. 35Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 131 through 179 All Operations (All Units Combined)VOC8.36 tpyannualcombinedp. 35Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 131 through 179 All Operations (All Units Combined)PM3.03 tpyannualcombinedp. 35Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 131 through 179 All Operations (All Units Combined)PM103.07 tpyannualcombinedp. 35Machine-extracted from an official permit limit table; header grouping requires second review.
Ref. Nos. 131 through 179 All Operations (All Units Combined)PM2.53.07 tpyannualcombinedp. 35Machine-extracted from an official permit limit table; header grouping requires second review.
visible emissions5 percent opacityvisiblep. 36Machine-extracted from a page line in an older official PDF; literal context: Page 9 13. Visible Emission Limit – Visible emissions from each emergency diesel engine gen-set (Ref. Nos. 131 through 179) exhausts shall not exceed 5% opacity except during one 6- minute period in any one hour in which visible emissions shall not exceed 10% opacity as
visible emissions10 percent opacityvisiblep. 36Machine-extracted from a page line in an older official PDF; literal context: 13. Visible Emission Limit – Visible emissions from each emergency diesel engine gen-set (Ref. Nos. 131 through 179) exhausts shall not exceed 5% opacity except during one 6- minute period in any one hour in which visible emissions shall not exceed 10% opacity as determined by EPA Method 9 (reference 40 CFR 60, Appendix A). This condition applies
visible emissions20 percent opacityvisiblep. 36Machine-extracted from a page line in an older official PDF; literal context: During startup and shutdown, visible emissions from each emergency diesel engine gen-set shall not exceed 10% opacity except during one 6-minute period in any one hour in which visible emissions shall not exceed 20% opacity as determined by EPA Method 9 (reference 40 CFR 60, Appendix A).

DOCUMENT HISTORY

What this document says it changes

amended or superseding permit document

Explicitly supersedes the document dated 2024-10-07.

p. 1, p. 3

QA NOTES

Ambiguity stays visible

  • Machine-extracted candidate. Verify every reused value against the cited official PDF page.
  • Verify table column grouping and any alternative models.
  • Confirm whether the limit is per unit, combined, or limited to testing/maintenance.
  • Confirm multi-row and merged-column header association.
  • Older-PDF text fallback; verify row and unit alignment.
← Return to evidence index